HomeMy WebLinkAboutB14-0264_Fisher firestop submittal 11-18-15_1447973760.pdfHilti Firestop Systems
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com • en español 1-800-879-5000 • P.O. Box 21148, Tulsa, Oklahoma 74121
Hilti (Canada) Corp. 1-800-363-4458 www.hilti.ca • 2360 Meadowpine Blvd., Mississauga, Ontario L5N 6S2
Hilti. Outperform. Outlast.
Firestop Submittal Package
Project:
Date:
Submitted by:
Hilti Firestop
Saving lives
through innovation
and education
This submittal is auto-generated based on user-selected inputs.
Therefore, Hilti makes no representation as to the suitability of these systems for their intended use.
Table Of Contents
UL Listings
C-AJ-1154.............................................................................................................................................1
C-AJ-2098 (US Only)............................................................................................................................2
C-AJ-2167 (US Only)............................................................................................................................3
C-AJ-2170 (US Only)............................................................................................................................4
C-AJ-2305 (US Only)............................................................................................................................5
C-AJ-2335 (US Only)............................................................................................................................6
C-AJ-3095.............................................................................................................................................7
C-AJ-5096.............................................................................................................................................9
C-AJ-7051...........................................................................................................................................11
C-AJ-7084...........................................................................................................................................12
C-AJ-8099...........................................................................................................................................13
C-AJ-8148...........................................................................................................................................15
W-L-1054............................................................................................................................................17
W-L-2075 (US Only)...........................................................................................................................19
W-L-2128 (US Only)...........................................................................................................................20
W-L-3065............................................................................................................................................21
W-L-3310............................................................................................................................................23
W-L-5096............................................................................................................................................24
W-L-7042............................................................................................................................................26
W-L-7096............................................................................................................................................27
W-L-7153............................................................................................................................................28
W-L-7156............................................................................................................................................30
W-L-8004 (US Only)...........................................................................................................................32
CFS-S SIL GG
Product Data Sheet for CFS-S SIL GG Firestop Silicone Sealant......................................................34
UL Certificate of Compliance for CFS-S SIL SL and CFS-S SIL GG Firestop Silicone Sealant.........35
LEED information for CFS-S SIL GG Firestop Silicone Sealant.........................................................36
CFS-S SIL SL
Product Data Sheet for CFS-S SIL SL Firestop Silicone Sealant.......................................................37
UL Certificate of Compliance for CFS-S SIL SL and CFS-S SIL GG Firestop Silicone Sealant.........38
LEED information for CFS-S SIL SL Firestop Silicone Sealant..........................................................39
CP 606
Product Data Sheet for CP 606 Flexible Firestop Sealant..................................................................40
UL Certificate of Compliance for CP 606 Flexible Firestop Sealant...................................................41
LEED information for CP 606 Flexible Firestop Sealant.....................................................................42
CP 618
Product Data Sheet for CP 618 Firestop Putty Stick..........................................................................43
UL Certificate of Compliance for CP 618 Firestop Putty Stick............................................................44
CP 648-E (Endless)
Product Data Sheet for CP 648-E Firestop Wrap Strip.......................................................................45
UL Certificate of Compliance for CP 648-E and CP 648-S Firestop Wrap Strip.................................46
LEED information for CP 648-S and CP 648-E Firestop Wrap Strip..................................................47
FS-ONE MAX
Product Data Sheet for FS-ONE MAX Intumescent Firestop Sealant................................................48
Buy American Certification for FS-ONE MAX Intumescent Firestop Sealant.....................................51
LEED information for FS-ONE MAX Intumescent Firestop Sealant...................................................52
Mineral wool
UL Certificate of Compliance for Mineral Wool...................................................................................53
Material Safety Data Sheet (MSDS) for Mineral Wool........................................................................54
LEED information for Mineral Wool.....................................................................................................56
System No. C-AJ-1154
SECTION A-A CAJ 1154)ORRURU:DOO$VVHPEO\²0LQLQPPWKLFNUHLQIRUFHGOLJKWZHLJKWRUQRUPDOZHLJKWSFIRUNJPFRQFUHWH:DOO
may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 14 in. (356 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
7KURXJK3HQHWUDQWV²2QHPHWDOOLFSLSHFRQGXLWRUWXELQJWRLQVWDOOHGHLWKHUFRQFHQWULFDOO\RUHFFHQWULFDOO\ZLWKLQWKHILUHVWRSV\VWHP7KH
annular space shall be min 0 in. to max 3-1/4 in. (83 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The
following types and sizes of metallic pipes, conduits or tubing may be used:
$6WHHO3LSH²1RPLQPPGLDPRUVPDOOHU6FKHGXOHRUKHDYLHUVWHHOSLSH
%&RQGXLW²1RPLQPPGLDPRUVPDOOHUVWHHOHOHFWULFDOPHWDOOLFWXELQJRUVWHHOFRQGXLW
&&RSSHU7XELQJ²1RPLQPPGLDPRUVPDOOHU7\SH/RUKHDYLHUFRSSHUWXELQJ
'&RSSHU3LSH²1RPLQPPGLDPRUVPDOOHU5HJXODURUKHDYLHUFRSSHUSLSH
)LUHVWRS6\VWHP²7KHILUHVWRSV\VWHPVKDOOFRQVLVWRIWKHIROORZLQJ
$3DFNLQJ0DWHULDO²0LQHUDOZRROEDWWLQVXODWLRQILUPO\SDFNHGLQWRRSHQLQJDVDSHUPDQHQWIRUP3DFNLQJPDWHULDOWREHUHFHVVHGIURPWRS
surface of floor or from both surfaces of wall to accommodate the required thickness of fill material. As an option to the above, backer rod
and/or foamed plastic backer material may be used.
%)LOO9RLGRU&DYLW\0DWHULDO
²6HDODQW²0LQLQPPWKLFNQHVVRIILOOPDWHULDODSSOLHGZLWKLQWKHDQQXOXVIOXVKZLWKWRSVXUIDFHRI
floor or with both surfaces of wall. At the point contact location between pipe and concrete, a min 1/2 in. (13 mm) diam bead of fill material
shall be applied at the concrete/pipe interface on the top surface of floor and on both surfaces of wall.
+,/7,&216758&7,21&+(0,&$/6',92)+,/7,,1&²)621(6HDODQWRU)621(0$;,QWXPHVFHQW6HDODQW
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 06, 2015
A 3B
2
3A
3B 2
C CLAS S IFI
EDClassified by
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US ANSI/UL1479 (ASTM E814)CAN/ULC S115
)5DWLQJ²+U )5DWLQJ²+U
75DWLQJ²+U )75DWLQJ²+U
/5DWLQJ$W$PELHQW²/HVV7KDQ&)0VTIW )+5DWLQJ²+U
/5DWLQJ$W)²&)0VTIW )7+5DWLQJ²+U
/5DWLQJ$W$PELHQW²/HVV7KDQ&)0VTIW
/5DWLQJ$W)²&)0VTIW
1
1
System No. C-AJ-2098
SECTION A-A CAJ 2098)ORRURU:DOO$VVHPEO\²0LQLQPPWKLFNUHLQIRUFHGOLJKWZHLJKWRUQRUPDOZHLJKWSFIRUNJPFRQFUHWH:DOO
may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 3 in. (76 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
(OHFWULFDO1RQPHWDOOLF7XELQJ²1RPLQPPGLDPRUVPDOOHUFRUUXJDWHGZDOO(17FRQVWUXFWHGRISRO\YLQ\OFKORULGH39&2QHWXEHWR
be centered within the firestop system. A nom annular space of 5/16 in. (8 mm) is required within the firestop system. Tube to be rigidly supported
on both sides of floor or wall assembly.
See Electrical Nonmetallic Tubing (FKHU) category in the Electrical Construction Materials Directory for names of manufacturers.
3DFNLQJ0DWHULDO²1RW6KRZQ²0LQHUDOZRROLQVXODWLRQILUPO\SDFNHGLQWRRSHQLQJDVDWHPSRUDU\IRUP3DFNLQJPDWHULDOWREHUHFHVVHGIURP
top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. In floors form may be removed
after fill material has cured.
