HomeMy WebLinkAboutA15-0061_A-FA000_1437147180.pdf 41° Cir I/4
4. X
Address Type of Device Level Description LEGEND : Arm
0
001 MONITOR MAIN SPRINKLER WATERFLOW
002 MONITOR MAIN SPRINKLER TAMPER SWITCH SYMBOL DEVICE MANUFACTURER/PART# MOUNTING Vail Fire&Emergency Services
07/17/15
003 CO/SMOKE DETECTOR MAIN REC ROOM FACP Caddx (NetworkX) NX-8E
004 SMOKE DETECTOR MAIN MASTER BEDROOM Fire Alarm Control Panel w/NX-2192 Addressable Card Mount on wall in manufacturer backbox
005 CO/SMOKE DETECTOR MAIN ENTRY OUTSIDE MASTER
006 CO/SMOKE DETECTOR MAIN HALL OUTSIDE BEDROOMS KP
007 SMOKE DETECTOR MAIN NORTH BEDROOM LCD Keypad/Annunciator Caddx (NetworkX) NX-148E Mount on wall in manufacturer backbox
008 SMOKE DETECTOR MAIN SOUTH BEDROOM
009 HEAT DETECTOR UPPER GARAGE Combination Smoke &
010 CO/SMOKE DETECTOR UPPER FAMILY ROOM Q Heat Detector w/Sounder System Sensor i3 series 4WTA—B 4" square box
011 CO/SMOKE DETECTOR UPPER LIVING ROOM
012 Combination Smoke and
013 OwCO Detector w/Sounder System Sensor i4 series COSMO-4W 4" square box
014
015 O System Sensor 5601P
016 Heat Detector w/4193SN Addressable module 4" square box
z
017 0
1=
018 ECosmo Interface Module COSMOD4W
019 0
020 co
KB
021 Knox Box z
022 0
023
024 aHorn/Strobe, weatherproof System Sensor P2RK Weatherproof backbox i
025
NOTE: LEVEL WILL BE INCLUDED IN DEVICE ADDRESS DESCRIPTION. .
w
1—
Battery Calculations 0
Caddx NX-$E
Standby
Number of Current Total Current z
Device Type Devices (Amps) (Amps) D = 4—WIRE DATA/POWER, 4—#16AWG (2 PAIR)
Main FACP CPU 1 X 0.075 = 0.075
-NX-14E LCD Keypad 2 X 0.075 = 0.15 X = 2—WIRE DATA, 2—#16AWG CO w
NX-2192 Addressable Interface Card (max draw) 1 X 0.17 = 0.17 o Z
SUM COLUMN FOR STANDBY LOAD 0.395 = 'AMPS N = 2—WIRE SOUNDER CIRCUIT, 2—#18AWG rn
Alarm Load Z = 2—WIRE DATA CIRCUIT, 2—#16AWG o a
Number of Current Total Current EOL EOL
Device Type Devices (Amps) - (Amps) KP = KEYPAD CIRCUITING, 4—#18AWG 21co > 0) of oo
Main FACP CPU 1 X 0.14 - 0.14 RISER NOTES: c 1---
0
NX-14E LCD Keypad 2 X 0.11 = 0.22 _ J
NX 21920.)Addressable Interface Card 1 X 0.17 = 0.17 D D L _1
Sounders (integral with detectors) 8 X 0.015 = 0.12 1. REFER TO PANEL INSTALLATION MANUAL FOR
Outside Horn/Strobe 1 X 0.239 = 0 23g MORE INFORMATION. L1
SUM COLUMN FOR ALARM LOAD 0.889 - AMPS 2. WIRE SIZE MAY BE VARIED, PROVIDED IT MEETS NX-8E L,N L,N c N
MANUFACTURERS SPECIFICATIONS. CONTROL PANEL 0V)
Standby Load Required Standby Time in Hours 3. VERIFY WIRING OF SYSTEM SENSOR COSMOD4W (NP) (NP) C
Current (Amps) PRIOR TO INSTALLATION. WIRING DIAGRAM IS
0.395 X 24 = 9.48 INCLUDED SUBMITTAL BOOKS. 4193 Z 10
Alarm Load Required Alarm Time in Hours C
Current (Amps) (15 MINUTES) 120VAC DEDICATED POWER
0.889 X 0.25 = 0.22 4193 Z FLOW SWITCH
Add Standby and Alarm Load for Required Z
Ampere Hour Battery 9.70
4193 TAMPER SWITCH C
Multiply by the Derating Factor of 1.2 I I - TELEPHONE LINE N WP
Total Ampere Hours Required 11.64 BELL EOLR
OUTPUT +
Batteries Provided: 12AH 0
L.
