HomeMy WebLinkAboutA16-0052_FA-1_1478896669.pdf ijiTh 4 ur ti b #k 4trii qo '� Vail Fire&Emergency Services 09/22/16 BATTERY CALCULATION LOCATION: 2171 N FRONTAGE RD HOURS OF SUPERVISION: 24 HOURS MINUTES OF ALARM: 5 MINUTES PANEL: POTTER PFC-6075 Device Device Total Total PART Supervisory Alarm Supervisory Alarm VOLTAGE DROP CALCULATION ITEM QTY NUMBER DESCRIPTION Current Current Current Current PANEL : POTTER PFC-6075 LOCATION: 2171 N FRONTAGE RD 1 1 6075 PANEL 0.130000 0.220000 0.130000 0.220000 TOTAL TOTAL CURRENT ESTIMATED 2 1 PSA SMOKE DETECTOR 0.000325 0.001200 0.000325 0.001200 CURRENT CURRENT CURRENT CURRENT PER STARTING ONE-WAY CIRCUIT MIN. INSTALLED BY: 3 1 APS-DA PULL STATION 0.000325 0.000325 0.000325 0.000325 AVAILABLE CIRCUIT CIRCUIT PER PER PER CIRCUIT CIRCUIT WIRE WIRE VOLTAGE FINAL OPERATE FOR DEVICES NUMBER TYPE CIRCUIT DEVICES QUAN DEVICE DEVICE REMAINING VOLTAGE GAGE DISTANCE DROP VOLTAGE VOLTAGE 4 1 DCM-4 DUAL MONITOR MODULE 0.000325 0.001000 0.000325 0.001000 5.000 Circuit 1 NAC 3.000 110cd H/S 1 0.212 0.212 2.788 20.4 14 100 0.135 20.265 16.000 5 4 SCM-4 MONITOR MODULE 0.000325 0.001000 0.001300 0.004000 6 1 P2R 110cd HORN/STROBE 0.000000 0.212000 0.000000 0.212000 Pre Action Fire, Inc Circuit 2 NAC 3.000 110cd H/S WP 1 0.212 0.212 2.788 20.4 14 125 0.169 20.231 16.000 7 1 P2RK 110cd HORN/STROBE EXTERIOR 0.000000 0.212000 0.000000 0.212000 PANEL TOTALS TOTAL: 0.132275 0.650525 TOTAL NOTES: NEC 2014 TABLE 8 PO Box 478 SUPERVISORY: CURRENT Denver, CO 80201 USED 0.424 Current draws are Average (RMS) amperes. wire gage resistance ohms per 1000 feet SUB-TOTAL: 0.132275 AMPS TOTAL All voltage calculations are in volts D.C. 12 2.01 24 HOURS OF SUPERVISORY: 24.000000 HOURS 303 CURRENT Voltage drops are calculated assuming all of 14 3.19 ( ) 682-01 13 SUB-TOTAL: 3.174600 AMP HOURS AVAIL 5.000 the load is at the end of the circuit. 16 5.08 (303) 872-9015 FAX ALARM: TOTAL Voltage Drop = Resistance X (one way wire Distance X2) X circuit Amps 18 8.08 SUB-TOTAL: 0.650525 AMPS Top of DeviceEll Ell CURRENT 5 MINUTES OF ALARM: 0.083333 HOURS REMAINING 4.576 15 SUB-TOTAL: 0.054210 AMP HOURS Lens of Strobe \75 ) TOTALS: Top of Cabinet DROP CALCULATIONS TOTAL SUPERVISORY: 3.174600 AMP HOURS TOTAL ALARM: 0.054210 AMP HOURS Max in FACP FAPS flVOLTACE TOTAL: 3.228810 AMP HOURS bellow Max 0 " Top of Unit FAA MAP 11 SPARE OF 20% (SPARE) 0.645762 AMP HOURS ceiling (96") Top of Box MINIMUM BATTERY SIZE REQUIRE[ 3.874573 AMP HOURS Min Min P BATTERIES SUPPLIED 7.000 AMP HOURS 7 6" 6 8 (90") (80") 5'4" 4,0" (64") (48") Existing tenant remodel that has a sprinkled basement. BATTERY CALCULATIO\ S CO\ TROL PA\ EL All heights are Lo / measured from (AFF) Installation of an addressable Potter PFC-6030 sprinkler monitoring system. <IC CO / Above Finished Floor Area: 5,285sf Occupancy