)LOO9RLGRU&DYLW\0DWHULDO
²6HDODQW²0LQLQPPWKLFNQHVVRIILOOPDWHULDODSSOLHGZLWKLQWKHDQQXOXVIOXVKZLWKWRSVXUIDFHRIIORRURU
with both surfaces of wall.
+,/7,&216758&7,21&+(0,&$/6',92)+,/7,,1&²)62QH6HDODQWRU)621(0$;,QWXPHVFHQW6HDODQW
+Bearing the UL Listing MarkA
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 09, 2015
F Rating -- 3 Hr
T Rating -- 3 Hr
L Rating At Ambient -- Less Than 1 CFM/sq ft
L Rating At 400 F -- 4 CFM/sq ft
A
1
2
4
2CLASSIFIEDClassified by
Underwriters Laboratories, Inc.
to UL 1479
2
System No. C-AJ-2167
SECTION A-A CAJ 2167)ORRURU:DOO$VVHPEO\²0LQLQPPWKLFNUHLQIRUFHGOLJKWZHLJKWRUQRUPDOZHLJKWSFIRUNJPFRQFUHWH:DOO
may also be constructed of any UL Classified Concrete Blocks*. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified
hollow core Precast Concrete Units* having a min 2 in. (51 mm) concrete thickness below the core. Max diam of opening is 3 in. (76 mm).
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers.
7KURXJK3HQHWUDQWV²2QHQRQPHWDOOLFSLSHWREHLQVWDOOHGFRQFHQWULFDOO\RUHFFHQWULFDOO\ZLWKLQWKHILUHVWRSV\VWHP$QQXODUVSDFHEHWZHHQSLSH
and edge of opening to be min 0 in. (point contact) and max 5/8 in. (16 mm). Pipe to be rigidly supported on both sides of floor-ceiling assembly.
The following types and sizes of nonmetallic pipes may be used.
$3RO\YLQ\O&KORULGH39&3LSH²1RPLQPPGLDPRUVPDOOHU6FKHGXOHVROLGRUFHOOXODUFRUH39&SLSHIRUXVHLQFORVHGSURFHVV
or supply) or vented (drain, waste or vent) piping systems.
%&KORULQDWHG3RO\YLQ\O&KORULGH&39&3LSH²1RPLQPPGLDPRUVPDOOHU6'5&39&SLSHIRUXVHLQFORVHGSURFHVVRU
supply) piping systems.
)LOO9RLGRU&DYLW\0DWHULDO
²6HDODQW²0LQLQPPWKLFNQHVVRIILOOPDWHULDODSSOLHGZLWKLQWKHDQQXOXVIOXVKZLWKERWWRPVXUIDFHRIIORRU
or with both surfaces of wall. At point contact location, min 1/2 in. (13 mm) diam bead of sealant applied at pipe/concrete interface on bottom
surface of floor or both surfaces of wall.
+,/7,&216758&7,21&+(0,&$/6',92)+,/7,,1&²)621(6HDODQWRU)621(0$;,QWXPHVFHQW6HDODQW
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 09, 2015
F Rating -- 2 Hr
T Rating -- 0 Hr
A
2
3
1
2
3CLASSIFIEDClassified by
Underwriters Laboratories, Inc.
to UL 1479
3
System No. C-AJ-2170
SECTION A-A CAJ 2170)ORRURU:DOO$VVHPEO\²0LQLQPPWKLFNUHLQIRUFHGOLJKWZHLJKWRUQRUPDOZHLJKWSFIRUNJPFRQFUHWHIORRU
Wall may also be constructed of any UL Classified Concrete Blocks+. Maximum diameter of opening is 2 in. (51 mm).
See Concrete Blocks (CAZT), category in the Fire Resistance Directory for names of manufacturers.
7KURXJK3HQHWUDQWV²2QHQRPLQDOLQPPGLDPHWHUFURVVOLQNHGSRO\HWK\OHQH3(;6'5WXEHIRUXVHLQFORVHGSURFHVVRUVXSSO\RU
vented (drain, waste or vent) piping systems. The annular space between the tube and the periphery of the opening shall be min 1/4 in. (6 mm) to
a max 3/4 in. (19 mm). Pipe to be rigidly supported on both sides of the floor-ceiling assembly.
)LOO9RLGRU&DYLW\0DWHULDO²6HDODQW²0LQLQPPWKLFNQHVVRIILOOPDWHULDODSSOLHGZLWKLQWKHDQQXOXVIOXVKZLWKWRSVXUIDFHRIIORRU
or with both surfaces of wall.
+,/7,&216758&7,21&+(0,&$/6',92)+,/7,,1&²)62QH6HDODQWRU)621(0$;,QWXPHVFHQW6HDODQW
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 09, 2015
F Rating -- 2 Hr
T Rating -- 0 Hr
A
2
3 2
1CLASSIFIEDClassified by
Underwriters Laboratories, Inc.
to UL 1479
4
5
6
7
8
9
10
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 14, 2015
System No. C-AJ-7051
SECTION A-A CAJ 7051)ORRURU:DOO$VVHPEO\²0LQLQPPWKLFNUHLQIRUFHGOLJKWZHLJKWRUQRUPDOZHLJKWSFIRUNJPFRQFUHWHIORRU
or min 5-1/2 in. (140 mm) thick lightweight on normal weight concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*.
Max area of opening is 1024 in. sq (6606 cm2) with a max dimension of 32 in. (813 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
6WHHO'XFW²1RPE\LQE\PPE\1RJDXJHRUKHDYLHUJDOYVWHHOGXFW2QHVWHHOGXFWWREHSRVLWLRQHGZLWKLQWKHILUHVWRS
system. The annular space shall be min 1/4 in. (6 mm) to max 1-3/4 in. (44 mm). Duct to be rigidly supported on both sides of floor or wall
assembly.
)LUHVWRS6\VWHP²7KHILUHVWRSV\VWHPVKDOOFRQVLVWRIWKHIROORZLQJ
$3DFNLQJ0DWHULDOV²0LQLQPPWKLFNQHVVRIPLQSFINJPPLQHUDOZRROEDWWLQVXODWLRQILUPO\SDFNHGLQWRRSHQLQJDVD
permanent form between the bare steel duct and the periphery of the opening. Packing material to be recessed from top surface of floor or
both surfaces of wall as required to accommodate the required thickness of fill material.
%)LOO9RLGRU&DYLW\0DWHULDO
²6HDODQW²0LQLQPPWKLFNQHVVRIILOOPDWHULDODSSOLHGZLWKLQWKHDQQXOXVIOXVKZLWKWRSVXUIDFHRIIORRU
or with both surfaces of wall.
+,/7,&216758&7,21&+(0,&$/6',92)+,/7,,1&²&3)OH[LEOH)LUHVWRS6HDODQW)621(6HDODQWRU)621(0$;,QWXPHVFHQW
Sealant
6WHHO5HWDLQLQJ$QJOH²1RPLQE\LQE\PPE\1RJDXJHRUKHDYLHUVWHHODQJOHVDWWDFKHGWRDOOIRXUVLGHVRIWKHVWHHOGXFWRQ
the top surface or both surfaces of the wall. The angles shall be attached with No. 8 (or larger) steel sheet metal screws spaced max of 1 in. (25
mm) from each end and a max of 3 in. (76 mm) OC.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
A
A
2
3B
4
3A
1
C CLAS S IFI
EDClassified by
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US ANSI/UL1479 (ASTM E814)CAN/ULC S115
F Rating - 3 Hr )5DWLQJ²+U
T Rating - 1 Hr FT Rating - 1 Hr
FH Rating - 3 Hr
FTH Rating - 1 HR
11
12
13
14
15
16
17
18
19
20
21
22
23
Page: 1 of 2
System No. W-L-5096
SECTION A-A WL 5096Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
March 30, 2015
A
A
23
4 5
1A
1B
2
C CLAS S IFI
EDClassified by
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
US
ANSI/UL1479 (ASTM E814)CAN/ULC S115
F Ratings - 1 and 2 Hr (See Item 1)F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 0, 1/2 and 1 (See Items 3 and 4)FT Ratings - 0, 1/2 and 1 (See Items 3 and 4)
FH Ratings - 1 and 2 Hr (See Item 1)
FTH Ratings - 0, 1/2 and 1 (See Items 3 and 4)
:DOO$VVHPEO\²7KHRUKUILUHUDWHGZDOOERDUGVWXGZDOODVVHPEO\VKDOOEHFRQVWUXFWHGRIWKHPDWHULDOVDQGLQWKHPDQQHUVSHFLILHGLQWKH
individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
construction features:
$6WXGV²:DOOIUDPLQJVKDOOFRQVLVWRIHLWKHUZRRGVWXGVRUVWHHOFKDQQHOVWXGV:RRGVWXGVWRFRQVLVWRIQRPE\LQE\PP
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC.
