HomeMy WebLinkAboutA16-0018_FA-0 UNIT A_1478896257.pdf islei OF gr, a ec rb UNIT A- Battery Calculations ELK M1 LEGE\ D : Standby4�U8ire&Emergency Services Number of Current Total Current SYMBOL DEVICE MANUFACTURER/PART# MOUNTING Device Type Devices (Amps) (Amps) ELK M1 GOLD Main FACP CPU 1 X 0.032 = 0.032 FACP Keypad 2 X 0.04 = 0.08 Fire Alarm Control Panel w/10AH Batteries Mount on wall in manufacturer backbox i3 Smoke Detector with Sounder 5 X 0.00005 = 0.00025 i4 COSMO Smoke/CO Detector w/Sounder 4 _ X 0.00005 = 0.0002 KP COSMO Interface Module 9 X 0.022 = 0.198 LCD Keypad/Annunciator ELK M1 LCD Mount on wall in manufacturer backbox SUM COLUMN FOR STANDBY LOAD 0.31045 = AMPS Alarm Load O Combination Smoke & Heat Detector w/Sounder System Sensor i3 series 4WTA—B 4" square box Number of Current Total Current Device Type Devices (Amps) (Amps) Combination Smoke and Main FACP CPU 1 X 0.032 = 0.032 coOCO Detector w/Sounder System Sensor i4 series COSMO-4W 4" square box Keypad 2 X 0.04 = 0.08 i3 Smoke Detector with Sounder 5 X 0.025 = 0.125 1 System Sensor 5601 P i4 COSMO Smoke/CO Detector w/Sounder 4 X 0.04 = 0.16 Heat Detector w/4193SN Addressable module 4" square box COSMO Interface Module 9 X 0.034 0.306 o Outside Horn/Strobe 1 X 0.212 = 0.212 i= SUM COLUMN FOR ALARM LOAD 0.915 = AMPS c Cosmo Interface Module COSMOD4W 0_ E Standby Load Required Standby Time in Hours ci Current (Amps) w 0.31045 X 24 = 7.45 KB Knox Box 0z Alarm Load Required Alarm Time in Hours o Current (Amps) (15 MINUTES) 7. > 0.915 X 0.25 = 0.23 ,U, Horn/Strobe, weatherproof System Sensor P2RK Weatherproof backbox 1 Add Standby and Alarm Load for Required Ampere Hour Battery 7.68 Multiply by the Derating Factor of 1.2 Total Ampere Hours Required = 9.22 GENERAL NOTES: w Minimum Battery Size Provided: 10AH Approved. Have db rati ,, 0 L �illllIS TO BE INSTALLED AND TESTED IN ACCORDANCE WITH MANUFACTURER STANDARDS, FIRE DEPARTMENT REQUIREMENTS AND NFPA 72. 2. REFER TO MANUFACTURERS DATA SHEETS AND INSTALLATION INSTRUCTIONS FOR FURTHER DEVICE ZONE LIST- UNIT A a INFORMATION REGARDING PRODUCT INSTALLATION, WIRING DIAGRAMS, PROGRAMMING AND DEVICE z Zone Type of Device Level Description OPERATION. 001 HEAT DETECTORS LOWER GARAGE 002 CO/SMOKE DETECTOR LOWER MUD ROOM CNI CO w 003 SMOKE DETECTOR MAIN EAST BEDROOM O z • 004 SMOKE DETECTOR MAIN CENTER BEDROOM I c 005 CO/SMOKE DETECTOR MAIN LIVING AREA o Q 006 SMOKE DETECTOR MAIN WEST BEDROOM > 007 SMOKE DETECTOR UPPER EAST BEDROOM/OFFICE },,,IJ •/,• 0) I O 008 CO/SMOKE DETECTOR UPPER GREAT ROOM T, ap�D RprIr% C o 009 CO/SMOKE DETECTOR UPPER ,OUTSIDE MASTER i ti1� ` ' '. _ rn cn 010 SMOKE DETECTOR UPPER MASTER BEDROOM l ' �N. }Yr �fi- 0 = 43 _1 011 MONITOR LOWER SPRINKLER WATERFLOW r�' 35233i � � �I c z 012 MONITOR LOWER SPRINKLER TAMPER ‘14.7.