HomeMy WebLinkAboutA15-0100_FA000_1447371720.pdf Cir I/4
e.
LEGEND :
SYMBOL 1 DEVICE MANUFACTURER/PART# MOUNTING %
Honeywell Vista-128BPT .!`'' '.._ %.
FACP y C'?;';��tIG/ '�' .. Vail Fire
&Emergency Services
Fire Alarm Control Panel w/7AH Batteries Mount on wall in manufacturer backbox ;s ,r,�
ocdp 2i:a .
KP •
0:92 352331 F? Z -
LCD Keypad/Annunciator Honeywell 6160 Mount on wall in manufacturer backbox _,f i/...4.,f
. �►Gf�lAl.-'� �
0 Smoke Detector Honeywell 5193SD 4" square box .'..•'A1-'c''
z
® System Sensor 5601P o
Heat Detector w/4193SN Addressable module 4" square box a
o
H❑ Sounder System Sensor MHW Single gang box
z
0
Co Carbon Monoxide Detector Honeywell 580000 Single gang box LL
KB Knox Box
w
I.
0
GENERAL NOTES: 3 #16 PAIR, 1 DATA, 1 SOUNDER, 1 POWER o
1 . ALL EQUIPMENT IS TO BE INSTALLED AND TESTED IN / U)
ACCORDANCE WITH MANUFACTURER STANDARDS, FIRE EOLR p El ® p
DEPARTMENT REQUIREMENTS AND NFPA 72. 0
2. REFER TO MANUFACTURERS DATA SHEETS AND (9) (9) (12) (1) Honeywell z
INSTALLATION INSTRUCTIONS FOR FURTHER INFORMATION VISTA 128 o
REGARDING PRODUCT INSTALLATION, WIRING DIAGRAMS,
PROGRAMMING AND DEVICE OPERATION. i
KP
0
DIALER W
J O
DEDICATED 120V J w CV
CO
TELE LINESJ CO 00
PRIMARY RESIDENCE D x o 2
SYSTEM ONE- LINE DIAGRAM ooI- coz c,
NOTE 1. NO T-TAPPING PERMITTED ON ANY CIRCUIT . o O)
NOTE 2. ALL WIRING TO BE 18AWG FPL. > 0 > O
60J
SEQUENCE OF
Q
CZE Q00
OPERATIONS:
(n J Z
X
Q Z � Z oz p ���
C9 O 0 0 (n O ZO
E z N N ~ > ~ JD u m
m Oo mN N mrn Z
_ = O cu,-2 0 c z O
o_ gz Dz � z mla)
Q =
li M OOOUOHHH
DEVICE a a0 zm zm zm > z
DESCRIPTION I � ct go go go 0o
Q a � ~ ~ ~ ~ ~ ~ ¢ (n
f>r\e")
SMOKE DETECTOR X X X iDrN
■ ■
HEAT DETECTOR X X X
CARBON MONOXIDE DETECTOR X X X
POWER LOSS, OPEN CIRCUIT, GROUND FAULT X I X
CO
CO
1-
0)
CD
1370 SANDSTONE #9a) W
ZONE LIST Ademco Vista 128 FACP PROJECTINFORMATION :
Standby Number of Current Total Current 1370 SAN D STO \ E R D . #9 v
DEVICE # DEVICE TYPE LEVEL DESCRIPTION
001 CO DETECTOR LOWER UTILITY ROOM Device Type Devices (Amps) (Amps) - W
002 CO DETECTOR LOWER ENTRY/BOTTOM OF STAIR Main FACP CPU 1 X 0.032 = 0.032 VAI L, COLORADO z =
4193SN Serial Interface 5 X 0.00015 = 0.00075 FRE A LA R IV SYSTEM
003 SMOKE DETECTOR LOWER ENTRY/BOTTOM OF STAIR 5192SD Smoke Detectors 6 X 0.00084 = 0.00504
004 HEAT DETECTOR LOWER GARAGE Carbon Monoxide Detectors 4 X 0.00025 = 0.001
005 SMOKE DETECTOR MAIN LIVING ROOM 6160 Keypad 1 X 0.04 = 0.04 AHJ: VAIL FIRE & EMERGENCY SERVICES 0) U C/)
006 CO DETECTOR MAIN LIVING ROOM SUM COLUMN FOR STANDBY LOAD 0.07879 = AMPS APPLICABLE CODES: 2010 NFPA 72, 2012 IFC, 2012 IBC I W =
007 SMOKE DETECTOR _ UPPER NE BEDROOM
008 SMOKE DETECTOR UPPER NW BEDROOM OCCUPANCY: GROUP R p
W
009 CO DETECTOR UPPER HALLWAY Alarm Load USE: TOWNHOUSE Q
Number of Current Total Current
010 SMOKE DETECTOR UPPER HALLWAY 12
O J CO
Type Devices (Amps) (Amps) FIRE ALARM SYSTEM FOR TOWNHOUSE. SYSTEM INCLUDES NEW
011 SMOKE DETECTOR UPPER MASTER BEDROOM Main FACP CPU 1 X 0.032 = 0.032 12L �
ADDRESSABLE VISTA 128 FIRE ALARM CONTROL PANEL. SMOKE
012 4193SN Serial Interface - 5 .. X . 0.00015 - 0.00075 W = W
013 5192SD Smoke Detectors 6 x 0.0196 = 0.1176 DETECTORS WILL BE INSTALLED IN SLEEPING ROOMS, STAIRWELL LANDINGS z
014 Carbon Monoxide Detectors 4 ' X 0.00025 = 0.001 AND AREAS OUTSIDE OF SLEEPING ROOMS. A HEAT DETECTOR WILL BE o -
015 6160 Keypad 1 _• X 0.1 = 0.1 INSTALLED IN GARAGE. SOUNDERS WILL BE PROVIDED IN SLEEPING 0 Q o >--
016 MHW Sounder - 5 X 0.066 -= 0.33 ROOMS AND AS NEEDED TO ACHIEVE AUDIBILITY. A KNOX BOX WILL BE (f) ' m
017 SUM COLUMN FOR ALARM LOAD 0.58135 AMPS MOUNTED ON THE OUTSIDE OF THE HOME. MONITORED CARBON 0 ~ 10
018 Standby Load Required Standby Time in Hours MONOXIDE DETECTORS ARE PROVIDED. = J 0
019 Current (Amps) 0 W
020 0.07879 X 24 = 1.89 '=
021 Alarm Load Required Alarm Time in Hours � I-Q v
D22 Current (Amps) (15 MINUTES) CD J Z (f)
023 0.58135 X 0.25 = 0.15 O W
024 Add Standby and Alarm Load for Required co > U
025 Ampere Hour Battery 2.04
FIRE PROTECTION ENGINEER:
Multiply by the Derating Factor of 1.2 DEBORAH SHAN ER, P.E., SHAN ER LIFE SAFETY SHEET DESCRIPTION:
Total Ampere Hours Required = 2.44
Batteries Provided: . 4AH Minimum, PO BOX 1073, FRISCO, CO 80443 FIRE ALARM PLAN
PHONE: 970-409-9082
FAX: 970-797- 1898 DRAWN BY: DATE:
DLS 11/6/15
SHEET#:
FA-0.00