%*\SVXP%RDUG
²1RPLQPPWKLFNIWPZLGHZLWKVTXDUHRUWDSHUHGHGJHV7KHJ\SVXPERDUGW\SHWKLFNQHVVQXPEHURI
layers, fastener type and sheet orientation shall be as specified in the individual U300, U400, V400 or W400 Series Design in the Fire
Resistance Directory. Max diam of openings is 14-1/2 in. (368 mm) for wood stud walls. Max diam of opening is 18-5/8 in. (473 mm) for steel
studs walls or sized to the outside diam of steel sleeve (Item 2) when optional steel sleeve is used.
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
6WHHO6OHHYH²2SWLRQDO0D[LQPPGLDP6FKHGXOHRUKHDYLHUVWHHOSLSHVOHHYHLQVHUWHGLQRSHQLQJFRUHGULOOHGWKURXJKZDOO
Length of steel sleeve to be equal to thickness of wall.
24
Page: 2 of 2
System No. W-L-5096
WL 50967KURXJK3HQHWUDQW²2QHPHWDOOLFSLSHRUWXELQJLQVWDOOHGFRQFHQWULFDOO\RUHFFHQWULFDOO\ZLWKLQWKHILUHVWRSV\VWHP3LSHRUWXEHWREHULJLGO\
supported on both sides of wall assembly. The following types and sizes of metallic pipes or tube may be used:
$6WHHO3LSH²1RPLQPPGLDPRUVPDOOHU6FKHGXOHRUKHDYLHUVWHHOSLSH:KHQVWHHOSLSHLVXVHG7)7DQG)7+5DWLQJV
are 1/2 hr and 1 hr when installed in 1 and 2 hr rated walls, respectively.
%&RSSHU7XEH²1RPLQPPGLDPRUVPDOOHU7\SH/RUKHDYLHUFRSSHUWXEH:KHQFRSSHUWXEHLVXVHG7)7DQG)7+5DWLQJV
are 1/2 hr and 1 hr when installed in 1 and 2 hr rated walls, respectively.
&&RSSHU3LSH²1RPLQPPGLDPRUVPDOOHU5HJXODURUKHDYLHUFRSSHUSLSH:KHQFRSSHUSLSHLVXVHG7)7DQG)7+5DWLQJV
are 1/2 and 1 hr when installed in 1 and 2 hr rated walls respectively.
3LSH&RYHULQJ
²0D[LQPPWKLFNKROORZF\OLQGULFDOKHDY\GHQVLW\QRPSFIRUNJPñJODVVILEHUXQLWVMDFNHWHGRQWKHRXWVLGH
with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied SSL tape. Transverse joints secured with metal
fasteners or with butt tape supplied with the product. The annular space between insulated penetrant and periphery of opening shall be min 0 in.
(point contact) to max 1-7/8 in. (48 mm).
When pipe covering thickness is less than 2 in. (51 mm), T, FT and FTH Ratings are 0 hr.
See Pipe and Equipment Covering-Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering
material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke
Developed Index of 50 or less may be used.
)LOO9RLGRU&DYLW\0DWHULDO
6HDODQW²0LQLQPPRUWKLFNQHVVRIILOOPDWHULDODSSOLHGZLWKLQDQQXOXVIOXVKZLWKERWKVXUIDFHVRIZDOO
assembly for At point contact an additional 1/2 in. (13 mm)bead of sealant shall be applied to the insulated pipe/ wall interface.
+,/7,&216758&7,21&+(0,&$/6',92)+,/7,,1&²)621(6HDODQWRU)621(0$;,QWXPHVFHQW6HDODQW
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification
(such as Canada), respectively.
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
March 30, 2015
25
26
27
28
29
30
31
32
33
Product Information
Hilti. Outperform. Outlast.
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com • www.us.hilti.com/firestop • en español 1-800-879-5000
Firestop Gun Grade Silicone Sealant CFS-S SIL GG
Product description
■A silicone based firestop sealant that provides maximum movement in
fire-rated joints, and seals through-penetration applications
Product features
■Halogen and solvent free
■Asbestos free
■Simple to use and apply
■Good adhesion without use of a primer
■Smoke, fume, water and UV resistant
■Excellent movement capability, meets 500 cycle requirements
(ASTM E 1966 and UL 2079)
■Meets Class I W-rating requirements
■Meets LEED™ requirements for indoor environmental quality credit 4.1
Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and
Coatings
Areas of application
■Sealing construction/expansion joints
■Top-of-wall joints
■Metal pipes
■Cable bundles
■HVAC penetrations
For use with
■Various base materials such as masonry, concrete, metal, etc.
■Wall and floor assemblies rated up to 4 hours
Examples
■Where a gypsum wall assembly meets the underside of a metal or
concrete deck
■Sealing expansion joints to impede the passage of fire, smoke and
toxic fumes
■Sealing around penetrations through fire-rated assemblies
Installation instructions
■Refer to what is included in the package, the MSDS, and the applicable
listing.
Technical Data* CFS-S SIL GG
Chemical basis Neutral elastic silicone
Density Approx. 1.4 g/cm3
Color Available in red, white, and gray
Application temperature 40°F to 104°F (5°C to 40°C)
Skin-forming time Approx. 15 min.
Curing time Approx. 2 mm / 3 days
Volume shrinkage Approx. 0 – 5%
Movement capability
(UL 2079)
Approx. 33%
Temperature resistance –40°F to 300°F (–40°C to 149°C)
Surface burning characteristics
(ASTM E84-12)
Flame spread: 0
Smoke development: 25
Sound transmission classification
(ASTM E 90-09)
59 (Relates to specific construction)
Tested in accordance with UL 2079
ASTM E 814
ASTM E 1966
ASTM C 920
UL 1479
ASTM E 84
ASTM G21
*At 73°F (23°C) and 50% relative humidity
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS AND
JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
5BP5
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Visit fbcsystemcompatible.com.
FBC™ is a trademark of
the Lubrizol Corporation.
34
CERTIFICATE OF COMPLIANCE
Certificate Number 20131115-R13240
Report Reference R13240
Issue Date 2013-November-15
William R. Carney, Director, North American Certification Programs
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus
Page 1 of 1
Issued to: Hilti Construction Chemicals, Div of Hilti Inc.
5400 S 122nd East Ave
Tulsa, OK 74146
This is to certify that
representative samples of
Fill, Void or Cavity Materials
Fill, Void or Cavity Materials Certified for Canada
CFS-S SIL GG and CFS-S SIL SL for use in Through-
Penetration Firestop and Joint Systems in the UL Fire
Resistance Directory and in the Products Certified for
Canada Directory.
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through-Penetration
Firestops," – Edition 3 – Revision Date 2012/10/19
ANSI/UL 2079, "Tests for Fire Resistance of Building Joint
Systems," – Edition 4 – Revision Date 2012/12/12
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop
Systems." – Edition 4 – Issue Date 2011/06/01
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Classification Mark should be considered as being covered by
UL’s Classification and Follow-Up Service.
The UL Classification Mark includes: UL in a circle: with the word “CLASSIFIED” (as shown); a control
number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL’s evaluation of
the product; and the product category name (product identity) as indicated in the appropriate UL
Directory.
Look for the UL Classification Mark on the product.
35
Hilti, Inc.
5400 South 122nd East Avenue
Tulsa, OK 74146
1-800-879-8000
www.hilti.com
March 20, 2014
To Whom It May Concern:
Re: Hilti CFS-S SIL GG Firestop Sealant - LEED Info.
The Hilti CFS-S SIL GG Firestop Sealant is manufactured in Toronto, Ontario.
