Loading...
HomeMy WebLinkAboutA16-0010_FA-1_1457129940.pdf lAOF4,. 4tri 3QO Vail Fire&Emergency Services 03/04/16 BATTERY CALCULATION LOCATION: LAZZARA RES HOURS OF SUPERVISION: 24 HOURS MINUTES OF ALARM: 15 MINUTES PANEL: GE NX-8E Device Device Total Total PART Supervisory Alarm Supervisory Alarm VOLTAGE DROP CALCULATION ITEM QTY NUMBER DESCRIPTION Current Current Current Current PANEL: GE NX-8E LOCATION: LAZZARA RES INSTALLED BY: 1 1 NX-8E PANEL BOARD 0.075000 0.075000 0.075000 0.075000 TOTAL TOTAL CURRENT ESTIMATED 2 2 NX-148E-RF LCD KEYPAD 0.075000 0.075000 0.150000 0.150000 CURRENT CURRENT CURRENT CURRENT PER STARTING ONE-WAY CIRCUIT MIN. SAFARI 3 1 NX-2192E ADDRESSABLE CARD 0.170000 0.170000 0.170000 0.170000 Top of DeviceAVAILABLE CIRCUIT CIRCUIT PER PER PER CIRCUIT CIRCUIT WIRE WIRE VOLTAGE FINAL OPERATE 4 11 SI-ID ADDRESSABLE INPUT MODULE 0.000250 0.000250 0.002750 0.002750 al al FOR DEVICES NUMBER TYPE CIRCUIT DEVICES QUAN DEVICE DEVICE REMAINING VOLTAGE GAGE DISTANCE DROP VOLTAGE VOLTAGE SECURITY AND INTEGRATION LLC 5 8 541 NCSXT SMOKE DETECTOR 0.000070 0.006000 0.000560 0.048000 Lens of Strobe 15 1.000 Circuit 1 NAC 1.000 SMOKE DET SOUNDER 8 0.060 0.480 0.520 10.2 18 6 2 5603 HEAT DETECTOR 0.000000 0.000000 0.000000 0.000000 MI75 POWER SUP MODULE 1 0.066 0.066 0.454 10.2 18 125 1.103 9.097 8.000 PANEL TOTALS 315 E 17TH STREET 7 4 260-CO CARBON MONOXIDE DETECTOR 0.020000 0.040000 0.080000 0.160000 Top of' Cabinet TOTAL NOTES: NEC 2014 TABLE 8 LEADVILLE, CO 80461 CURRENT 8 1 405-03 ESL POWER REVERSAL MODULE 0.043000 0.043000 0.043000 0.043000 FACP FAPS USED 0.480 Current draws are Average (RMS) amperes. wire gage resistance ohms per 1000 feet 9 1 204-12/24 ESL POWER SUP MODULE 0.066000 0.066000 0.066000 0.066000 Max Max Top of' Unit TOTAL All voltage calculations are in volts D.C. 12 2.01 970 306-6560 10 1 MHR SYSTEM SENSOR HORN 0.000000 0.012000 0.000000 0.012000 below 8"0" FAA MAP CURRENT Voltage drops are calculated assuming all of 14 3.19 TOTAL: 0.587310 0.726750 ceiling (96") AVAIL: 1.000 the load is at the end of the circuit. 16 5.08 Top of Box TOTAL Voltage Drop = Resistance X (one way wire Distance X2) X circuit Amps 18 8.08 SUPERVISORY: Min Min P CURRENT SUB-TOTAL: 0.587310 AMPS 7'6" 6'8" 24 HOURS OF SUPERVISORY: 24.000000 HOURS (90") (80") 5'4" 4'0" REMAINING 0.520 (64") (48") SUB-TOTAL: 14.095440 AMP HOURS I All heights cine DROP CALCU LATI O\ S ALARM: measured from (AFF) l SUB-TOTAL: 0.726750 AMPS Above Finished Floor -/ 15 MINUTES OF ALARM: 0.250000 HOURS SUB-TOTAL: 0.181688 AMP HOURS DEVICE V OU \ TI \ G HEIGHTS TOTALS: TOTAL SUPERVISORY: 14.095440 AMP HOURS LU TOTAL ALARM: 0.181688 AMP HOURS TOTAL: 14.277128 AMP HOURS 11 SPARE OF 20% (SPARE) 2.855426 AMP HOURS - MINIMUM BATTERY SIZE REQUIRED 17.132553 AMP HOURS BATTERIES SUPPLIED 18.000 AMP HOURS Installation of a monitored residential fire alarm system . 