HomeMy WebLinkAboutBlower Door Report - Final.pdf Page 1 of 1 9/8/2016 P.O. Box 7627, Avon, CO 81620 | P: 970.306.4233 | F: 866.403.3485 | www.activeenergies.com 1183 Cabin Circle Blower Door Report Test Date: September 7, 2016 Builder: Turnipseed Contact: Mike Guzik Site Address: 1183 Cabin Circle, Vail, CO Site Visit By: Megan Gilman Background The project goal is to undergo testing at final construction to determine the final amount of air infiltration. The project is located in the Town of Vail and must meet the IECC code requirements of 3 ACH50 or lower. Active Energies was contracted to perform a final blower door test to determine total air infiltration. Site Observations Construction of the building envelope was complete. All exterior openings were shut and locked and interior doors were open. No alterations were made to any openings on the exterior of the home. The blower door test was performed in the entry doorway adjacent to the garage, separating the entry hallway from the outdoors. The pressure probe place outside. Blower Door Test The home was depressurized, utilizing blower door testing equipment to a pressure of -50 Pa. At the test pressure, the CFM50 was recorded, in order to determine the ACH50. The blower door air leakage resulted in the following measurements: 2.92 ACH50 This is a follow up test to one performed on 9/1/16, where a few areas of leakage were identified for mediation, including the trim around fixed windows, the shade pocket area above the East Master Bedroom window and the lower tracks of the lift and slide window units located in the main living area. Please call with any questions or concerns.