There is no post-consumer or post-industrial content in CFS-S SIL GG and it cannot be recycled.
The CFS-S SIL GG does not contain any Rapidly Renewable Materials. The VOC content for
CFS-S SIL GG is 48.0 grams/liter.
CFS-S SIL GG is not regulated as a hazardous waste by the Federal EPA Standards. The
regulations for the disposal of non-regulated industrial waste can vary from state to state and even
city to city. For this reason, you should consult your local and state regulatory agencies for
direction on disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Sr. Mgr. Safety/Environmental
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com
Rev. Date: 3/20/14
36
Product Information
Hilti. Outperform. Outlast.
Hilti, Inc. (U.S.) 1-800-879-8000 www.us.hilti.com • www.us.hilti.com/firestop • en español 1-800-879-5000
Hilti Firestop
Saving lives
through innovation
and education
Firestop Self Leveling Silicone Sealant CFS-S SIL SL
Product description
■Self-leveling, single-component, silicone-based firestop sealant for use
with through-penetrations as well as construction joints in floors.
Product features
■Self-leveling–requires no tooling
■Excellent elongation/compression properties
■Meets 500 cycle requirements (ASTM E 1966 and UL 2079)
■Smoke, fume, water and UV resistant
■Meets Class I W-rating requirements
■Meets LEED™ requirements for indoor environmental quality credit 4.1
Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and
Coatings
Areas of application
■Sealing construction/expansion joints
■Metal pipes
■Cable bundles
■Sealing multiple penetrations in small or large openings
For use with
■Concrete floors rated up to 4 hours
Examples
■Penetrations for metal pipes between floor levels
■Construction joints and expansion joints in floors
Installation instructions
■Refer to what is included in the package, the MSDS, and the applicable
listing.
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS, JOINT SYSTEMS
AND PERIMETER FIRE CONTAINMENT
SYSTEMS
SEE UL FIRE RESISTANCE
DIRECTORY 5BP5
Technical Data* CFS-S SIL SL
Chemical basis Neutral elastic silicone
Density Approx. 1.4 g/cm3
Color Gray
Application temperature 40°F to 104°F (5°C to 40°C)
Skin forming time Approx. 15 min
Curing time Approx. 2 mm/3 days
Volume shrinkage Approx. 0 – 5%
Joint movement capability
(UL 2079)
Approx. 33%
Temperature resistance –40°F to 300°F (–40°C to 149°C)
Surface burning characteristics
(ASTM E 84-12)
Flame Spread: 0
Smoke Development: 50
Sound transmission classification
(ASTM E 90-09)
53
(Relates to specific construction)
Tested in accordance with UL 1479
ASTM E 1966
UL 2079
ASTM E 814
ASTM E 2307
ASTM E 84
ASTM G21
*At 73°F (23°C) and 50% relative humidity
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Visit fbcsystemcompatible.com.
FBC™ is a trademark of
the Lubrizol Corporation.
37
CERTIFICATE OF COMPLIANCE
Certificate Number 20131115-R13240
Report Reference R13240
Issue Date 2013-November-15
William R. Carney, Director, North American Certification Programs
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus
Page 1 of 1
Issued to: Hilti Construction Chemicals, Div of Hilti Inc.
5400 S 122nd East Ave
Tulsa, OK 74146
This is to certify that
representative samples of
Fill, Void or Cavity Materials
Fill, Void or Cavity Materials Certified for Canada
CFS-S SIL GG and CFS-S SIL SL for use in Through-
Penetration Firestop and Joint Systems in the UL Fire
Resistance Directory and in the Products Certified for
Canada Directory.
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through-Penetration
Firestops," – Edition 3 – Revision Date 2012/10/19
ANSI/UL 2079, "Tests for Fire Resistance of Building Joint
Systems," – Edition 4 – Revision Date 2012/12/12
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop
Systems." – Edition 4 – Issue Date 2011/06/01
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Classification Mark should be considered as being covered by
UL’s Classification and Follow-Up Service.
The UL Classification Mark includes: UL in a circle: with the word “CLASSIFIED” (as shown); a control
number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL’s evaluation of
the product; and the product category name (product identity) as indicated in the appropriate UL
Directory.
Look for the UL Classification Mark on the product.
38
Hilti, Inc.
5400 South 122nd East Avenue
Tulsa, OK 74146
1-800-879-8000
www.hilti.com
March 20, 2014
To Whom It May Concern:
Re: Hilti CFS-S SIL SL Firestop Sealant – LEED Info.
The Hilti CFS-S SIL SL Firestop Sealant is manufactured in Toronto, Ontario.
There is no post-consumer or post-industrial content in CFS-S SIL SL and it cannot be recycled.
The CFS-S SIL SL does not contain any Rapidly Renewable Materials. The VOC content for
CFS-S SIL SL is 50 grams/liter.
CFS-S SIL SL is not regulated as a hazardous waste by the Federal EPA Standards. The
regulations for the disposal of non-regulated industrial waste can vary from state to state and even
city to city. For this reason, you should consult your local and state regulatory agencies for
direction on disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Sr. Mgr. Safety & Environmental
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com
Rev. Date: 3/20/14
39
Product Information
Hilti. Outperform. Outlast.
Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide IntroductionApplications and ProductsSelector GuideThrough-PenetrationJointReference DataFlexible Firestop Sealant (CP 606)
Product description
■An acrylic based firestop sealant that provides movement
capability in fire rated joints and seals through-penetrations
applications
Product features
■Silicone free
■Halogen, asbestos and solvent free
■Paintable
■Tested up to 33% movement with 500 cycles in accordance to UL
2079 and ASTM 1966
■Smoke and fume resistant
■Easy clean up with water
■Single component systems available
■Meets LEED™ requirements for indoor environmental quality credit
4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints
and Coatings
Areas of application
■Sealing construction/expansion joints
■Top-of-wall joints
■Metal pipes
■Cable bundles
■HVAC penetrations
For use with
■Various base materials such as masonry, concrete, gypsum, etc.
■Wall and floor assemblies rated up to 3 hours
Examples
■Where a gypsum wall assembly meets the underside of a metal or
concrete deck
■Sealing expansion joints to impede the passage of fire, smoke and
toxic fumes
■Sealing around HVAC penetrations through fire-rated assemblies FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Notice
• Before handling, read Material Safety Data Sheet and
product label for safe usage and health information.
• Instructions below are general guidelines — always
refer to the applicable drawing in the UL Fire
Resistance Directory or Hilti Firestop Systems Guide
for complete installation information
• The use of backing material is recommended to
control the sealant depth and help ensure assembly
seal is complete
Opening
1. Clean the opening. Surfaces to which CP 606 will
be applied should be cleaned of loose debris, dirt,
oil, wax and grease. The surface should be moisture
and frost free.
Application of firestop
2. Insert fill of mineral wool or backer (as required).
3. Apply firestop over backer.
4. Smooth firestop sealant with a trowel before the skin
forms. Once cured, CP 606 can only be removed
mechanically.
5. For maintenance reasons, a penetration seal can be
permanently marked with an identification plate and
fastened in a visible position next to the seal.
Not for use
• On areas immersed in water
Storage
• Store only in the original packaging in a location
protected from moisture at a temperature of 40°F to
77°F (5°C to 25°C)
• Observe expiration date on package
Installation instructions for CP 606
1. Clean opening 2. Insert backing
material compressed
per UL System
3. Apply CP 606 4. Smooth CP 606 5. Fasten identification
plate (if required)
1. Clean opening 2. Insert backing
material
3. Apply CP 606 4. Smooth CP 606 5. Fasten identification
plate (if required)
FirestopSystem
FirestopSystemFirestopSystemJOINTDUCTFILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS AND
JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Technical Data* CP 606
Chemical basis Acrylic based firestop sealant
Color Available in red, white and gray
Application temperature 40°F to 104°F (5°C to 40°C)
Skin-forming time Approx. 15 min
Curing time Approx. 3 mm / 3 days
Average volume shrinkage
(ASTM C1241)
22.2%
Movement capability Approx. 10%
Temperature resistance –22°F to 176°F (–30°C to 80°C)
Surface burning characteristics
(ASTM E 84-96)
Flame Spread: 10
Smoke Development: 0
Sound transmission classification
(ASTM E 90-99)
56
(Relates to specific construction)
Tested in accordance with
• UL 2079 • ASTM E 814 • ASTM E 1966
• ASTM E 84 • UL 1479 • ASTM G21
*At 73°F (23°C) and 50% relative humidity
40
41
Hilti, Inc.