Group A-2 Construction Type: V-B Codes used: IEC 2015ed., NEPA 72 2013ed. DEVICE MOUNTING HEIGHTS r 1 le* SCOPE OF WORK 0 L 0 I QUAN. PART # DESCRIPTIO \ 1 PFC-6075 POTTER CONTROL PANEL SYMBOL DESCRIPTION DESC � PT0 \ CLASS TYPE D0 1 PSA POTTER SMOKE DETECTOR SIGNALING LINE CIRCUITS B 2 #16 AWG FPLP FACP FIRE ALARM CONTROL PANEL 2 APS-DA POTTER PULL STATION MAP GRAPHIC MAP SYSTEM HORN/STROBE CIRCUITS B 2 #14 AWG FPLP 4 SCM-4 POTTER MONITOR MODULE 0 1 1 DCM-4 POTTER DUAL MONITOR MODULE KHS KITCHEN HOOD SYSTEM 1 P2R SYSTEM SENSOR MULTI CANDELA HORN/STROBE F PULL STATION 1 P2RK SYSTEM SENSOR EXTERIOR HORN/STROBE (2) SMOKE DETECTOR (PHOTOELECTRIC) Z1 PS1270 POWER SONIC 7 AMP HOUR BATTERY P (AIM) ADDRESSABLE MONITOR MODULE WIE CHART c6‘11\ 2 ADDRESSABLE DUAL MONITOR MODULE HORN WITH STROBE MATERIALS LIST �75 (NUMBER INDICATES CANDELA) CNI f-Z--1 WATER FLOW SWITCH TAMPER VALVE F SUBMITTAL PREPARED BY: EOL END OF LINE RESISTOR Syste T O u t D u is RE A A Control Panel Notification SafetyControl D FIRE DEPARTMENT KNOX BOX Annunciation S ( L E G E\ 3 �o,�,°� Alarm Design Solutions Inc. 8391 Delaware St, Suite 103 ��o`�°�°� °�0�°o Denver, CO 80221 a°t ,�°t G c)\' .c'� �,�° (303) 828-0802 �azc o\°c `�°J<.,6 .\zo °� °c F� �°�'° �\�•t� o G \�a o§i, Goy �° °> o` o�� \o� alarmdesignsolu@cs.com �°moo`c• &s:\J.SO&. cpo`.a\ P\° ��� c:"\o--c.,� Po&k:)A"5\oto,te Pia J�ooe c;\-k c.;- c\' Pot�\%c\ & \ GoO \)c JOB NUMBER: 5357 co co P P co O o t, cP cz Go es' zc arm °c ‘,.°c cl roc roc O \°c °c k\ °c� CD\ �z °c °� o\ P o0 0o P P C, `Z` � �5 z c �, Q ,Z. WP °c& °ccj z,k_ z�` �`° �`, e``' .oc .6 ,z) (3�z` e °s o,,6 s, ° MAP POTTERC� EOL CIRCUIT 2 �� �� . c ,R(=. ��`e �� °� �� �� ° �,,Q �,� P e, JQ JQ o 0 p v\, y� co c, •\c \0 z,\o NATIONAL INSTITUTE FOR CERTIFICATION 1 10 RE `z ,`� 2 ,`� ,`z ,`2 ,`z `z ,`� �\ �� �� �� c� i, C)° IN ENGINEERING TECHNOLOGIES System I� l,I t 5 0 0 &,. 0 0 0 0 0 0 5 e e 5 0 0c` Fire Protection Engineering Technology Geo G,„ G\o N..-c, G�� GAJ G�� �� GAJ tom tom tom tom t`� e° r� ro Fire Alarm rm S ste m s 120 VAC - PEC- 6075 % �� EOL R� CIRCUIT 1 Smoke Detector X XP P P P P XP •.,c,XP X Q y DEDICATED CONTROL 110 2 Pull Station X X X X X 4 01 02 03 �� 05 08 3 Kitchen Hood System X X X X X PA\ EL 4 Sprinkler Water Flow Switch X X X X X X I HONEYWELL Ht 0 AIM AIM AIM AIM AIM 5 Sprinkler Tamper Valves X X X X IPGSM-4G P 2 6 Ground Fault X X X X Joel Blatt S.E.T. 7 Open Circuit X X X X NICET #103704 Level IV C❑MMUNICAT❑R KHS KHS KHS 8 Notification Circuit Trouble X X X X f f ,c-{Z-o--[%--1. 9 Low Battery X X X X EXP. 10/1/2019 06 10 AC Power Failure X X X X DATE:09/14/16 SCALE: N.T.S. 07 11 Communicator Trouble Condition X X X X REVISIONS: #1 PAGE NAME: TITLE PAGE Index: ONE L \ E AG� AV OE OPEATONSFA- 1 . Title Page\ flSEQUE\ CEA1 FA-2. Floor Plan FA-3. System Map SHEET 1 OF 3