Loading...
HomeMy WebLinkAboutB14-0201_B14-0201 Test & Balance Report_1443219420.pdf TEST, ADJUST AND BALANCE REPORT PROJECT MARRIOTT MOUNTAIN VIEW #1149 PREPARED FOR R&H MECHANICAL REPORT ISSUE DATE 9/22/2015 X REVIEWED _REVISE AND RESUBMIT REJECTED FURNISH AS CORRECTED Corrections or comments made on the shop drawings during this PREPARED BY review do not relieve contractor from compliance with requirements of the drawings and specifications. This check is only for review of general conformance with the design concept of the project and general compliance with the information given in the contract documents. The contractor is responsible for.confirming and H VAC TAB I I c correlatingrons all iqu and dimensions;;coordinating ting ll ontechniques work with that of all other trades;and performing his work in a satisfactory manner. Date: 9/25/15 By: R&H Mechanical P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB I l c INSTRUMENT CALIBRATION REPORT DATE: 9/1/2015 PROJECT : MARRIOTT PROJECT ALTITUDE: 22.0"HG INSTRUMENT/SERIAL# APPLICATION DATE OF USE CALIBRATION CALIBRATION DATE DUE DATE SHORTRIDGE ADM-870C/#M09211 AIR FLOW READINGS 9/1/2015 06/12/2014 06/012/2015 ANEMOMETER#T57251515001 AIR FLOW READINGS 9/1/2015 04/6/2015 04/6/2016 SHORTRIDGE FLOW HOOD AIF FLOW READINGS 9/1/2015 * * TH-720 HYGROMETER/#TH7200950003 AIR TEMP/HUMIDITY NOT USED 06/04/2014 06/04/2015 PITOT TUBE 18" PRES.READINGS 9/1/2015 N/A N/A PITOT TUBE 24" PRES.READINGS 9/1/2015 N/A N/A PITOT TUBE 36" PRES.READINGS NOT USED N/A N/A PITOT TUBE 48" PRES.READINGS NOT USED NA NA SHIMPO TACHOMETER /#C105B0010 RPM READINGS NOT USED 06/18/2014 06/18/2015 FLUKE 375/#21290229 VOLT/AMP 9/1/2015 06/04/2014 06/04/2015 SHORTRIDGE HDM-250/#W08162 WATER PRES.READINGS 5/5/2015 06/12/2014 06/12/2015 ASCROFT/0-100 PSI/#DO68332-06 WATER PRES.READINGS NOT USED * * FLUKE 561 THERMOMETER/22370109 TEMP.READINGS NOT USED 06/19/2014 06/19/2015 REFRACTOMETER RHA-100 /#RHA- GLYCOL%READINGS 5/5/2015 N/A N/A 100 *CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: HVAC TAB Ilc TEST, ADJUST AND BALANCE REPORT THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS OBTAINED IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS. ANY VARIANCES FROM THE DESIGN REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT. THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE,TO THE EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED THROUGH- OUT THIS SURVEY. THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE PROJECT SPECIFICATIONS. CERTIFIED BY: DATE: 91I Sr THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING, ADUSTING AND BALANCING'OF ENVIRONMENTAL SYSTEMS AND THE PROJECT SPECIFICATIONS. CERTIFIED BY: ��- DATE: 11 ' °94 475-- HVAC TAB Ilc