5400 South 122nd East Avenue
Tulsa, OK 74146
1-800-879-8000
www.hilti.com
February 26, 2010
To Whom It May Concern:
Re: Hilti CP 606 Flexible Firestop – LEEDs Info.
The Hilti CP 606 Flexible Firestop Sealant is manufactured in Germany.
The CP 606 pail is made of polyethylene and can be completely recycled. There is no post-
consumer or post-industrial content in CP 606 and it cannot be recycled. The CP 606 does not
contain any Rapidly Renewable Materials. The VOC content for CP 606 is 71.0 grams/liter.
CP 606 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for
the disposal of non-regulated industrial waste can vary from state to state and even city to city.
For this reason, you should consult your local and state regulatory agencies for direction on
disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Safety/Environmental Manager
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com
Rev. Date: 2/26/10
42
Hilti Firestop
Saving lives
through innovation
and education
Product Information
Hilti. Outperform. Outlast.
Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide IntroductionApplications and ProductsSelector GuideThrough-PenetrationJointReference DataFirestop Putty Stick (CP 618)
Product description
■An intumescent, non-hardening, firestop putty for cable and pipe
penetrations
Product features
■Contains no volatile solvents or asbestos
■Easy to re-penetrate
■Reusable
■Easy to add or remove cables
■Fast installation
Areas of application
■Single or bundled cables
■Non-combustible pipe
■Blank openings
For use with
■Concrete, masonry and gypsum wall assemblies
■Wall and floor assemblies rated up to 3 hours
Examples
■Where telecommunication and data lines penetrate gypsum wall
assemblies
■Where steel conduit and EMT penetrate concrete and block wall
assemblies
■Where blank openings exist in concrete and block wall assemblies
Installation instructions for CP 618
Notice
• Before handling, read Material Safety Data Sheet and
product label for safe usage and health information.
• Instructions below are general guidelines — always
refer to the applicable drawing in the UL Fire
Resistance Directory or Hilti Firestop Systems Guide
for complete installation information
Opening
1. Clean the opening: Surfaces to which CP 618 will be
applied should be cleaned of loose debris, dirt, oil,
moisture, frost and wax.
Application of firestop putty
2. Install the prescribed backing material, if required.
3. Install CP 618 Firestop Putty to the required depth,
making sure that the putty contacts all surfaces to
provide the greatest adhesion.
4. Smooth CP 618 putty.
5. For maintenance reasons, a penetration seal can be
permanently marked with an identification plate and
fastened in a visible position next to the seal.
6. Re-installation (not shown): Remove and re-install
CP 618 Firestop Putty as needed.
Not for use
• In areas exposed to water
Storage
• Store only in the original packaging at temperatures
40°F to 104°F (5°C to 40°C)
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
1. Clean opening 2. Slice CP 618 to be
packed into opening from
stick (optional sleeve)
3. Pack in CP 618 4. Smooth CP 618 5. Fasten installation plate
(if required)
Technical Data* CP 618
Volume 18 in3
Consistency Moldable putty
Color Red
Application temperature 40°F to 95°F (5°C to 35°C)
Curing time Non-curing
Density Approx. 1.48 g/cm3
Surface burning characteristics
(ASTM E84-96)
Flame Spread: 15
Smoke development: 10
Sound transmission classification
(ASTM E 90-97)
49 (Relates to specific construction)
Tested in accordance with
• UL 1479 • ASTM E 814 • ASTM E 84 • ASTM G21
*At 73°F (23°C) and 50% relative humidity
43
44
Hilti Firestop
Saving lives
through innovation
and education
Product Information
Hilti. Outperform. Outlast.
Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide
Firestop Wrap Strip (CP 648-E)
Product description
■An intumescent, flexible firestop wrap strip for plastic and
insulated pipe penetrations
Product features
■Highly Intumescent
■Long length avoids waste
■Can be continuously wrapped
■Cost effective
■Quick and easy closure without tools
■Ideal for very tight installations
Areas of application
■Firestopping combustible pipe penetrations
■Difficult applications where space is limited
■Penetrations through concrete over metal deck
■Plastic and insulated penetrations using
PVC, CPVC, ABS, FRPP and PEX
For use with
■Concrete, masonry, wood floor and gypsum wall assemblies
■Wall and floor assemblies rated up to 4 hours
Examples
■Waste water pipes
■Fresh water pipes
■Decking penetrations
Technical Data* CP 648-E
Density Approx. 1.35 g/cm3
Dimensions (approximate)3/16" x 1" x 33 ft or
3/16" x 1-3/4" x 33 ft
Color Black with foil backing
Temperature resistance –40°F to 212°F (–40°C to 100°C)
Intumescent activation Approx. 320°F (160°C)
Expansion ratio (unrestricted)1:40
Tested in accordance with
• UL 1479 • ASTM E 814 • ASTM G21
*At 73°F (23°C) and 50% relative humidity
Installation instructions for CP 648-E
sodfm,ev
i
J
d
j
f
i
w
h
r
i
u
h
.
N|oWE
Z8Z23aw
|p3i4e0288u27
uze
4i5kirdwilo
i
4
j
t
f
-
|x-.vbvbvh,
i
r
e
i
v
u9+12oeoo
CP 648 Bra
n
d
s
c
h
u
t
z
m
a
n
s
ch.
Notice
• Before handling, read Material Safety Data Sheet and
product label for safe usage and health information.
• Instructions below are general guidelines — always
refer to the applicable drawing in the UL Fire
Resistance Directory or Hilti Firestop Systems Guide
for complete installation information
Opening
1. Clean the plastic or insulated pipe penetration.
Expansion of the intumescent material during a fire
closes the plastic or insulated pipe penetration. Very
dirty pipes (ie: with remains of mortar) may lead to
a delay in this closing action. Soiled plastic pipes
or insulated pipe penetrations should, therefore, be
cleaned in the area where the CP 648-E Firestop
Wrap Strip is to be installed.
Application of firestop system
2. Tightly wrap the required number of strips
continuously around the penetrant, and hold in place
with tape.
3. Push the Hilti Wrap Strip into the opening until it is
flush with the substrate surface unless otherwise
required by the UL system. It may be required by
the UL system to clamp, wire or use a Hilti Retaining
Collar to secure the wrap strip in place for some
applications.
4. If the UL system requires a cold smoke seal, then
apply the proper amount of Hilti FS-ONE sealant in
the opening over the wrap strip.
5. For maintenance reasons, a penetration seal can be
permanently marked with an identification plate and
fastened in a visible position next to the seal.
Not for use
• In highly corrosive surroundings
• With unapproved retaining collars, anchors/fasteners
• Outdoors
Storage
• Store only in the original packaging in a location
protected from moisture at temperatures between
23°F and 86°F (–5°C and 30°C).
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
1. Clean penetration 2. Wrap strips around
pipe the specified number
of times
3. Push Wrap Strips
into hole
4. Seal penetration against
smoke with FS-ONE
5. Fasten installation plate
(If required)
FirestopSystem
Visit fbcsystemcompatible.com.
FBC™ is a trademark of
the Lubrizol Corporation.
45
46
Hilti, Inc.
5400 South 122nd East Avenue
Tulsa, OK 74146
1-800-879-8000
www.hilti.com
May 12, 2011
To Whom It May Concern:
Re: The CP 648 E & S Firestop Wrap Strips – LEEDs Info.
The Hilti CP 648 E & S Firestop Wrap Strips are manufactured in Germany.
The Hilti CP 648 E & S Firestop Wrap Strips have a VOC content of 3.1 grams/liter.
The amount of post-consumer or post-industrial content in CP 648 E & S Firestop Wrap Strips is
not known. The packaging is recyclable. The CP 648 E & S Firestop Wrap Strips do not contain
any Rapidly Renewable Materials.
