HomeMy WebLinkAboutA15-0084_Brook Tree Sheet 4 cert_1448403720.pdf 4,4011 : � 4, C .4 r7r IS ar System 2 (Bldgs C & D ,,,�,Standby Battery Calculations Based on Remote Station Type System (NEPA 72, 2013) Fire Vail &EmE gency Services 11/24/15 5 24 Hours Standby Phase 11 5 minute Alarm Phase II Scope of Work V. System 2 (Bldgs C & D) Modify existing Fire Alarm System to meet current adopted building codes (International Building Code 2012 and adopted amendments) Vit System 1 (Add 55 Smoke Detectors (with Sounder Base) and 2 Power Supplies) Standby (ea) Standby (total) Alarm (ea) Alarm (total) Cable Specifications moa if, /410/7 `O ,,42 Phase I Current (Amps) Current (Amps) Current (Amps) Current (Amps) Signal Line Circuit Style 4 16 awg 2 Conductor FPL �t�t 1 ea FACP (5820XL) 0.215 0.215 0.385 0.385 Sounder Base Power 16 awg 2 Conductor FPL �� . 24ea Addressable Smoke/Heat/CO Detector 0.0003 0.0072 0.0072 0.17 4.14147;,,,,, � 9ea Addressable Pull Station 0.0003 0.0027 0.0003 0.0027I Addressable Point Configurations 24ea Addressable Sounder Base 0.0003 0.0072 0. 14 3.36 44'6 Phase I Phase II Phase I Phase II �NFACP Buildin C Buildin C Buildin D Buildin D Site Plan 9' 9' 9' 9 -�©/- :' NTS Phase II # Device Type Apt# Level # Device Type Apt# Level # Device Type Apt# Level # Device Type Apt# Level I! 1 Smoke/Heat/CO Detector Unit 1 Garden 41 Smoke/Heat/CO Detector Unit 1 Garden 10 Smoke/Heat/CO Detector Unit 15 Garden 56 Smoke/Heat/CO Detector Unit 1 Garden 55ea Addressable Smoke/Heat/CO Detector 0.0003 0.0165 0.0072 0.396 2 Smoke/Heat/CO Detector Unit 2 Garden 42 Smoke/Heat/CO Detector Unit 2 Garden 11 Smoke/Heat/CO Detector Unit 1 1 57 Smoke/Heat/CO Detector Unit 2 Garden 2ea Addressable Power Supply 0.04 0.08 0. 16 0.32 3 Smoke/Heat/CO Detector Unit 3 Garden 43 Smoke/Heat/CO Detector Unit 3 Garden 12 Smoke/Heat/CO Detector Unit 2 1 58 Smoke/Heat/CO Detector Unit 3 Garden 4 Smoke/Heat/CO Detector Unit 4 1 44 Smoke/Heat/CO Detector Unit 4 1 13 Smoke/Heat/CO Detector Unit 3 1 59 Smoke/Heat/CO Detector Unit 4 Garden 5 Smoke/Heat/CO Detector Unit 5 1 45 Smoke/Heat/CO Detector Unit 5 1 14 Smoke/Heat/CO Detector Unit 4 1 60 Smoke/Heat/CO Detector Unit 5 Garden 6 Smoke/Heat/CO Detector Unit 6 1 46 Smoke/Heat/CO Detector Unit 6 1 15 Smoke/Heat/CO Detector Unit 5 1 61 Smoke/Heat/CO Detector Unit 6 Garden 7 Smoke/Heat/CO Detector Unit 7 3 47 Smoke/Heat/CO Detector Unit 7 2 16 Smoke/Heat/CO Detector Unit 6 1 62 Smoke/Heat/CO Detector Unit 15 Garden 8 Smoke/Heat/CO Detector Unit 8 3 48 Smoke/Heat/CO Detector Unit 8 2 17 Smoke/Heat/CO Detector Unit 7 1 63 