HomeMy WebLinkAboutA15-0050_FAPT_1432758480.pdf April 1, 2003 DN-6833•H-110
0
R®
FAPT-751
N OT I F I E R Acclimate PIusTM Multi-Sensor
Low-Profile Intelligent Detector
Section: Intelligent/Addressable Devices
GENERAL California
The NOTIFIER FAPT-751 Acclimate PlusTM detector is an intel-
ligent,addressable,multi-sensing,low-profile detector designed : Marshal
for use on the NOTIFIER AFP 300,AFP 400,AFC 600(classic [4-`1 7272-0028:208
mode only),ONYXTM Series NFS-640 and NFS-3030(classic or 7272-0028:206
CS308
FlashScan®modes),AFP1010,and AM2020 Fire Alarm Control LISTED (FAPT-751A)
Panels. S1115 •••/
The Acclimate PIusTM detector uses a combination of photo- MARYLAND
electric and thermal sensing technologies that are designed to MEA State Fire Marshal LISTED
increase immunity to false alarms. Unlike traditional intelligent Permit# 2046
detectors, the Acclimate PlusTM detector has a microproces- 229-00-E XF1747/R3
sor in the detector head that processes alarm data. As a re-
•
sult,the Acclimate PlusTM detector adjusts its sensitivity auto •
-
matically, without needing operator intervention.
Areas where the Acclimate Plus TM detector is especially use-
ful include office complexes,schools,college campuses,manu- 7 •
facturing and industrial facilities,and anywhere else the use of f
a particular area may change. One day a conference room, I .A
tomorrow a kitchen,the next day a copy machine room—the 1
Acclimate Plus TM detector automatically adjusts its sensitivity a',\ ;
to the environment!
KFEATURES
• Automatically adjusts sensitivity levels without the need for
operator intervention or programming.Sensitivity increases
with heat.
• Combination photo and thermal technology.
• Microprocessor-based technology.
• FlashScan®(NFS-640 and NFS-3030)and classic system - ssaaPno,.;P9
(NFS-640, NFS-3030, AFP-300, AFP-400, AFC-600,
AFP1010, and AM2020)compatible. systems;fixed-sensitivity levels:1,2,and 4%/ft.with Legacy
• Sleek, low-profile design. systems; 0.5, 1, 2, 3, and 4%/ft. with ONYXTM systems.
• Rotary, decimal addressing (1 -99 on current classic sys- Operating voltage range: 15-32 volts DC peak.
tems, 1 - 159 on FlashScan®systems). Standby current (max. avg.): 250 NA @ 24 VDC (without
• Addresses can be viewed and changed without the need for communication); 360 pA @ 24 VDC (one communication ev-
electronic programmers. ery 5 seconds with LED enabled).
• Dual bi-color LED design provides 360° viewing angle. Maximum alarm current(LED on):10 mA @ 24 VDC("ON").
• In FlashScan®, LEDs flash GREEN in Standby for normal Loop resistance:40 ohms maximum;varies according to con-
condition. trol panel used. Refer to panel installation manuals.
• LEDs lock RED when in Alarm. Operating humidity range: 10%-93% non-condensing.
• Several base options,including relay,isolator,and sounder. Operating temperature range: 0° to 38°C (32°to 100°F).
• Built-in functional test switch activated by external magnet. Air velocity rating: 0 to 4,000 ft/min (20.32 m/sec).
• Listed to UL 268. Height: 1.66 inches (4.216 cm).
• Capable of heat-only alarm mode,enabled by a special com Diameter: 4.1" (10.4 cm) in B501 base; 6.1" (15.5 cm) in
mand from the panel. Smoke alarms are ignored. g710LP base.
• Backwards-compatible on most panels. Weight: 3.6 oz. (104 g).
• Low-temperature signal at 45°F/7.22°C (+/- 10°F/5.54°C). Thermal sensor: 135°F (57°C)fixed.