WARRANTS THAT THE AIR AND HYDRONIC SYSTEM EVALUATED DURING THIS SURVEY IS OPERATING AT THE SPECIFIED LEVELS AS SHOWN WITHIN THIS REPORT,AT AND ONLY AT THIS TIME. HVAC TAB Ilc MAKES NO OTHER WARRANTIES, STATED OR IMPLIED, CONCERNING THE CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS EQUIPMENT PASS THIS TIME. CERTIFIED Michael T.Richardson Page: 1 HVAC TAB,LLC 113-084-03 Expires 2/22!2417 NATIONAL BALANCING COUNCIL HVAC TAB lic AIR APPARATUS TEST REPORT DATE: 9/1/2015 PROJECT: MARRIOTT SYSTEM: FC-1 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER CARRIER MANUFACTURER - MODEL 42DFA16WLHY6AY2 HP R.P.M. - - SERIAL NF PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET TOTAL 1600CFM@0.5"ESP VOLTS AMPS - - MIN OSA CFM 200 CFM THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE (AMPS) NONE FAN BORE DD SET AT (AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE CENTERLINE MOTOR ADJ PULLEY SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 1606 FAN R.P.M. DD DD OSA CFM 330 VOLTAGE 207 207 RETURN CFM 1276 AMPERAGE 2.0 3.8 F COIL ATMOS I -0.59" O CW 0.03" L 'J HW T E R NOTES: HI SPEED PAGE: HVAC TAB lic AIR APPARATUS TEST REPORT DATE: 9/1/2015 PROJECT: MARRIOTT SYSTEM: FC-2 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER CARRIER MANUFACTURER - MODEL 42DFA16WLHY6AY2 HP R.P.M. - - SERIAL NF PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET TOTAL 1600CFM@0.5"ESP VOLTS AMPS - - MIN OSA CFM 200 CFM THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE (AMPS) NONE FAN BORE DD SET AT (AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE CENTERLINE MOTOR ADJ PULLEY SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 1489 FAN R.P.M. DD DD OSA CFM 335 VOLTAGE 208 208 RETURN CFM 1154 AMPERAGE 1.1 4.3 F COIL ATMOS L -0.50" O CW 0.09" T 'J HW E R NOTES: HI SPEED PAGE: HVAC TAB Ilc AIR TERMINAL TEST REPORT DATE: 9/1/2015 PROJECT: MARRIOTT SYSTEM: FC-1 / FC-2 SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-1 1 CD 24/24 260 216 256 2 CD 24/24 260 276 254 3 CD 24/24 260 244 252 4 CD 24/24 275 230 282 5 CD 24/24 275 324 278 6 CD 24/24 275 222 284 1605 1512 1606 TOTAL FC-2 1 CD 24/24 260 139 235 2 CD 24/24 260 140 244 3 CD 24/24 260 129 244 4 CD 24/24 275 154 248 5 CD 24/24 275 158 256 6 CD 24/24 275 115 262 1605 832 1489 TOTAL NOTES: PAGE: HVAC TAB lic AIR APPARATUS TEST REPORT DATE: 9/1/2015 PROJECT: MARRIOTT SYSTEM: FC-3 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER CARRIER MANUFACTURER - MODEL 42DFA16WLHY6AY2 HP R.P.M. - - SERIAL NF PHASE FRAME - - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET TOTAL 1600CFM@0.5"ESP VOLTS AMPS - - MIN OSA CFM 55 CFM THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE (AMPS) NONE FAN BORE DD SET AT (AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE CENTERLINE MOTOR ADJ PULLEY SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 1408 FAN R.P.M. DD DD OSA CFM 65 VOLTAGE 208 208 RETURN CFM 1343 AMPERAGE NA NA F COIL -0.11" L -0.15" O CW 0.22" T HW E R NOTES: HI SPEED PAGE: HVAC TAB lic ERV FAN TEST REPORT DATE: 9/1/2015 PROJECT: MARRIOTT SYSTEM: ERV-1 FAN NUMBER ERV-1 NOT USED UNIT DATA UNIT DATA UNIT DATA MANUFACTURER RENEW AIRE MODEL EV 450 IN SERIAL E14 2518L SCHEDULE RATING/OUTLET TOTAL 400CFM@0.75"ESP MOTOR DATA MOTOR DATA MOTOR DATA MANUFACTURER - - MOTOR HP RPM 0.6 - PHASE FRAME - - S.F. TYPE - - VOLTS AMPS I 208/230 3.9/3.6 DRIVE DATA DRIVE DATA DRIVE DATA MOTOR DRIVE BORE DD DD FAN DRIVE BORE DD DD NO. BELTS SIZE DD DD II DRIVE CHANGE ROTATION DD CORRECT STARTER DATA STARTER DATA STARTER DATA MFG. MODEL NONE NONE RANGE SET AT (AMPS) NONE NONE SET AT HERTZ REQ. THERM NONE NONE THERMAL PROTECTION NONE NONE TEST DATA TEST DATA TEST DATA CFM VOLTS 665 208 FAN RPM AMPS DD 2.2 RETURN-0.12" EXHAUST 0.10" RETURN-0. EXHAUST 0. 0 0 OUTSIDE AIR-0.18" SUPPLY 0.15" OUTSIDE AIR-0. SUPPLY 0. NOTES: HI SPEED PAGE: HVAC TAB Hc AIR TERMINAL TEST REPORT DATE: 9/1/2015 PROJECT: MARRIOTT SYSTEM: FC-3 / ERV-1 SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-3 1 CD 24/24 600 468 510 2 CD 24/24 400 280 364 3 CD 24/24 600 436 534 1600 1184 1408 TOTAL ERV-1 1 PITOT 8"R 200 - 330 2 PITOT 8"R 200 - 335 400 665 TOTAL ERV-1 RETURN 1 ER 24/24 190 222 I 222 2 ER 24/24 190 208 208 380 430 430 TOTAL NOTES: PAGE: HVAC TAB lic AIR APPARATUS TEST REPORT DATE: 5/5/2015 PROJECT: MARRIOTT SYSTEM: FC-4 AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA MANUFACTURER CARRIER MANUFACTURER X 2 MOTORS MODEL 42DDA20QRHY6AY2R HP R.P.M. 1/2 - SERIAL 107641-30-1 PHASE FRAME 1 - FAN TYPE CENTRIFUGAL S.F. TYPE - - RATING/OUTLET TOTAL 1900CFM@0.5"ESP VOLTS AMPS 208 5.4 MIN OSA CFM 755 CFM THERMALLY PROTECTED - STARTER DATA DRIVE DATA MANUFACTURER NONE MOTOR DRIVE DD MODEL NONE MOTOR BORE DD SIZE/THERMAL NO. NONE FAN DRIVE DD RANGE (AMPS) NONE FAN BORE DD SET AT (AMPS) NONE NO. BELTS & SIZE DD REQ. THERMAL NONE ROTATION CORRECT RATING (AMPS) NONE CENTERLINE MOTOR ADJ PULLEY SPEED AIRFLOW DATA TEST DATA INITIAL FINAL SUPPLY CFM 2138 FAN R.P.M. DD DD OSA CFM 550 VOLTAGE 208 208 RETURN CFM 1588 AMPERAGE 3.5 3.5 F COIL -0.20" L -0.55" O CW 0.13" T HW E R NOTES: PAGE: HVAC TAB Ilc AIR TERMINAL TEST REPORT DATE: 5/5/2015 PROJECT: MARRIOT SYSTEM: FC-4 SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-4 1 CD 13"R - 169 169 2 CD 13 R - 162 162 3 CD 13 R - 168 168 4 CD 13 R - 162 162 5 CD 13 R - 160 160 6 CD 13R 171 171 7 CD 13 R 167 167 8 SR 20/6 - 526 526 HALL _ REGISTERS 9 SR 20/6 - 453 453 HALL REGISTERS 1900 2138 2138 TOTAL NOTES: PAGE: HVAC TAB