Smoke/Heat/CO Detector Unit 1 1 SYMBOLS 9 Smoke/Heat/CO Detector Unit 9 3 49 Smoke/Heat/CO Detector Unit 9 2 18 Smoke/Heat/CO Detector Unit 8 3 64 Smoke/Heat/CO Detector Unit 1 1 50 Smoke/Heat/CO Detector Unit 7 3 19 Smoke/Heat/CO Detector Unit 9 3 65 Smoke/Heat/CO Detector Unit 2 1 Totals 0.33 4.63 31 Manual Station NA Garden 51 Smoke/Heat/CO Detector Unit 7 3 20 Smoke/Heat/CO Detector Unit 10 3 66 Smoke/Heat/CO Detector Unit 2 1 PHASE I 24 Hours 5 minutes 32 Manual Station NA 1 52 Smoke/Heat/CO Detector Unit 8 3 21 Smoke/Heat/CO Detector Unit 11 3 67 Smoke/Heat/CO Detector Unit 3 1 33 Manual Station NA 1 53 Smoke/Heat/CO Detector Unit 8 3 22 Smoke/Heat/CO Detector Unit 12 3 68 Smoke/Heat/CO Detector Unit 3 1 FACP FIRE ALARM CONTROL PANEL Standby Alarm Total 34 Manual Station NA 2 54 Smoke/Heat/CO Detector Unit 9 3 23 Smoke/Heat/CO Detector Unit 13 3 69 Smoke/Heat/CO Detector Unit 4 1 Current (AH) Current (AH) Battery Capacity (AH) 55 Smoke/Heat/CO Detector Unit 9 3 24 Smoke/Heat/CO Detector Unit 14 3 70 Smoke/Heat/CO Detector Unit 4 1 2O## SMOKE/HEAT/CO DETECTOR(ADDRESSABLE) 71 Smoke/Heat/CO Detector Unit 5 1 7.92 0.38 8.3 35 Manual Station NA Garden 72 Smoke/Heat/CO Detector Unit 5 1 ElPULL STATION(ADDRESSABLE) Battery Derating (20%) 9.6 36 Manual Station NA Garden 73 Smoke/Heat/CO Detector Unit 6 1 37 Manual Station NA 1 74 Smoke/Heat/CO Detector Unit 6 1 38 Manual Station NA 1 75 Smoke/Heat/CO Detector Unit 7 1 Battery provided: 12 AH 39 Manual Station NA 2 76 Smoke/Heat/CO Detector Unit 8 2 PHASE II 77 Smoke/Heat/CO Detector Unit 9 2 78 Smoke/Heat/CO Detector Unit 10 2 ® 79 Smoke/Heat/CO Detector Unit 11 2 SMOKE/HEAT/CO DETECTOR(ADDRESSABLE) 80 Smoke/Heat/CO Detector Unit 12 2 81 Smoke/Heat/CO Detector Unit 13 2 Voltage Drop Calculations For worst case voltage drop, these calculations assume that the entire current load is at the end of the circuit. 82 Smoke/Heat/CO Detector Unit 14 2 83 Smoke/Heat/CO Detector Unit 8 3 Ohms Law method used for the following calculations 84 Smoke/Heat/CO Detector Unit 8 3 85 Smoke/Heat/CO Detector Unit 9 3 NAC Circuit Cable - 16 awg FPLP (Ohms/Ft = .00508) from NEC 2011, Chapter 9, Table 8 86 Smoke/Heat/CO Detector Unit 9 3 87 Smoke/Heat/CO Detector Unit 10 3 88 Smoke/Heat/CO Detector Unit 10 3 Kenneth L. Buffington 89 Smoke/Heat/CO Detector Unit 11 3 NICET Level IV Fire Alm Stems 90 Smoke/Heat/CO Detector Unit 11 3 Certification#113575 System 2 (P/S NACI - Building C) System 2 (P/S NACI - Building D) 92 Smoke/Heat/CO Detector Unit 12 3 Smoke/Heat/CO Detector Unit 12 3 Curtis F. Toon Smoke/Heat/CO Detector