Vail Fire&Emergency Services
Fire & 08/24/16
Security
SimplexGrinnell
August 11, 2016
Vail Fire and Emergency Services
2399 North Frontage Road
Vail, Colorado 81657
Re: Chalets at Vail
Unit 1A Remodel
151 Vail Lane
Vail, Colorado 81657-4511
Scope of Work:
We have been contracted by Vail Chalets to perform work on the existing SimplexGrinnell
FACP (4100U network system) located at the above referenced project. The family room and
office in the existing unit lA first floor will remodeled to create a smaller family room and a
bedroom.
This letter is our request for a permit to be issued for the following work:
1. (1) existing wall mount speaker strobe (circuit 7:S317:N1-1) to be relocated to the new
bedroom wall and reconnected to existing circuits. Added wire approximately 6 feet.
2. (1)new wall mount 110 candela speaker strobe to be installed in the new bedroom and
connected to existing circuits (circuit 7:S3/7:N1-1). Added current to 7:N1-1 will be
.2520 amps, added wattage to existing amplifier will be .5 Watts. Approximately 38 feet
will be added to the existing circuits for the new device.
3. (1)photo sensor with sounder base to be relocated for better coverage in the new
bedroom.No added current.
4. On-site technical services to temporarily de-program and program alarm points affected.
There will be no change to the existing sequence of operations.
5. Provide Record of Completion at final test.
Please let us know if we can furnish any other information to aid in your review process.
If you should have any questions please contact me at 303-552-4521.
Thank you,
Nancy Wiltsie
Senior Designer
NICET III (Cert. # 93727,thru 03/01/2015)
SimplexGrinnell
Denver, Colorado