The CP 648 E & S Firestop Wrap Strips are not regulated as a hazardous waste by the Federal
EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from
state to state and even city to city. For this reason, you should consult your local and state
regulatory agencies for direction on disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Sr. Manager Safety, Environmental, & Facilities
Hilti Inc.
(918) 872 3704
jerry.metcalf@hilti.com
Rev. Date: 5/12/11
47
Hilti FS-ONE MAX product substitution letter
February 2015
To W hom It May Concern:
Hilti FS-ONE Intumescent Firestop Sealant is being discontinued and replaced by FS-ONE MAX
Intumescent Firestop Sealant. The listed UL/cUL systems on the next page have been updated to include
FS-ONE MAX.
Testing is ongoing. Please check online for the most up to date listings.
As compared to FS-ONE, the new FS-ONE MAX offers W -rated systems, superior handling properties,
extended shelf life, and is now ethylene glycol free.
The new FS-ONE MAX will be offered in the same package types as the FS-ONE Intumescent Firestop
Sealant (cartridge, foil and bucket). Item numbers have changed.
Item Number Product Typ e Product Name
2101534 Firestop Intum escent Sealant 10 oz. cartridge FS-ONE MAX
2101535 Firestop Intum escent Sealant 20 oz. foil FS-ONE MAX
2101536 Firestop Intum escent Sealant 5 gallon pail FS-ONE MAX
Sincerely,
Kevin Brandon
Fire Protection Product Manager
Hilti, Inc.
United States www.us.hilti.com/f irestop
Canada www.hilti.ca/firestop
48
Hilti FS-ONE MAX product substitution letter
Testing is ongoing. Please check online for the most up to date listings.
FS-ONE MAX Intumescent Firestop Sealant for use in Joint System
BW -S-0001, BW -S-0002, CJ-D-0008, CJ-D-0009, CJ-D-0010, HW -D-0060, HW -D-0061, HW-D-0118, HW-D-0119, HW -D-0120, HW-
D-0528, HW -D-0529, HW -D-0530, HW -D-1011, HW-D-1012, HW -D-1020, HW -S-0036, HW-S-0037, HW-S-0038, HW-S-0039, HW-
S-0090.
FS-ONE MAX Intumescent Firestop Sealant for use in Through-Penetration Firestop System
C-AJ-0070, C-AJ-0090, C-AJ-0138, C-AJ-1149, C-AJ-1150, C-AJ-1151, C-AJ-1152, C-AJ-1153, C-AJ-1154, C-AJ-1155, C-AJ-1156, C-AJ-1158, C-
AJ-1172, C-AJ-1173, C-AJ-1174, C-AJ-1177, C-AJ-1184, C-AJ-1226, C-AJ-1278, C-AJ-1291, C-AJ-1326, C-AJ-1342, C-AJ-1346, C-AJ-1380, C-AJ-
1421, C-AJ-1454, C-AJ-1513, C-AJ-1534, C-AJ-1575, C-AJ-1597, C-AJ-1609, C-AJ-1610, C-AJ-2062, C-AJ-2066, C-AJ-2091, C-AJ-2094, C-AJ-
2095, C-AJ-2098, C-AJ-2109, C-AJ-2110, C-AJ-2118, C-AJ-2141, C-AJ-2164, C-AJ-2167, C-AJ-2168, C-AJ-2169, C-AJ-2170, C-AJ-2217, C-AJ-
2218, C-AJ-2220, C-AJ-2283, C-AJ-2284, C-AJ-2285, C-AJ-2294, C-AJ-2304, C-AJ-2305, C-AJ-2335, C-AJ-2336, C-AJ-2337, C-AJ-2342, C-AJ-
2343, C-AJ-2371, C-AJ-2372, C-AJ-2393, C-AJ-2402, C-AJ-2407, C-AJ-2419, C-AJ-2420, C-AJ-2434, C-AJ-2435, C-AJ-2451, C-AJ-2468, C-AJ-
2469, C-AJ-2488, C-AJ-2567, C-AJ-2569, C-AJ-2570, C-AJ-2599, C-AJ-2600, C-AJ-2613, C-AJ-2631, C-AJ-2632, C-AJ-2639, C-AJ-2647, C-AJ-
2667, C-AJ-2674, C-AJ-2677, C-AJ-2700, C-AJ-3069, C-AJ-3070, C-AJ-3078, C-AJ-3079, C-AJ-3084, C-AJ-3095, C-AJ-3096, C-AJ-3152, C-AJ-
3180, C-AJ-3198, C-AJ-3209, C-AJ-3232, C-AJ-3236, C-AJ-3239, C-AJ-3281, C-AJ-3283, C-AJ-3284, C-AJ-3285, C-AJ-3298, C-AJ-3318, C-AJ-
3319, C-AJ-3320, C-AJ-4034, C-AJ-4035, C-AJ-4071, C-AJ-4083, C-AJ-4093, C-AJ-4094, C-AJ-5044, C-AJ-5045, C-AJ-5046, C-AJ-5047, C-AJ-
5048, C-AJ-5057, C-AJ-5061, C-AJ-5069, C-AJ-5090, C-AJ-5091, C-AJ-5096, C-AJ-5184, C-AJ-5185, C-AJ-5198, C-AJ-5277, C-AJ-5289, C-AJ-
5301, C-AJ-5320, C-AJ-5341, C-AJ-5342, C-AJ-5343, C-AJ-6017, C-AJ-6042, C-AJ-7006, C-AJ-7051, C-AJ-7084, C-AJ-7095, C-AJ-7098, C-AJ-
7103, C-AJ-7104, C-AJ-7111, C-AJ-7122, C-AJ-7123, C-AJ-7140, C-AJ-7145, C-AJ-8038, C-AJ-8041, C-AJ-8044, C-AJ-8056, C-AJ-8058, C-AJ-
8081, C-AJ-8099, C-AJ-8100, C-AJ-8107, C-AJ-8110, C-AJ-8143, C-AJ-8166, C-AJ-8178, C-AJ-8207, C-AJ-8208, C-AJ-8209, C-AJ-8210, C-AJ-
8211, C-BJ-1034, C-BJ-1037, C-BJ-1045, C-BJ-1046, C-BJ-1055, C-BJ-1059, C-BJ-2011, C-BJ-2012, C-BJ-2013, C-BJ-2014, C-BJ-2016, C-BJ-
2017, C-BJ-2021, C-BJ-2028, C-BJ-2040, C-BJ-2041, C-BJ-3024, C-BJ-3031, C-BJ-4025, C-BJ-4026, C-BJ-5006, C-BJ-5007, C-BJ-5013, C-BJ-
5015, C-BJ-5018, C-BJ-7005, C-BJ-8010, C-BJ-8013, C-BJ-8024, C-BJ-8027, F-A-1014, F-A-1018, F-A-1028, F-A-1029, F-A-1105, F-A-1108, F-A-
1127, F-A-1134, F-A-1135, F-A-1137, F-A-2009, F-A-2025, F-A-2046, F-A-2058, F-A-2067, F-A-2068, F-A-2074, F-A-2075, F-A-2089, F-A-2143, F-A-
2154, F-A-2209, F-A-3012, F-A-3022, F-A-5019, F-A-5021, F-A-8004, F-B-2029, F-B-5003, F-C-0002, F-C-1009, F-C-1059, F-C-1106, F-C-1134, F-C-
1135, F-C-1142, F-C-1147, F-C-2029, F-C-2030, F-C-2071, F-C-2081, F-C-2128, F-C-2142, F-C-2160, F-C-2189, F-C-2203, F-C-2204, F-C-2230, F-