Unit 13 3 NICET Level IV Total NAC# 1 Circuit distance=200' ((200'x 2)x 0.00508)=2.03 Ohms Total NAC# 1 Circuit distance =200' ((200'x 2)x 0.00508)=2.02 Ohms 94 moeaFire Alarm Systems Total Resistance=2.03 Ohms Total Resistance=2.03 Ohms Smoke/Heat/CO Detector Unit 13 3 Certification#107227 95 Smoke/Heat/CO Detector Unit 14 3 6 total Sounder Base Units @ 0.14 Amps=0.84 Amps 12 total Sounder Base Units @ 0.14 Amps= 1.68 Amps Total Current=0.84 Amps Total Current= 1.68 Amps (Resistance)2.03 Ohms X(Current) 0.84 Amps = 1.71 Volts (Resistance)2.03 Ohms X(Current) 1.68 Amps = 3.41 Volts Lo 1.71 Volts Total Voltage Dropthis Circuit 3.41 Volts Total Voltage Dropthis Circuit SYSTEM 2 co 9' g One Line Riser Diagrams Nominal Voltage=24 VDC Nominal Voltage=24 VDC - 85%of Nominal Voltage=20.4 VDC 85%of Nominal Voltage=20.4 VDC (20.4) - (1.71) = 18.69 End of Line Voltage = 18.69 VDC (20.4) - (3.41) = 16.99 End of Line Voltage = 16.99 VDC E Operating Voltage Range 16 - 33 VDC Operating Voltage Range 16 - 33 VDC BUILDING C BUILDING D FACP 7 8 9 18 19 20 21 22 23 24 5820XL O O O © O O O O O O co C!) Flexputs © © © © © © © © © © © © © © © © © © 4 Q > Unit 7 Unit 8 Unit 9 Unit 8 Unit 9 Unit 10 Unit 11 Unit 12 Unit 13 Unit 14 M System 2 (P/S NAC2 - Building C) System 2 (P/S NAC2 - Building 0) _ 3rd Level 50 51 I�53 AO 55 83 84 8 86 87 88 89 90 91 92 9 94 95 Total NAC# 1 Circuit distance=250' ((250'x 2)x 0.00508)=2.54 Ohms Total NAC# 1 Circuit distance =200' ((200'x 2)x 0.00508)=2.03 Ohms I/O 1 Sounder Base Pwr (Bldg C) i 3rd Level 2 Total Resistance=2.54 Ohms Total Resistance=2.03 Ohms I/O 2 Sounder Base Pwr (Bldg C) 1 39 CZZQ 9 total Sounder Base Units @ 0.14 Amps= 1.26 Amps 8 total Sounder Base Units @ 0.14 Amps= 1.12 Amps I/O 3 Sounder Base Pwr (Bldg D) 34 ❑ Total Current= 1.26 Amps Total Current= 1.12 Amps ❑ 4 4 4 4 4 4 4 4 © (Resistance)2.54 Ohms X(Current) 1.26 Amps = 3.2 Volts (Resistance)2.03 Ohms X(Current) 1.12 Amps =2.27 Volts X00 Sounder Base Pwr (Bldg D) NAC 47 -a 49 NAC° 76 77 78 79 80 81 82 a 3.2 Volts Total Voltage Drop this Circuit 2.27 Volts Total Voltage Drop this Circuit I/O 6 2nd Level 2nd Level NAC 4 0 Nominal Voltage=24 VDC Nominal Voltage=24 VDC - x 85%of Nominal Voltage=20.4 VDC 85%of Nominal Voltage=20.4 VDC 32 33 4 5 6 11 12 13 14 15 16 17 37 38 m` is (20.4) - (3.2) = 17.2 End of Line Voltage = 17.2 VDC (20.4) - (2.27) = 18.13 End of Line Voltage = 18. 