HomeMy WebLinkAboutA16-0019_FA-0 UNIT B_1478896458.pdf islei OF gr, a ec LEGE\ D :� � Vail Fire&Emergency Services 04/18/16 UNIT B - Battery Calculations SYMBOL DEVICE MANUFACTURER/PART# MOUNTING ELK Ml FACP ELK M1 GOLD Standby Fire Alarm Control Panel w/10AH Batteries Mount on wall in manufacturer backbox Number of Current Total Current — Device Type Devices (Amps) (Amps) KP Main FACP CPU 1 X 0.032 = 0.032 LCD Keypad/Annunciator ELK M1 LCD Mount on wall in manufacturer backbox Keypad 2 X 0.04 _= 0.08 i3 Smoke Detector with Sounder 4 X 0.00005 = 0.0002 Combination Smoke & i4 COSMO Smoke/CO Detector w/Sounder 4 X 0.00005 , __ 0.0002 O Heat Detector w/Sounder System Sensor i3 series 4WTA—B 4" square box COSMO Interface Module 8 X 0.022 = 0.176 SUM COLUMN FOR STANDBY LOAD 0.2884 = AMPS Combination Smoke and Alarm Load ®co CO Detector w/Sounder System Sensor i4 series COSMO-4W 4" square box Number of Current Total Current Device Type Devices (Amps) (Amps) O System Sensor 5601 P Main FACP CPU 1 X 0.032 = 0.032 Heat Detector w/41935N Addressable module 4" square box Keypad 2 X 0.04 = 0.08 0 i3 Smoke Detector with Sounder 4 X 0.025 = 0.1 H Cosmo Interface Module COSMOD4W i4 COSMO Smoke/CO Detector wlSounder 4 X 0.04 = 0.16 c E 0 COSMO Interface Module 8 X 0.0340.2712 w w Outside Horn/Strobe 1 X 0.212 = 0.2120 SUM COLUMN FOR ALARM LOAD 0.856 = AMPS KB Knox Box z 0 Standby Load Required Standby Time in Hours ' Current (Amps) w ,0, Horn/Strobe, weatherproof System Sensor P2RK Weatherproof backbox 1 0.2884 X 24 = 6.92 Alarm Load Required Alarm Time in Hours Current (Amps) (15 MINUTES) 0.856 X 0.25 = 0.21 Add Standby and Alarm Load for Required GENERAL NOTES: w Ampere Hour Battery 7.14 Q Multiply by the Derating Factor of 1.2 1 . ALL EQUIPMENT IS TO BE INSTALLED AND TESTED IN ACCORDANCE WITH MANUFACTURER STANDARDS, 0 Total Ampere Hours Required = 8.56 FIRE DEPARTMENT REQUIREMENTS AND NFPA 72. Minimum Battery Size Provided: 10AH 2. REFER TO MANUFACTURERS DATA SHEETS AND INSTALLATION INSTRUCTIONS FOR FURTHER INFORMATION REGARDING PRODUCT INSTALLATION, WIRING DIAGRAMS, PROGRAMMING AND DEVICE z OPERATION. DEVICE ZONE LIST- UNIT B cv 1— Zone Type of Device _Level Description o z 001 HEAT DETECTOR LOWER GARAGE am • 002 CO/SMOKE DETECTOR LOWER MUD ROOM o < 003 SMOKE DETECTOR MAIN WEST BEDROOM } 004 SMOKE DETECTOR MAIN EAST BEDROOM ,Err •ftp 0) I o D. > 005 CO/SMOKE DETECTOR MAIN LIVING AREA i'' cu S] �pr1r 006 SMOKE DETECTOR MAIN NE BEDROOM -, ;` °• `: U) 007 CO/SMOKE DETECTOR UPPER GREAT ROOM I .r i; v 0 " _1 008 CO/SMOKE DETECTOR UPPER OUTSIDE MASTER !o: 35233 r �� 11 o Z 009 SMOKE DETECTOR UPPER MASTER BEDROOM t.. ,_. 