C-2231, F-C-2232, F-C-2262, F-C-2263, F-C-2270, F-C-2310, F-C-2334, F-C-2335, F-C-2382, F-C-2389, F-C-2401, F-C-2403, F-C-2404, F-C-3012,
F-C-3044, F-C-3094, F-C-5004, F-C-5036, F-C-5037, F-C-5086, F-C-7013, F-C-7036, F-C-7037, F-C-7042, F-C-7043, F-C-7055, F-C-7057, F-C-
7058, F-C-7059, F-C-8009, F-C-8014, F-C-8026, F-C-8038, F-E-1004, F-E-1018, F-E-2005, F-E-2026, F-E-2027, F-E-2028, F-E-2029, F-E-2033, F-E-
3005, F-E-3012, F-E-5004, F-E-5013, F-E-7008, F-E-8008, W-J-0007, W-J-0015, W-J-0022, W-J-1020, W-J-1021, W-J-1022, W-J-1028, W-J-1041,
W-J-1042, W-J-1058, W-J-1067, W-J-1068, W-J-1088, W-J-1089, W-J-1095, W-J-1174, W-J-1175, W-J-1191, W-J-1193, W-J-1202, W-J-1210, W-J-
1214, W-J-1215, W -J-1221, W -J-1222, W-J-1226, W-J-1245, W-J-2019, W-J-2057, W-J-2072, W-J-2091, W-J-2107 W-J-2108, W-J-2115, W-J-2120,
W-J-2121, W-J-2191, W-J-2205, W-J-2206, W-J-2207, W-J-2218, W-J-2229, W-J-2230, W-J-2236, W-J-2237, W-J-2242, W-J-2255, W-J-3050, W-J-
3060, W-J-3061, W -J-3074, W -J-3121, W-J-3167, W-J-3168, W-J-3188, W-J-3189, W-J-3190, W-J-3196, W-J-3197, W-J-3199, W-J-4016, W-J-4027,
W-J-4029, W-J-4048, W-J-4059, W-J-4060, W-J-4072, W-J-5003, W-J-5028, W-J-5041, W-J-5066, W-J-5067, W-J-5122, W-J-5134, W-J-5136, W-J-
5145, W-J-5150, W -J-5151, W -J-5152, W-J-6003, W-J-7021, W-J-7022, W-J-7029, W-J-7038, W-J-7091, W-J-7109, W-J-7110, W-J-7112, W-J-7123,
W-J-7124, W-J-8004, W-J-8007, W-J-8008, W-J-8009, W-J-8016, W-J-8022, W-J-8034, W-J-8035, W-J-8039, W-J-8043, W-J-8044, W-J-8045, W-J-
8047, W-J-8048, W -J-8049, W -J-8050, W-J-8051, W-K-3002, W-L-0013, W-L-0014, W-L-0018, W-L-0019, W-L-0023, W-L-0030, W-L-0040, W-L-
0042, W-L-0043, W-L-1054, W-L-1055, W-L-1056, W-L-1057, W-L-1058, W-L-1085, W-L-1092, W-L-1095, W-L-1110, W-L-1111, W-L-1148, W-L-
1164, W-L-1165, W-L-1176, W-L-1205, W-L-1206, W-L-1214, W-L-1243, W-L-1252, W-L-1304, W-L-1359, W-L-1367, W-L-1380, W-L-1389, W-L-
1392, W-L-1406, W-L-1408, W-L-1410, W-L-1412, W-L-1440, W-L-1441, W-L-1464, W-L-1465, W-L-1496, W-L-1497, W-L-2043, W-L-2044, W-L-
2045, W-L-2051, W-L-2052, W-L-2053, W-L-2055, W-L-2075, W-L-2078, W-L-2098, W-L-2124, W-L-2127, W-L-2128, W-L-2165, W-L-2184, W-L-
2186, W-L-2196, W-L-2197, W-L-2217, W-L-2236, W-L-2244, W-L-2245, W-L-2251, W-L-2292, W-L-2295, W-L-2315, W-L-2330, W-L-2335, W-L-
2340, W-L-2341, W-L-2345, W-L-2377, W-L-2406, W-L-2411, W-L-2444, W-L-2445, W-L-2447, W-L-2453, W-L-2466, W-L-2467, W-L-2471, W-L-
2472, W-L-2473, W-L-2474, W-L-2480, W-L-2482, W-L-2509, W-L-2510, W-L-2537, W-L-2538, W-L-2541, W-L-2546, W-L-2557, W-L-2558, W-L-
2568, W-L-2583, W-L-2584, W-L-2593, W-L-2602, W-L-2603, W-L-3045, W-L-3046, W-L-3047, W-L-3048, W-L-3049, W-L-3058, W-L-3059, W-L-
3065, W-L-3071, W-L-3079, W-L-3112, W-L-3139, W-L-3161, W-L-3185, W-L-3213, W-L-3220, W-L-3224, W-L-3226, W-L-3272, W-L-3278, W-L-
3307, W-L-3310, W-L-3320, W-L-3334, W-L-3335, W-L-3382, W-L-3384, W-L-3385, W-L-3391, W-L-3392, W-L-3394, W-L-3396, W-L-4006, W-L-
4011, W-L-4019, W-L-4038, W-L-4048, W-L-4060, W-L-4081, W-L-5016, W-L-5021, W-L-5022, W-L-5024, W-L-5025, W-L-5026, W-L-5027, W-L-
5028, W-L-5046, W-L-5047, W-L-5073, W-L-5143, W-L-5144, W-L-5223, W-L-5224, W-L-5225, W-L-5240, W-L-5244, W-L-5257, W-L-5259, W-L-
5260, W-L-5261, W-L-5263, W-L-5274, W-L-5292, W-L-5293, W-L-5294, W-L-6017, W-L-6019, W-L-7017, W-L-7018, W-L-7040, W-L-7042, W-L-
7059, W-L-7068, W-L-7069, W-L-7096, W-L-7121, W-L-7124, W-L-7130, W-L-7151, W-L-7153, W-L-7154, W-L-7155, W-L-7156, W-L-7157, W-L-
7158, W-L-7159, W-L-7188, W-L-7198, W-L-8004, W-L-8013, W-L-8014, W-L-8015, W-L-8023, W-L-8035, W-L-8047, W-L-8052, W-L-8059, W-L-
8065, W-L-8071, W-L-8079, W-L-8081, W-L-8082, W-L-8085, W-L-8086, W-L-8087, W-L-8093, W-L-8094, W-L-8095, W-L-8098
FS-ONE MAX Intumescent Firestop Sealant for Canadian-Specific Systems
C-AJ-0004, C-AJ-1010, C-AJ-1011, C-AJ-1016, C-AJ-1023, C-AJ-1612, C-AJ-2021, C-AJ-2022, C-AJ-2023, C-AJ-2024, C-AJ-2035,
C-AJ-2042, C-AJ-2049, C-AJ-2054+, C-AJ-2055+, C-AJ-2056+, C-AJ-2057+, C-AJ-2061, C-AJ-2070, C-AJ-2071, C-AJ-2072, C-AJ-
2078, C-AJ-2079, C-AJ-2080, C-AJ-2678, C-AJ-3007, C-AJ-8014, F-A-2009, F-B-2008, F-A-2026+, F-C-2005, F-C-2006, F-C-2007,
F-C-2009, F-C-2010, F-C-2035, F-C-2045, F-C-2378+, F-C-2416, F-C-7042, F-E-2005, F-E-2006, W -J-2019, W-J-2027, W-J-2028,
W-L-2028, W -L-2050, W -J-2029+, W -J-2030, W -J-2031, W-J-2032, W -J-2245, W-J-2246, W-J-2247, W-J-5136, W-J-7001, W -J-8005,
W-L-8005, W -L-0005, W -L-1406, W -L-2018, W -L-2027, W -L-2031, W-L-2032, W -L-2038, W-L-2043, W-L-2044, W -L-2047, W-L-2048,
W-L-2052, W -L-2056, W -L-2057, W -L-2060, W -L-2061, W -L-2062, W-L-2406, W -L-2447, W-L-2471, W-L-2472, W -L-2565, W-L-2578,
W-L-3307, W -L-5010, W -L-5011, W -L-5259, W -L-5260, W -L-5263, W-J-7007, W -L-8001, W-L-8010.