Note: The maximum draw for the NX-2192 Addressable Interface Card was used, This accounts for all RISER DIAGRAM DAOUTPUM KP KEYPAD KEYPAD N
initiating devices (smokes and heats)attached to the system. Therefore, each device is not individually a) + lo
accounted for. 0d-
C '- o
i1 00
0
GENERAL NOTES: 0N
1 . ALL EQUIPMENT IS TO BE INSTALLED AND TESTED IN ACCORDANCE WITH 0
r — CC
o 0
o
MANUFACTURER STANDARDS, FIRE DEPARTMENT REQUIREMENTS AND NFPA 72. CO ,.
2. REFER TO MANUFACTURERS DATA SHEETS AND INSTALLATION INSTRUCTIONS FOR m 0
FURTHER INFORMATION REGARDING PRODUCT INSTALLATION, WIRING DIAGRAMS, ,, m
PROGRAMMING AND DEVICE OPERATION. 0_ u_
00 + ,
v
iot
��ll
r
r, 3523 - ,;c:11,--,
te.• - :: 0 :4'
.
•
IONP1
0
PROJECT INFORMATION : z
401 HEAVER DAM ROAD , UNIT A =
SEQUENCE OF0 Q w w cn
OPERATIONS: N J z Z VAI L, COLORADO
Q =
w < o 5o (no FIRE ALARM SYSTEIV
J C9 1 w 1,77
H (n M z0 Q F
m NQ ¢ wQ w L.L
D r cn a o o 0 z w o AHJ: VAIL FIRE & EMERGENCY SERVICES Z 2 0
v Q z N z z w w CO
APPLICABLE CODES: 2010 NFPA 72, 2012 IFC, 2012 IBC W W
Q E � w Q I I- 0 .. W
,� 1- o 1- o 1- o o c� ow OCCUPANCY: GROUP R CCI—
w � z � z � z w l w w 0
DEVICE a No No r„ o QN ao a� USE: DUPLEX Q p
zM z
DESCRIPTION >— Q Q Q > w > z > z O <
Q cto w o Eto a m a o 0 o FIRE ALARM SYSTEM FOR DUPLEX UNIT. SYSTEM WILL INCLUDE A NEW i co
l— l— l— l— l— H
ADDRESSABLE FACP. COMBINATION SMOKE/HEAT DETECTORS WILL BE w 0
SMOKE DETECTOR X X X INSTALLED IN SLEEPING ROOMS WITH SMOKE/HEAT/CO DETECTORS ON cL
> J Q Cl
W
STAIRWELL LANDINGS AND AREAS OUTSIDE OF SLEEPING ROOMS. A HEAT < 0 J z
HEAT DETECTOR X X X DETECTOR WILL BE INSTALLED IN THE GARAGE. DETECTORS HAVE W 0 < 0
INTEGRAL SOUNDERS. A KNOX BOX AND OUTSIDE HORN/STROBE WILL CO J w
CARBON MONOXIDE DETECTOR X X X BE MOUNTED AT THE FDC. THE HOME IS SPRINKLERED AND THE FACP N— Q 0 W
WILL MONITOR FLOW/TAMPER. > LL 0
SPRINKLER WATERFLOW SWITCH X X X X FIRE PROTECTION ENGINEER: SHEET DESCRIPTION:
DEBORAH SHANER, P.E., SHANER LIFE SAFETY FIRE ALARM PLAN
SPRINKLER TAMPER SWITCH X X PO BOX 1073, FRISCO, CO 80443
PHONE: 970-409-9082 DRAWN BY: DATE:
POWER LOSS, OPEN CIRCUIT, GROUND FAULT X X FAX: 970-797- 1898 DLS 6/16/15
SHEET#:
FA-000