HomeMy WebLinkAboutA16-0045_TOV FA0.00_1478896274.pdf Cir I/4 Le 1 Qin 0 Vail Fire&Emercncy Services TOY FIRE STATION # 1 RENOVATION 08/12/16 FIRE ALARM SYSTEM VAIL COLORADO 81657 Approved as noted . . . N FIRE ALARM SYSTEM LEGEND eliminate detection SYMBOL DESCRIPTION MANUFACTURER OPERATING MOUNTING HEIGHT BACKBOX REMARKS MODEL NUMBER VOLTAGE VIGILANT TOP OF CABINET AT 1.83 M. (6 FT.) AFF OR FACP FIRE ALARM CONTROL PANEL VS2-G 120 VAC CENTER AT 1.52 M. (5 FT.) AFF INCLUDED WALL MOUNTED WHICHEVER IS LOWER NOT LESS THAN 10.16 CM. (4") TO CORNERS OP PHOTOELECTRIC SMOKE DETECTOR VIGILANT STANDARD 101.6 MM.V-PS 15.2-19.95 VDC OR BETWEEN 10.16 CM. (4") TO 30.48 CM. (4") SQUARE BOX CEILING MOUNTED (12") FOR WALL MOUNTING where VIGILANT . . NOT LESS THAN 10.16 CM. (4") TO CORNERS PHOTOELECTRIC SMOKE DETECTOR WITH LOW &1516-332-1995 VDC STANDARD 101.6 MM. O2P,SB FREQUENCY AUDIBLE (SOUNDER) BASE V-PS FOR AUDIBLE OR BETWEEN 10.16 CM. (4") TO 30.48 CM. (4") SQUARE BOX CEILING MOUNTED WITH SB4U-LF ��55 (12") FOR WALL MOUNTING nQtadMnn COMBINATION PHOTOELECTRIC SMOKE VIGILANT 15.2- VDC NOT LESS THAN 10.16 CM. (4") TO CORNERS O & 16-33 VDC STANDARD 101.6 MM. P,CO,SB DETECTOR & CARBON MONOXIDE SENSOR V-PCOS FOR AUDIBLE OR BETWEEN 10.16 CM. (4") TO 30.48 CM. (4") SQUARE BOX CEILING MOUNTED WITH AUDIBLE (SOUNDER) BASE WITH GSA-SBT BASE (12") FOR WALL MOUNTING 1. THE FI ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72. VIGILANT STANDARD SINGLE GANG BOX INDEX OF DRAWINGS TP TEMPORAL PATTERN GENERATOR GSA-T3T4 15.2-19.95 VDC 64 MM. (2 1/2") DEEP WALL MOUNTED 2. L AL NITIATING DEVICE CIRCUITS SHALL BE CLASS B SUPERVISED. ALL SIGNALING LINE CIRCUITS SHALL BE CLASS B SUPERVISED. ALL R KATION CIRCUITS SHALL BE CLASS A SUPERVISED. DRAWING NUMBER DRAWING TITLE 3. L RM CONDUIT SHALL BE 19mm (3/4") MINIMUM, ADJUST CONDUIT SIZE ACCORDING TO WIRE COUNTS AS PER NATIONAL PS MANUAL PULL STATION (DOUBLE ACTION) VIGILANT 15.2-19.95 VDC 122 CM. (48") AFF TO TOP OF DEVICE 276B-RSB WALL MOUNTED ELECTR L CODE. GSA-M278 FA0.00 PROJECT TITLE, FIRE ALARM SYSTEM LEGEND, NOTES, INDEX OF DRAWINGS, AND DEVICES MOUNTING DETAILS 4. SEPARATE CONDUITS SHALL BE USED FOR 120 VAC AND 24 VDC CIRCUITS. VIGILANT STANDARD SINGLE GANG BOX FA0.01 FIRE ALARM SYSTEM RISER DIAGRAM, SEQUENCE OF OPERATIONS MATRIX, PANEL CIRCUIT DISTRIBUTION SCHEDULE, SINGLE INPUT MODULE GSA-CT1 15.2-19.95 VDC 64 MM. (2 1/2") DEEP WALL MOUNTED AND WIRING LEGEND 5. SMOKE DETECTORS SHOULD NOT BE LOCATED NO CLOSER THAN 0.914 m (3') FROM ALL AIR SUPPLY DIFFUSER, RETURN AIR OPENING, FA1.01 LEVEL 1 FIRE ALARM SYSTEM PLAN BATHROOM DOORS, LIGHTING FIXTURES AND OTHER ELECTRICAL EQUIPMENTS THAT MAY EMIT NOISE/EMF. El RISER MONITOR MODULE VIGILANT GSA-RM1 15.2-19.95 VDC STANDARD 101.6 MM. (4") SQUARE BOX FA1.02 LEVEL 2 FIRE ALARM SYSTEM PLAN WALL MOUNTED 6. MANUAL PULL STATION SHALL BE LOCATED WITHIN 1.5 m (5') OF EACH EXIT DOORWAY. WALL MOUNTED HORN/STROBE, RED, WITH 203.2 CM. (80") AFF TO BOTTOM OF DEVICE FA1.03 LEVEL 3 FIRE ALARM SYSTEM PLAN 7. REMOVE DEVICE SERIAL NUMBER LABELS