FS-ONE MAX Intumescent Firestop Sealant for Intertek Systems
HI/PHV 120-01 (now HI/PF 120-01) (now HI/PF 120-02), HI/PHV 120-03 (now HI/PF 120-03), HI/PHV 120-04 (now HI/PF 120-04),
HI/PHV 120-05 (now HI/PF 120-05), HI/PV 60-01 (now HI/PF 60-01)
49
Product Information
Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca
Hilti. Outperform. Outlast.01/15 DBSVRGIP
H
Y
L
-
G
M
I
L
Z
K
U
L
X
K
1
|
R
:
(
==
D
Z
|
S
L
H
X
X
]
H
LNLU
G
Z
L
O
R
L
M
W
I
|
[
Y
E
Y
E
Y
K
L
U
H
L
Y
X
R
H
R
R
WONH
A
5
W
F
Y
High performance intumescent firestop sealant FS-ONE MAX
Product description
■Intumescent (expands when exposed to fire) firestop sealant that helps
protect combustible and non-combustible penetrations for up to 4
hours fire rating
Applications
■Effectively seals most common through penetrations in a variety of
base materials
■For use on concrete, masonry and drywall
■Mixed and multiple penetrations
■Metal pipe penetrations
■Insulated metal pipe penetrations
■Plastic pipe penetrations
■Cable bundles and trays
■HVAC penetrations
Advantages
■One product for a variety of common through penetrations
■Cost-effective and easy-to-use solution
■Water-based and paintable
■W-rated systems available
■Ethylene glycol-free
■Industry leading VOC results
■Convenient multi application firestop solution for penetrations
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Technical Data*
Chemical basis Water-based acrylic dispersion
Color Red
Application temperature 41°F to 104°F
Storage and transportation range 41°F to 77°F
Approx. cure time *4 mm / 3 days
Shelf life 12 months **
Temperature resistance range -4°F to 212°F
Mold and mildew performance Class 0 (ASTM G21-13)
Mold and mildew resistant Yes
Surface burning characteristics
(ASTM E 84-14)
Flame Spread: 0
Smoke Development: 10
Approvals California State Fire Marshal - in
progress
Tested in accordance with ASTM G21
ASTM E 90
CAN/ULC-S115
UL 1479
ASTM E 814
ASTM E84
* At 75°F (24°C) and 50% relative humidity
** from date of manufacture
Visit fbcsystemcompatible.com.
FBC™ is a trademark of
the Lubrizol Corporation.
50
51
Hilti, Inc.
5400 South 122nd East Avenue
Tulsa, OK 74146
1 -800-879-8000
www.hilti.com
August 26, 2015
To Whom It May Concern:
Re: Hilti FS-ONE Max Firestop – LEED Info.
Item Numbers:
2101531
2101532
2101533
The Hilti FS-ONE MAX Firestop is manufactured in the United States
There is no post-consumer or post-industrial content in FS-ONE MAX and it cannot be recycled. The VOC content for FS-ONE
MAX is 9 grams/liter.
FS-ONE MAX is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-
regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and
state regulatory agencies for direction on disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Sr. Manager, Safety/Environmental
Hilti Inc
(918) 872 3704
jerry.metcalf@hilti.com
Rev. Date: 7/31/15
The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used
for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America
requirements, as those requirements differ.
The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. “Specially” produced
non-catalog Hilti products may have differing manufacturing plant locations.
Contact your Hilti representative in cases of “specially” produced products for a custom LEEDS certificates.
52
53
®
MSDS No.: 270
Revision No.: 005
Revision Date: 11/29/12
Page: 1 of 2
HILTI ® is a registered trademark of Hilti Corp.
MATERIAL SAFETY DATA SHEET
Product name: Mineral wool
Description: Synthetic vitreous fiber
Supplier: Hilti, Inc. P.O. Box 21148, Tulsa, OK 74121
Emergency # (Chem-Trec.): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)
INGREDIENTS AND EXPOSURE LIMITS
Ingredients: CAS Number: PEL: TLV: STEL:
Slag wool fiber 65997-17-3 NE 1 fiber / cc NE
Phenolic resin 09003-35-4 NE NE NE
Polyvinyl alcohol 09002-89-5 NE NE NE
Abbreviations: PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. STEL = Short Term Exposure
Limit. NE = None Established. NA = Not Applicable.
PHYSICAL DATA
Appearance: 2’ x 4’ x 4” sheets. Odor:Negligible.
Boiling Point: Not applicable. Vapor Pressure:Not applicable.
Melting Point: Approx. 2400 F VOC Content: < 1% w/w
Evaporation Rate: Not applicable. Solubility in Water:Insoluble.
pH: Not applicable. Specific Gravity:Not determined.
FIRE AND EXPLOSION HAZARD DATA
Flash Point: Not applicable. Flammable Limits:Not applicable.
Extinguishing Media: As appropriate for surrounding fire; material does not burn.
Special Fire Fighting
Procedures:
Soak cartons to help prevent the spread of fire. Use a self-contained breathing apparatus when
fighting fires involving chemicals.
Unusual Fire and Explosion
Hazards:
None known.
REACTIVITY DATA
Stability: Stable. Hazardous Polymerization: Will not occur.
Incompatibility: Strong acids.
Hazardous Decomposition
Products:
Thermal decomposition products can be formed at temperatures exceeding 2000 F. Thermal
decomposition can yield CO and CO2.
Conditions to Avoid: None known.
HEALTH HAZARD DATA
Known Hazards: Acute: Eye, skin and respiratory irritation. Chronic: Respiratory impairment.
Routes of Exposure: Inhalation, Dermal.
Signs and Symptoms of
Exposure:
Eyes: Mechanical irritation. Skin: Itching, irritation. Inhalation: Nose, throat and upper
respiratory tract irritation.
Carcinogenicity: Slag wool has been classified by the IARC as Group 3 – Unclassifiable as to Carcinogenicity in
Humans.
Medical Conditions
Aggravated by Exposure:
Eye, skin, and respiratory conditions.
54
MSDS 270, Page 2 of 2
EMERGENCY AND FIRST AID PROCEDURES
Eyes: Flush with plenty of water while holding eyelids apart. Avoid rubbing the eyes as mechanical
abrasions can occur. Call a physician if symptoms persist.
Skin: Wash with soap and water. Launder clothing before reuse.
Inhalation: Move to fresh air.
Ingestion: No ill effects expected.
Other: Referral to a physician is recommended if there is any question about the seriousness of the
injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
Ventilation: General (natural or mechanically induced fresh air movements).
Eye Protection: Safety goggles recommended to prevent particulates from irritating the eyes.
Skin Protection: Cloth gloves and long sleeves to protect skin from irritating fibers.
Respiratory Protection: Use local exhaust and/or a NIOSH-approved dust respirator when air movement is inadequate to
control dusts / fibers below recommended exposure levels.
PRECAUTIONS FOR SAFE HANDLING AND USE
Handling and Storing
Precautions:
Avoid generating dusts. Local exhaust may be required to control dusts if power tools are used
for cutting / trimming. Wear appropriate personal protective equipment. Store away from
moisture; keep dry.
Spill Procedures: Not applicable.
REGULATORY INFORMATION
Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication
Standard 29 CFR 1910.1200.
HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B (Gloves, Goggles)
DOT Shipping Name: Not regulated.
IATA / ICAO Shipping Name: Not regulated.
TSCA Inventory Status: Chemical components listed on TSCA inventory.
SARA Title III, Section 313: This product does not contain any toxic chemicals which are subject to reporting under Section
313 of SARA Title III (40 CFR Part 372).
EPA Waste Code(s): Not regulated by EPA as a hazardous waste.
Waste Disposal Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that comply
with local, state, and federal safety, health and environmental regulations.
CONTACTS
Customer Service: 1 800 879 8000 Technical Service:1 800 879 8000
Health / Safety: 1 800 879 6000 Jerry Metcalf (x1003704)
Emergency # (Chem-Trec): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)
The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or warranty
of any kind expressed or implied is made with respect to the information provided.
55
Hilti, Inc.
5400 South 122nd East Avenue
Tulsa, OK 74146
1-800-879-8000
www.hilti.com
August 13, 2010
To Whom It May Concern:
Re: Hilti Mineral Wool-LEED Info.
The Hilti Mineral Wool is manufactured in Waubash Indiana.
The post-consumer recycled content in the Hilti Mineral Wool is 0%. The pre-consumer recycled
content in the Hilti Mineral Wool is 90%. There is no detectable VOC content in this product.
Hilti Mineral Wool is not regulated as a hazardous waste by the Federal EPA Standards. The
regulations for the disposal of non-regulated industrial waste can vary from state to state and even
city to city. For this reason, you should consult your local and state regulatory agencies for
direction on disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Safety/Environmental Manager
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com
Rev. Date: 8/13/10