A15-0093_BATT FACP Calcs_1444843980.pdf
FACP BATTERY CALCULATIONS PROJECT: Sun Vail Condos-Ricci Units E24&E34 HOURS OF SUPERVISION: 24 HOURS MINUTES OF ALARM: 5 MINUTES FACP: Gamewell Zans 400 LOCATION: Common Storage Room Device Device Total Total PART Supervisory Alarm Supervisory Alarm ITEM QTY NUMBER DESCRIPTION Current Current Current Current 1 1 Zans 400 Gamewell Zans 400 0.152000 0.592000 0.152000 0.592000 Mains Totals: 0.152000 0.592000 PERIPHERAL: Supervisory Alarm Device Device Total Total ITEM PART Supervisory Alarm Supervisory Alarm # QTY NUMBER DESCRIPTION Current Current Current Current 1 34 GE 541NCSRH Existing Smoke Detector 0.000070 0.000300 0.002380 0.010200 2 5 GE 541NCSRH New Smoke Detector 0.000070 0.000300 0.000350 0.001500 3 2 5601 Heat Detector 0.000300 0.000300 0.000600 0.000600 4 8 DS700 Pull Station 0.000010 0.000010 0.000080 0.000080 5 2 71138 Mini-Horn 0.000000 0.024000 0.000000 0.048000 6 1 P2RK 75cd Weatherproof Horn/Strobe 0.000000 0.176000 0.000000 0.176000 Peripheral Totals: 0.003410 0.236380 Supervisory Alarm SUPERVISORY COMPUTATIONS PANEL: 0.152000 AMPS PERIPHERAL 0.003410 AMPS SUB-TOTAL: 0.155410 AMPS X HOURS OF SUPERVISORY: 24.0000 _ HOURS SUPERVISORYSUB-TOTAL: 3.729840 AMP HOURS ALARM COMPUTATIONS PANEL: 0.592000 AMPS PERIPHERAL: 0.236380 AMPS SUB-TOTAL: 0.828380 AMPS X MINUTES OF ALARM: 0.08333 HOURS ALARM SUB-TOTAL: 0.069032 AMP HOURS BATTERY REQUIREMENT COMPUTATIONS TOTAL SUPERVISORY: 3.729840 AMP HOURS TOTAL ALARM: 0.069032 AMP HOURS TOTAL: 3.798872 AMP HOURS DERATE 25%: 4.74859 AMP HOURS MINIMUM BATTERY REQUIREMENT: 4.74859 AMP HOURS BATTERY SUPPLIED: 7.00000 AMP HOURS