lic BALANCE VALVE TEST REPORT DATE: 5/5/2015 PROJECT: MARRIOTT SYSTEM: FC-1 / FC-2/ FC-3/ FC-4 FLOW METER DESIGN MEASURED DESIGN DESIGN VALVE LOCATION TYPE SIZE AP GPM FINALA P POSITION FINAL GPM OPEN FC-1 HW TA 1" 7.1 0.49 4.2 5.06 FC-1 CW TA 1" 5.4 7.97 1.7 5.45 FC-2 HW TA 1" 7.1 0.57 4.3 5.46 FC-2 CW TA 1' 5.4 1.56 2.6 5.45 FC-3 HW TACO 1" 6.9 - 86% NA FC-3 CW TACO 1" 5.5 16.4 65% 5.35 FC-4 HW TACO 1 1/4" 7.1 4.1 100% 5.1 FC-4 CW TACO 1" 7.1 31.0 75% 7.2 NOTES: PAGE: / 11aN INIONNNIL PHASE I GENERAL NOTES: PLAN NOTES: � - . N • 1. ToR To RE Fc.GET-ERIL I. ERV ORM.,THE ft0 ,R ;OJECT.PAII WI.I°ETM INSTALISoOt a lR comNECTN e � 00 LFCYMw1.1EFaNITB ORYOWNGF VA0. OTUAuo couuaidREcnv THs a• _-.. - - -� ^� a81 ucwRPO4 TPEFR PRa ISTALLePIIII° L s't'o RR,I 1 > IEDLITIST DUCT TO MO MAN. LL FM Oonom mut+P.I.14,JNRRFF OWE PxI0TNG0A o*gr REWV2,Ba0 _ _ �,� `i \ _. ` 0. Ayl OVGauORRpweslSgNSARF 9NpwNWe 4 Gou N'aTI: -ZIL Dsr ol.CSTo Gx�Lk TO ouT NO aeloMpicE lx olxids6 O Ev CIIPREYIOIMRT L¢EO • uecesEARTroRccouxisORwemil.um.. 'T rNNw pwedWW< VrHE a• eaO IQ'W. $ 111 ''' . Oe w� e ALL RpDIJOrA/oxo DucuCOlaEc,n¢SRWNO lk.DuC come,DE ©SO4NECT NEW 10'I.IME-6IMIITO • - III E uEW ryaiuRowrefeduecwawlEurilco G . BT4TEII to RCM.oPER6611•0.1.DuRNO ©00414E7ImatS.p> IMR MI TD SME 1 1 /{ • o FAN co ATI,,Ow SHALL .9144.1.11E EC.0 O oiFIPFNSEPsOiuw RcelmuNOFcn�T J I B"\ 00101.ee B.MISALL REwWRK MON NITCR iAIII TO _ ^E 01 BQ D 7.2. ItM Nu r AieoweTxmRR PAEaluo n.,eo�uE p4lrec OO pONIE Yea fRN�ILfoa Mr.EOBGf1A RATEOMWMB ICHT.AssemeuEs 1 OF 1XE ASSEIT, Rov,AGKORAPT[MAIM Y ,'-I:,)F .B a pn A,9 E, YNRTwNAPuiEE.eGRee Elsow6sNAu'"a ORECYOG RE4bT�O GOt LPNG x�vrs'wo _ 9r IETLIRN own I414 9 1� O ALL DUCTWORK PAIL DE RAI In.TO uxO[RSIDE Ci sITRDDhmENRLR54DIMEAWLSE fal2.0 SU.I/N�uCt N AE CO rpR CD PA >r� ✓ WIRO- p lo£o,PRO rlmnolA lc DAMPER t alsriuocalwG ltehlirs.sTRuc-MOL REouweO.vER EMEND O ,owRioRa IN Flew. ETONAwLROOTOG£M1uO • Q-.� 'c " HEIGHTS.COORDINATE ArmRa4rwTDET..6,15 �e '� Nt GICe NEVI CWBer pxFvOC,GWITH AWE.eHFrmocK \� now-P E ANO PANT TO WWII. 44 THE VW<P,W. • .T PBPOEDPIC FAII.RR.MRS CON R e PRIOR SO WBNRT CO WINO ATO T�tEEa Ni�Fd, WOW eV1Mv pwnreR ..... O ad1 TION • IES. 67 too • N j II;' .4�p u • �� J • frij I• N(1) s U QnCO o�o.B g �'- ,oma I, .o Z V • / I 0 ,. � • "` IIS z •. La. r„ell. 0.,-,,, , ....... .„,„.. _a - o• E O . • :a iy NII� ° Mw 71 •• . O raIsNII 0dj O • 0. • .O. .O O..RriliMIMIEIMp —J ,ia...tio,- _ _ r.Q° v OZ { 0- Lf V , Ira_____...., fr ...4.. • • C// • 0 e© o- � W� Q ,wG.wilGRaMMx ;, }IL7 1 '� IISo19 t a . 11 o �/ o J roe nu,aaE. PRATE 1 PARTIAL MECH.HVAC • • - PLAN _ '.. - - . •_ x ,aer FR.TcTlosrev,LW NORTH vow.e. W.,1 PARTIAL MECHANICAL HVAC PLAN r� .._,„...•.,..„,„„ M2PERMIT BID DOCUMENTS s .J �,� , r-