Vail Fire&Emergency Services
04/18/16
UNIT B - Battery Calculations SYMBOL DEVICE MANUFACTURER/PART# MOUNTING
ELK Ml FACP ELK M1 GOLD
Standby Fire Alarm Control Panel w/10AH Batteries Mount on wall in manufacturer backbox
Number of Current Total Current —
Device Type Devices (Amps) (Amps) KP
Main FACP CPU 1 X 0.032 = 0.032 LCD Keypad/Annunciator ELK M1 LCD Mount on wall in manufacturer backbox
Keypad 2 X 0.04 _= 0.08
i3 Smoke Detector with Sounder 4 X 0.00005 = 0.0002 Combination Smoke &
i4 COSMO Smoke/CO Detector w/Sounder 4 X 0.00005 , __ 0.0002 O Heat Detector w/Sounder System Sensor i3 series 4WTA—B 4" square box
COSMO Interface Module 8 X 0.022 = 0.176
SUM COLUMN FOR STANDBY LOAD 0.2884 = AMPS Combination Smoke and
Alarm Load ®co CO Detector w/Sounder System Sensor i4 series COSMO-4W 4" square box
Number of Current Total Current
Device Type Devices (Amps) (Amps) O System Sensor 5601 P
Main FACP CPU 1 X 0.032 = 0.032 Heat Detector w/41935N Addressable module 4" square box
Keypad 2 X 0.04 = 0.08 0
i3 Smoke Detector with Sounder 4 X 0.025 = 0.1 H
Cosmo Interface Module COSMOD4W
i4 COSMO Smoke/CO Detector wlSounder 4 X 0.04 = 0.16 c E
0
COSMO Interface Module 8 X 0.0340.2712 w
w
Outside Horn/Strobe 1 X 0.212 = 0.2120
SUM COLUMN FOR ALARM LOAD 0.856 = AMPS KB Knox Box z
0
Standby Load Required Standby Time in Hours
'
Current (Amps) w
,0, Horn/Strobe, weatherproof System Sensor P2RK Weatherproof backbox 1
0.2884 X 24 = 6.92
Alarm Load Required Alarm Time in Hours
Current (Amps) (15 MINUTES)
0.856 X 0.25 = 0.21
Add Standby and Alarm Load for Required GENERAL NOTES: w
Ampere Hour Battery 7.14 Q
Multiply by the Derating Factor of 1.2 1 . ALL EQUIPMENT IS TO BE INSTALLED AND TESTED IN ACCORDANCE WITH MANUFACTURER STANDARDS, 0
Total Ampere Hours Required = 8.56 FIRE DEPARTMENT REQUIREMENTS AND NFPA 72.
Minimum Battery Size Provided: 10AH 2. REFER TO MANUFACTURERS DATA SHEETS AND INSTALLATION INSTRUCTIONS FOR FURTHER
INFORMATION REGARDING PRODUCT INSTALLATION, WIRING DIAGRAMS, PROGRAMMING AND DEVICE z
OPERATION.
DEVICE ZONE LIST- UNIT B cv 1—
Zone Type of Device _Level Description o z
001 HEAT DETECTOR LOWER GARAGE am •
002 CO/SMOKE DETECTOR LOWER MUD ROOM o <
003 SMOKE DETECTOR MAIN WEST BEDROOM
}
004 SMOKE DETECTOR MAIN EAST BEDROOM ,Err •ftp 0) I o
D.