44: \, -c _ 010 MONITOR 'LOWER SPRINKLER WATERFLOW µ • ';•maw;' cn 011 _MONITOR LOWER SPRINKLER TAMPER£-.` ��Q�tAL \c"." 0 C 012 013 014 C 015 (1) WQts — NOTE: LEVEL WILL BE INCLUDED IN DEVICE ADDRESS DESCRIPTION. D = 4—WIRE DATA/POWER, 4—#16AWG (2 PAIR) Alil X = 2—WIRE DATA, 2—#16AWG _1 0 N = 2—WIRE SOUNDER CIRCUIT, 2—#18AWG } Z = 2—WIRE DATA CIRCUIT, 2—#16AWG 0 EOL EOL `L () KP = KEYPAD CIRCUITING, 4—#18AWG ®co Q ( I///) ^vvv0 RISER NOTES: C " d- o D D 0_ °O 1. REFER TO ELK M1 INSTALLATION MANUAL FOR MORE INFORMATION. 0 p 2. WIRE SIZE MAY BE VARIED, PROVIDED IT MEETS I L,N E L,N 0 < MANUFACTURERS SPECIFICATIONS. �� 3. VERIFY WIRING OF SYSTEM SENSOR COSMOD4W MP) CDT) � 0 0 PRIOR TO INSTALLATION. WIRING DIAGRAM ISZ LL Q U INCLUDED SUBMITTAL BOOKS. ® OX O m v 120VAC DEDICATED POWER ELK M1 CONTROL PANEL Z FLOW SWITCH 0- LJ- Z TAMPER SWITCH TELEPHONE LINE — FIRE TELEPHONE LINE — SECURITY _,WP BELL N ,0, EOLR OUTPUT DATA/COM KP I I I S E AG SAV OUTPUT (KEYPAD (KEYPAD W CL O C 0 W PROJECT I \ FOVATIO\ : J z SEQUE\CE OF z J w W CASCADE HOUSE > _ OPEATIO\S: z 0 0 � VAIL COLORADO CD oz oM FRE ALARV SYSTEV J = (n 1- Q W Q J 0 U co Q 12 Q N w cn m N o o z a_ W AHJ: VAIL FIRE & EMERGENCY SERVICES 1 o_ g z D z w z w m - o w APPLICABLE CODES: 2010 NFPA 72, 2012 IFC, 2012 IBC OM U QE NFt I– FtWw IY I- m 0 W W � o 1- o � o � I– I o � USE: DUPLEX W z H W W � Z � Z � Z W I WW N W (/� 0 DEVICE a (no (no No acn Qa Q� Cn > z z z > w > z > z FIRE ALARM SYSTEM FOR DUPLEX UNIT. SYSTEM INCLUDES A NEW COMBO > DESCRIPTION a Q QD a I- I- I- I- I- I- Q m Q D 00 SECURITY/FIRE ALARM CONTROL PANEL. SMOKE DETECTORS WILL BE 0 = CO SMOKE DETECTOR X X X INSTALLED IN SLEEPING ROOMS AND COMBINATION SMOKE/CARBON = = Ct 0 MONOXIDE DETECTORS WILL BE INSTALLED WITHIN 15' OF FIREPLACES W (!) W AND AREAS OUTSIDE OF SLEEPING ROOMS. DETECTORS HAVE INTEGRAL 0 W J z HEAT DETECTOR X X X SOUNDERS. A KNOX BOX WILL BE MOUNTED ON THE OUTSIDE OF THE Q 0 HOME. THE SPRINKLER SYSTEM WILL BE MONITORED, SMOKE DETECTORS C.) IN W CARBON MONOXIDE DETECTOR X X X ARE RESTORABLE AT THE KEYPAD. Q N W U 0 SPRINKLER WATERFLOW SWITCH X X X X FIRE PROTECTION ENGINEER: SHEET DESCRIPTION: SPRINKLER TAMPER SWITCH X X DEBORAH SHANER, P.E., SHANER LIFE SAFETY COVER SHEET PO BOX 1073, FRISCO, CO 80443 POWER LOSS, OPEN CIRCUIT, GROUND FAULT X X PHONE: 970-409-9082 DRAWN BY: DATE: FAX: 970-797- 1898 DLS 3/15/16 UNIT E SHEET#: FA-0.008