Loading...
HomeMy WebLinkAboutA16-0010_PRJ14-0676A16-0110CommentsResponse_1456493880.pdf * SAFARI ),\A, SECURITY AND INTEGRATION LLC 315 E 7th Street ,Leadville, 00,80461 Tel: (970)306-6560 Vail Fire and Emergency Services 2399 North Frontage Rd West Vail, CO 81657 02/26/2016 Re: Reply to comments for 1915 West Gore Creek Drive PRJ14-0676 A16-0010 To Mike Vaughan Thank you for your comments on PRJ14-0676 A16-010. The 500Nserieslnsta1l1036525B is over 14 years old. We have uploaded a sheet dated 30 April 2014. Heat detection in garage is not required. As per Fire Alarm Installation Standards dated January 2013 and publish on Town of Vail website it states: "Garages shall have either a sounder or a sounding keypad to provide notification of system activation. Heat detection in garages is required. " Why are you not using smoke/CO detector combo's. As far as we are aware only System Sensor makes these 2 wire and 4 wire devices. They need an interface module and are only suitable for adding to a zone and can't be point addressable to meet the Fire Alarm Installation Standards dated January 2013. If you have any further questions please contact me on 970-471-5774. Thanks if Craig Boulle NICET# 117361