- ;', ' y�= _c _ 0130' R i 014 µ * '- ••• 015 D 016 C NOTE: LEVEL WILL BE INCLUDED IN DEVICE ADDRESS DESCRIPTION. cI1 w D = 4—WIRE DATA/POWER, 4—#16AWG (2 PAIR) C X = 2—WIRE DATA, 2—#16AWG 0 N = 2—WIRE SOUNDER CIRCUIT, 2—#18AWG } Z = 2—WIRE DATA CIRCUIT, 2—#16AWG U EOL EOL `L N KP = KEYPAD CIRCUITING, 4—#18AWG ®co Q ( I///) ^vvv0 RISER NOTES: C " - i- o D D Il °O 1. REFER TO ELK M1 INSTALLATION MANUAL FOR MORE INFORMATION. 0 0 p 2. WIRE SIZE MAY BE VARIED, PROVIDED IT MEETS I L,N K L,N < MANUFACTURERS SPECIFICATIONS. C�I �� 3. VERIFY WIRING OF SYSTEM SENSOR COSMOD4W (TYP) ( ) � TYPo O PRIOR TO INSTALLATION. WIRING DIAGRAM ISZ LL s— O INCLUDED SUBMITTAL BOOKS. ® OX O m v 120VAC DEDICATED POWER ELK M1 U) CONTROL PANEL Z FLOW SWITCH cu u_ Z TAMPER SWITCH TELEPHONE LINE — FIRE TELEPHONE LINE — SECURITY oWP BELL N ,Q EOLR OUTPUT DATA/COM KP I I I S E AG SAV OUTPUT (KEYPAD (KEYPAD W O 0 0 w PROJECT I \ FOVATIO\ : J z SEQUE\CE OF z J w w CASCADE HOUSE > _ OPEATIO\S: z 0 � VAIL COLORADO CO if; 50 30 cno or,_, FRE ALARV SYSTEV J = (7, LT, Q Li J U co Q o i2 Q N w N m N o o z w AHJ: VAIL FIRE & EMERGENCY SERVICES Ct g z D z w z w a- a - o w APPLICABLE CODES: 2010 NFPA 72, 2012 IFC, 2012 IBC O U < E NE I— E Ww < I- m U W CO LI 1- o 1- o 1- o al— < I o � USE: DUPLEX W z H W w g z g z g z w I w w w N W (/" 0 DEVICE a 0 0 vl 0 vl 0 F- Q (2, Q� U) > z z z > w > z > z FIRE ALARM SYSTEM FOR DUPLEX UNIT. SYSTEM INCLUDES A NEW COMBO DESCRIPTION a Q << F- o F- o i- i- Q m Q o Q o SECURITY/FIRE ALARM CONTROL PANEL. SMOKE DETECTORS WILL BE 0 = SMOKE DETECTOR X X X CO INSTALLED IN SLEEPING ROOMS AND COMBINATION SMOKE/CARBON = = ct 0 MONOXIDE DETECTORS WILL BE INSTALLED WITHIN 15' OF FIREPLACES W U) W AND AREAS OUTSIDE OF SLEEPING ROOMS. DETECTORS HAVE INTEGRAL 0 W J z HEAT DETECTOR X X X SOUNDERS. A KNOX BOX WILL BE MOUNTED ON THE OUTSIDE OF THE Q 0HOME. THE SPRINKLER SYSTEM WILL BE MONITORED, SMOKE DETECTORS 0 p W CARBON MONOXIDE DETECTOR X X X ARE RESTORABLE AT THE KEYPAD. Q N 0 W 0 x— LL 0 SPRINKLER WATERFLOW SWITCH X X X X FIRE PROTECTION ENGINEER: SHEET DESCRIPTION: SPRINKLER TAMPER SWITCH X X DEBORAH SHANER, P.E., SHANER LIFE SAFETY COVER SHEET PO BOX 1073, FRISCO, CO 80443 POWER LOSS, OPEN CIRCUIT, GROUND FAULT X X PHONE: 970-409-9082 DRAWN BY: DATE: FAX: 970-797- 1898 DLS 3/15/16 UNIT A SHEET#: FA-0.00A