Re: Reply to comments for 1915 West Gore Creek Drive PRJ14-0676 A16-0010
To Mike Vaughan
Thank you for your comments on PRJ14-0676 A16-010.
The 500Nserieslnsta1l1036525B is over 14 years old. We have uploaded a sheet dated 30 April
2014.
Heat detection in garage is not required. As per Fire Alarm Installation Standards dated
January 2013 and publish on Town of Vail website it states: "Garages shall have either a
sounder or a sounding keypad to provide notification of system activation. Heat
detection in garages is required. "
Why are you not using smoke/CO detector combo's. As far as we are aware only System
Sensor makes these 2 wire and 4 wire devices. They need an interface module and are only
suitable for adding to a zone and can't be point addressable to meet the Fire Alarm Installation
Standards dated January 2013.