>
005 CO/SMOKE DETECTOR MAIN LIVING AREA i'' cu S] �pr1r
006 SMOKE DETECTOR MAIN NE BEDROOM -, ;` °• `: U)
007 CO/SMOKE DETECTOR UPPER GREAT ROOM I .r i; v 0 " _1
008 CO/SMOKE DETECTOR UPPER OUTSIDE MASTER !o: 35233 r �� 11 o Z
009 SMOKE DETECTOR UPPER MASTER BEDROOM t.. ,_. 44: \, -c _
010 MONITOR 'LOWER SPRINKLER WATERFLOW µ • ';•maw;' cn
011 _MONITOR LOWER SPRINKLER TAMPER£-.` ��Q�tAL \c"." 0 C
012 013
014 C
015 (1)
WQts —
NOTE: LEVEL WILL BE INCLUDED IN DEVICE ADDRESS DESCRIPTION. D = 4—WIRE DATA/POWER, 4—#16AWG (2 PAIR) Alil
X = 2—WIRE DATA, 2—#16AWG _1 0
N = 2—WIRE SOUNDER CIRCUIT, 2—#18AWG }
Z = 2—WIRE DATA CIRCUIT, 2—#16AWG 0
EOL EOL `L ()
KP = KEYPAD CIRCUITING, 4—#18AWG ®co Q ( I///)
^vvv0
RISER NOTES:
C " d-
o
D D 0_ °O
1. REFER TO ELK M1 INSTALLATION MANUAL FOR
MORE INFORMATION. 0 p
2. WIRE SIZE MAY BE VARIED, PROVIDED IT MEETS I L,N E L,N 0 <
MANUFACTURERS SPECIFICATIONS. ��
3. VERIFY WIRING OF SYSTEM SENSOR COSMOD4W MP) CDT) � 0 0
PRIOR TO INSTALLATION. WIRING DIAGRAM ISZ LL Q U
INCLUDED SUBMITTAL BOOKS. ® OX O
m v
120VAC DEDICATED POWER ELK M1
CONTROL PANEL Z FLOW SWITCH 0- LJ-
Z TAMPER SWITCH
TELEPHONE LINE — FIRE
TELEPHONE LINE — SECURITY _,WP
BELL N ,0, EOLR
OUTPUT
DATA/COM KP I I I
S E AG SAV OUTPUT (KEYPAD (KEYPAD
W
CL
O C
0 W
PROJECT I \ FOVATIO\ : J z
SEQUE\CE OF z J w W CASCADE HOUSE > _
OPEATIO\S: z
0 0 �
VAIL COLORADO CD
oz oM FRE ALARV SYSTEV J =
(n 1- Q W Q J 0 U
co Q
12
Q N w cn m N o o z a_ W AHJ: VAIL FIRE & EMERGENCY SERVICES 1
o_ g z D z w z w m - o w APPLICABLE CODES: 2010 NFPA 72, 2012 IFC, 2012 IBC OM
U QE NFt I– FtWw IY I- m 0 W W
� o 1- o � o � I– I o � USE: DUPLEX W z H W
W � Z � Z � Z W I WW
N W (/� 0
DEVICE a (no (no No acn Qa Q� Cn
> z z z > w > z > z FIRE ALARM SYSTEM FOR DUPLEX UNIT. SYSTEM INCLUDES A NEW COMBO >
DESCRIPTION a Q QD
a I- I- I- I- I- I- Q m Q D 00 SECURITY/FIRE ALARM CONTROL PANEL. SMOKE DETECTORS WILL BE 0 = CO
SMOKE DETECTOR X X X INSTALLED IN SLEEPING ROOMS AND COMBINATION SMOKE/CARBON = = Ct 0
MONOXIDE DETECTORS WILL BE INSTALLED WITHIN 15' OF FIREPLACES W (!) W
AND AREAS OUTSIDE OF SLEEPING ROOMS. DETECTORS HAVE INTEGRAL 0 W J z
HEAT DETECTOR X X X SOUNDERS. A KNOX BOX WILL BE MOUNTED ON THE OUTSIDE OF THE Q 0
HOME. THE SPRINKLER SYSTEM WILL BE MONITORED, SMOKE DETECTORS C.) IN W
CARBON MONOXIDE DETECTOR X X X ARE RESTORABLE AT THE KEYPAD. Q N W
U 0
SPRINKLER WATERFLOW SWITCH X X X X
FIRE PROTECTION ENGINEER: SHEET DESCRIPTION:
SPRINKLER TAMPER SWITCH X X DEBORAH SHANER, P.E., SHANER LIFE SAFETY COVER SHEET
PO BOX 1073, FRISCO, CO 80443
POWER LOSS, OPEN CIRCUIT, GROUND FAULT X X PHONE: 970-409-9082 DRAWN BY: DATE:
FAX: 970-797- 1898 DLS 3/15/16
UNIT E SHEET#:
FA-0.008