Loading...
HomeMy WebLinkAboutA17-0020_Scope of work letter_1492204140.pdf (4OF1/4 dikW1 Shaner _ife Safety Vail Fire&Emergency Services 04/14/17 PO Box 1073, Frisco, CO 80443 970.409.9082; fax 970.797.1898 April 10, 2017 Mike Vaughan Vail Fire & Emergency Services Vail, Colorado Re: Vail Racquet Club—Phase 5 Dear Mike, Approved for install This letter outlines an upcoming scope of work to be performed at Vail Racquet Club. This work will be performed by Thul Electronics. This scope constitutes Phase 5 of a series of upgrades planned at this complex. Vail Racquet Club consists of 15 buildings and one Clubhouse. The Clubhouse is up to date. Phase 1 consisted of upgrades to Buildings 3, 4 and 5. Phase 2 was upgrades to Buildings 1, 2 and 6. Phase 3 covered buildings 7, 8 and 9. Phase 4 covered buildings 10, 11 and 12. This phase, Phase 5, is the final phase and will include the following upgrades: • Fire alarm panel replacement in buildings 13 and 14 • Conversion of unit smoke detectors to point addressable through the installation of addressable monitor modules at each device • Installation of one wireless carbon monoxide detector per unit to be located in the central hallway outside of sleeping rooms adjacent to the existing hallway smoke detector • Conversion of existing common area heat detectors and manual pull stations to addressable through the installation of addressable modules • Installation of one outside strobe on each building to provide designation to an approaching fire department truck Device counts and equipment data sheets are attached. Please advise if a perm' may be issued. Sincerely, 'Nits4,©iRff(0-a Deborah L. Shaner, P.E. e•'� ,to Fire Protection Engineer r c.); 352331 , L �t+ i