13 VDC El ❑ OO OO OO OO OO OO OO OO OO OO ❑ ❑ 2 Operating Voltage Range 16 - 33 VDC Operating Voltage Range 16 - 33 VDC Silent Knight Unit 4 Unit 5 Unit 6 Silent Knight Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Unit 6 Unit 7 5 Addressable 4 4 4 Addressable 4 4 4 4 4 4 4 4 4 4 4 4 4 Supply 1st Level 44 �5 46 1st Level 63 64 65 66 67 68 69 70 71 72 7 74 75 Power Su I Power Supply ii � I0 l- NAC 2 31 1 2 3 NAC 2 � 10 35 36 -Th U System 2 (P/S NAC3 - BuildingD) ❑ 4 4 4 4 O ❑ ❑ 0_ co y / nit 1 .nit 2 . nit 3 NAC 3 NAC 1 it 15 Total NAC# 1 Circuit distance=250' ((250'x 2)x 0.00508)=2.54 Ohms 4 4 © 56 57 58 59 60 61 Total Resistance=2.54 Ohms Garden Level NAC 1 41 42 43 NAC 4 Garden Level NAC 2 62 12 total Sounder Base Units @ 0.14 Amps = 1.68 Amps °'s z Total Current= 1.68 Ampsf- F g = o 2 0 = Uw. (Resistance)2.54 Ohms X(Current) 1.68 Amps =4.27 Volts CD N Er- _ �L N N L 4.27 Volts Total Voltage Drop this Circuit >- 5 �, °3 X H cL Nominal Voltage=24 VDC �� 0 '' m a N o 85%of Nominal Voltage=20.4 VDC StandbyBatte Calculations Based on Remote Station Type System (NEPA 72, 2013) �''s Digitally signed by Paul 0 b a� 2 (20.4) - (4.27) = 16.13 End of Line Voltage = 16. 13 VDC 24 Hours Standby �o`'° 'o �; ���`'�, Naumann Operating Voltage Range 16 - 33 VDC :. / 9�ti.o s; 5 minute Alarm 25072 DN: cn=Paul Naumann, o, ou, :. s email=pdnaumann@aol.com, `'•. °, ... . . c=U S \.., dNAl.E�.= Date: 2015.11 .07 21 :16:31 -07'00' System 2 (P/S NAC4 - Building 0) Power Supply (Building C) Power Supply (Building D) (I) Total NAC# 1 Circuit distance=250' ((250'x 2)x 0.00508)=2.54 Ohms Standby (ea) Standby (total) Alarm (ea) Alarm (total) Standby (ea) Standby (total) Alarm (ea) Alarm (total) Total Resistance=2.54 Ohms Phase II Current (Amps) Current (Amps) Current (Amps) Current (Amps) Phase II Current (Amps) Current (Amps) Current (Amps) Current (Amps) n P.11 8 total Sounder Base Units @ 0.14 Amps= 1.12 Amps lea Addressable Power Supply 0.04 0.04 0.16 0.16 lea Addressable Power Supply 0.04 0.04 0.16 0.16 Total Current= 1.12 Amps 15ea Addressable Sounder Base 0.0003 0.0045 0.14 2.1 40ea Addressable Sounder Base 0.0003 0.012 0.14 5.6 (Resistance)2.54 Ohms X(Current) 1.12 Amps =2.84 Volts 2.84 Volts Total Voltage Drop this Circuit Totals 0.04 2.26 Totals 0.053 5.76 Nominal Voltage=24 VDC 24 Hours 5 minutes Total 24 Hours 5 minutes Total 85%of Nominal Voltage=20.4 VDC Standby Alarm Battery Standby Alarm Battery . Rev. 11/3/15 (20.4) - (2.84) = 17.56 End of Line Voltage = 17.56 VDC Current (AH) Current (AH) Capacity (AH) Current (AH) Current (AH) Capacity (AH) Operating Voltage Range 16 - 33 VDC 1.07 0.19 1.26 1.28 0.48 1.76 SHEET NO Battery Derating (20%) 5.6 Battery Derating (20%) 5.6 Battery provided: 7 AH Battery provided: 7 AH F1 . 4