AND PLACE ON FIELD DRAWINGS FOR LOCATION DESCRIPTIONS AND PROGRAMMING PURPOSES ONLY. STANDARD SINGLE GANG BOX "FIRE" MARKING, & CLEAR LENS VIGILANT 16-33 VDC OR 15.24 CM. (6") FROM CEILING WALL MOUNTED 8. USE SCREW TERMINAL BLOCKS FOR ALL WIRE TERMINATIONS, DO NOT USE WIRE NUTS. XX XX-STROBE CANDELA RATING(SEE FAS PLAN) MG1 RF-HDVM WHICHEVER IS LOWER 64 MM. (2 1/2") DEEP FA1.04 LEVEL 4 & LEVEL 5 FIRE ALARM SYSTEM PLAN OUTDOOR WALL MOUNTED HORN/STROBE, 203.2 CM. (80") AFF TO BOTTOM OF DEVICE 9. DO NOT ENTER ENCLOSURES FROM THE BOTTOM, THIS IS FOR THE BATTERIES. RED, WITH "FIRE" MARKING, & CLEAR LENS VIGILANT 24 VDC OR 15.24 CM. (6") FROM CEILING 74347U WITH WG4RTS WALL MOUNTED FA2.00 FIRE ALARM SYSTEM TYPICAL POINT-TO-POINT WIRING DIAGRAM WI' SET STROBE CANDELA RATING TO 65 CD WG4RF-HVMHC WHICHEVER IS LOWER 10. MODULES USED TO CONTROL EQUIPMENT SHALL BE INSTALLED WITHIN 0.914 m (3') OF THE EMERGENCY CONTROL DEVICES THAT CONTROLS THE EQUIPMENT. CEILING MOUNTED HORN/STROBE, RED, WITH STANDARD 101.6 MM. OH "FIRE" MARKING, & CLEAR LENS VIGILANT 16-33 VDC (4") SQUARE BOX 54 MM. CEILING MOUNTED 11. THE LOCATION OF THE CIRCUIT DISCONNECT MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. XX XX-STROBE CANDELA RATING(SEE FAS PLAN) MGCFR-HDVM (2 1/8") DEEP CEILING MOUNTED STROBE, RED, WITH "FIRE" STANDARD 101.6 MM. MARKING, & CLEAR LENS VIGILANT 16-33 VDC (4") SQUARE BOX 54 MM. CEILING MOUNTED XX XX-STROBE CANDELA RATING(SEE FAS PLAN) MGCFR-VM (2 1/8") DEEP Ju1Ar END-OF-LINE RESISTOR 4 WATERFLOW SWITCH PROVIDED BY OTHERS 16* TAMPER SWITCH PROVIDED BY OTHERS 10. 16 cm (4") I ................................... ................................. ................................. CEILING E DEVICES MOUNTING HEIGHT DETAILS CO0 DETECTOR LOCATION IS ACCEPTABLE HERE 120 VAC CONDUITS HORN/STROBE 1 1 OUTDOOR r ' I 1 74347U (MG1RF-HDVM) o HORN/STROBE _J BACKBOX o ' A FINISHED CEILING X �� A DETECTOR LOCATION < OUTDOOR IS NOT ACCEPTABLE HORN/STROBE IN HATCHED LOCATION (WG4RF-HVMHC) N PULL STATION \� S D EWALL E _ (GSA-M278) \ U REV DESCRIPTION DATE APPROVED { (OPTIONAL) 00 REVISIONS CONDUIT KNOCKOUTS FLOOR PLANS PROVIDED BY: PHONE FACP 0 N) FOR: PHONE 122 cm (48") TO 216 cm (85")TO 203.2 cm (80") TO 183 cm 152.4 cm NO CONDUIT INTO TOP OF DETECTOR DRAWN BY: DATE TOP BOTTOM BOTTOM (72") OR (60") THE BOTTOM OF ACCEPTABLE HERE ANO 7/16/2016 TO TOP TO CENTER THESE BOXES erima� CHECKED BY: DATE Whichever is lower InterMountain APPROVED BY: * EXCEPTION: IF A BATTERY CABINET IS REQUIRED FOR THE FIRE ALARM CONTROL PANEL, ONLY THEN Fire at security MAY CONDUIT PENETRATE INTO BOTTOM OF THE Mil\ FINISHED FLOOR FINISHED FLOOR ' FIRE ALARM CONTROL PANEL. A '`_N NICET LEVEL IV 98794 MERIDIAN INTERMOUNTAIN FIRE & SECURITY ABOVE ACCEPTABLE HEIGHT P.O. BOX 3940 AVON CO, 81620 BELOW ACCEPTABLE HEIGHT -00,------- TEL. NO. (970) 748-8888 TOV FIRE STATION #1 RENOVATION VAIL, COLORADO 81657 PROPER MOUNTING FOR DETECTORS DETAIL TITLE,PROJECT DRAWI G INDEXNOTES, DETAILS SCALE SCALE: NONE NOTPROX.TO SCALE DWG NO. REV SHEET N0. FAO. 00 1 OF 7