0 3ATTERY CALCU LATI O\ S CO\ TOOL PANEL Installation of a Networx \X-8E fire alarm system . L Installation of 4 wire smoke and heat detectors with point identification . Installation of individually zoned carbon monoxide detectors. II SYMBOL DESCRIPTION L Allthe smokes have sounders that willoperate in tandem on alarm . 0 FACP FIRE ALARM CONTROL PANEL Installation of an exterior knox box. 0 (?) SMOKE DETECTOR (PHOTOELECTRIC) < ll 0 135° HEAT DETECTOR 135° FIXED TEMP SCOPE OF WOR < QUA\ . PATT # DESC PT 0\ OF 0 1 NX-8E NETWORX CONTROL PANEL 000 CARBON MONOXIDE DETECTOR1 NX148E-RF NETWOX LCD KEYPAD 1 NX-2192E NETWORX ADDRESSABLE MODULE0 Lo (AIM) ADDRESSABLE MONITOR MODULE Lo 11 SI-ID NETWORX ADDRESSABLE INPUT MODULE 8 541NCSXT ESL SMOKE DETECTOR iii4 HORN 3 ES C PT 0\ CLASS TYPE 2 5603 SYSTEM SENSOR HEAT DETECTOR SIGNALING LINE CIRCUITS B 2 #18 AWG FPLP 4 260-CO ESL CARBON MONOXIDE DETECTOR EOL END OF LINE RESISTOR HORN CIRCUIT B 2 #18 AWG FPLP RE 1 MHR SYSTEM SENSOR HORN INITIAIING DEVICE CIRCUITS B 2 #18 AWU bPLN 1 405-03 ESL POWER REVERSAL RELAY EOL PS END OF LINE POWER SUPERVISION 12 VOLT SMOKE POWER CIRCUIT 2 #18 AWG FPLP 1 204-12/24 ESL POWER SUP. MODULE 1 P12180 POWER SONIC 18 AMP HOUR BATTERY QLECE \ D CHART 1 3221 KNOX BOX 3200 SERIES RECESSED flWIRE V ATE I ALS LIST SUBMITTAL PREPARED BY: System Outputs M< I1S c, s •��o °c\ Alarm Design Solutions Inc. 4' .0 �• •.c• ��Q\ 8391 Delaware St, Suite 103 .�g °. Denver, CO 80221 •° 0 \ �� � (303) 828-0802 H <- EOL RE �� �•�6� G�'\0 �a�C`� ��J JQ .��� TOCOEOL MONITORING STATION: ° ��° \ °G &�°�J ° alarmdesignsolu@cs.com RE ZONE 1 API Monitoring Inc. e, \� �� . �° ,L°, o� \ \ �\ � o 700 Broadway, Bldg 1 , Suite 105 �s.c), \)c), • .-`P� A\ c•sc\ �,e,c', �c°��4� �c\ &� JOB NUMBER: 5002 0 EOL RE ZONE 2 Denver, C 0 80221 P �o���o�� �G\� °�� O �o� ��`° �;�°\ \ ETWOX MONITORING METHOD: Telephone �Q���Qk� °P °P ��\ �,� °�° ��,° P° °�`° ��' \ X - 8E ZONE 3 P P P EOL L R f G� QQ' e,' .-. , o °J� NATIONAL INSTITUTE FOR CERTIFICATION CO EOL f <\'Ce' <\'Ce' ,`,C0 ,`�0 AGO Q° P\ GQ <�� C ' IN ENGINEERING TECHNOLOGIES C O \TOL -DCO RE ZONE 4 00 00 00 00 00 OO 00 00 Fire Protection Engineering Technology '� '� '� '� '� '� '� Fire Alarm Systems 120 VAC - S s t e ,-,1 Inputs p u t S °'�� G�� G�� G�� G�� G�� G�� G�� ��� ��� ��� DEDICATED PA\ EL 01 02 03 04 05 06 07 08 09 10 11 y P P P P P P P F '` '` PHONE W U SACT AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM 1 Smoke Detector X X X X X X !`• "1� / 2 Heat Detector X X X XX X 1 LINE 135° 3 CO Detector X X X X X X X Joel BlattS.E.T. 01350 F 1 F © © © © © © © © EOL Ps 4 Notification Circuit Trouble X X X P P P P P P P P X NICET #103704 Level IV 5 Low Battery X X X X EXP. 09/1/2016 6 AC Power Failure X X X X DATE:02/18/16 SCALE: 1/4"=1'0" 7 Telephone Line Fault X X X REVISIONS: PAGE NAME: TITLE PAGE 0 \ E \ E AGAV CDSEQUE\ CE OF OPERATIONS A 1 SHEET 1 OF 2