SPECIFICATIONS INSTALLATION
Sensitivity:auto-adjusting levels:1 to 2%/ft.and 2 to 4%/ft.
with Legacy systems;1 to 2,2 to 3,and 3 to 4%/ft.with ONYX TM The FAPT-751 plug-in detector uses a separate base to sim-
plify installation, service, and maintenance. A special tool al-
FlashScan®is a registered trademark and ONYXTM and Accli- lows maintenance personnel to plug-in and remove detectors
mate PlusTM are trademarks of NOTIFIER. without using a ladder.Mount base on a box at least 1.5"(38.1
NOTIFIER®is a Honeywell company.
This document is not intended to be used for installation purposes.We try to keep our
Iso
9001
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information,contact NOTIFIER. Phone:(203)484-7161 FAX:(203)484-7118 C E Fi r I VI EEO
0NOTI Fl E Rff 12 Clintonville Road,Northford,Connecticut 06472 ENGINEERING&MANUFACTURING
DN-6833•04/01/03— Page 1 of 2
mm)deep. Suitable mounting base boxes include: B224RB Intelligent relay base
• 4" (101.6 mm)square box. B224BI Intelligent isolator base. Isolates SLC from loop
• 3-1/2" (88.9 mm)or 4" (101.6 mm)octagonal box. shorts.
• Single-gang box(except relay or isolator base). ACCESSORIES:
APPLICATION NOTE:The FAPT-751 detector has the unique SDG-773 Smoke detector guard.This guard,although me-
ability to adjust sensitivity according to the environment,based chanically compatible, is NOT UL-compatibility
on heat and smoke levels.Avoid installing these detectors in Listed with the FAPT-751.
locations that are susceptible to rapid and high temperature F110 Retrofit replacement flange for BX-501 base.
changes.An example of an incorrect application would be near Converts BX-501 base for use with low-profile
or in line with the output of a self-contained heater. detectors.
ORDERING INFORMATION RA400Z Remote LED annunciator.3-32 VDC.Fits U.S.
single-gang electrical box.For use withB710LP
FAPT-751 Low-profile intelligent multi-sensor detector. and B501 bases only.
AVAILABLE BASES: SMK400 Surface mounting kit provides for entry of sur-
B710LP Standard U.S.6.2"(157.48 mm)low-profile base. face wiring conduit.For use withB501 base only.
B710LPBP Standard U.S.6.2"(157.48 mm)low-profile base. RMK400 Recessed mounting kit.For use with B501 base
Package of ten (10). only.
B501 Standard European 4" (101.6 mm) flangeless M02-04-01 Test magnet.
base. XR-2 Detector removal tool.Allows installation and/or
B501 BP Standard European 4" (101.6 mm) flangeless removal of 700 Series detector heads from bases
base. Package of ten (10). in high ceiling applications.
B501 BH Sounder base, includes B501 base above. XP-4 Extension pole for XR-2. Comes in three 5-ft.
B501BHT Same as B501 BH, but includes temporal (1.524 m)sections.
sounder.
751-6710.tif
6833pho2jpg ���
- - . . . - .-. cr:.y
I . _ r. ,
.fa•• M1•1.
r
. {I
IVENIMMI MINN.-7_ ipii.4. opIMEN NIMIRIZ.-ere.t •
}l
�' - •
.Cr ..
.+ 11111
++ . .
I
:1•':7. • . i ..' • FAPT-751 with B710LP base
- k
:fir . . ' ,6 • elm_ __ ."--t-iL,:.--_,77
--r
k
...F.;
FAPT-751 with RMK400 recessed mounting kit
,-.:4;!-.....1.'.-" ,..44•;_.L.....ti
• •• L+4^•-• - r• . +}rt REMOTE ANNUNCIATOR
FAPT-751, cover removedMI
+_
MINIMMEMI
( 891O1� 1g9
6 �✓ 1
5 12 6 Listed \ —
E1ii
,3 5 Compatible ``
0
a6l 10I111f1.
\ii
/k Q CONTROL 3`~2 ��_3 ='?
3 1y 3 - PANEL C :•: w. '�� C)I�.: .1 C.
_
6833addr.wmf
N ,
address dial on
back of detector
J
OPTIONAL RETURN LOOP
wiring diagram
} 4762wirl.if
(standard base)
Page 2 of 2 — DN-6833•04/01/03