HomeMy WebLinkAboutB15-0132_E-100 POWER PLAN_1431364740.pdfTV
TV
TV
GFCI
GFCI
GFCI
GFCI GFCI GFCI
GFCI
GFCI GFCI
GFCI
GFCI
TV
TV
D/W
WM
DWR
CONTROL
EXHAUST
FRIDGE
DBL
OVEN
M/W R
R R 1
N
CONNECT TO EXISTING
120V. RECEPTACLE
CIRCUIT AS SHOWN.
ENSURE CIRCUIT
CONTINUITY.
DINING
ROOM
105
KITCHEN
107
MASTER
BATH
103
MASTER
BED
104
ENTRY
100
LAUNDRY
101
POWDER
109
MEDIA
ROOM
108
NEW
OFFICE
110
106
ROOM
105
TV
FOURPLEX WALL OUTLET
TELEPHONE JACK
DUPLEX WALL RECEPTACLE
FLOOR DUPLEX RECEPTACLE
TV / COAXIL RECEPTACLE
FLOOR DUPLEX OUTLET
220V WALL RECEPTACLE
TELEPHONE & DATA JACK
IN-FLOOR TELEPHONE JACK
DATA JACK
HARDWIRE BOX LOCATION-AS NOTED, EXISTING
E
1. REFER TO ARCHITECTURAL PLANS FOR DIMENSIONS, ELEVATIONS,
DETAILS, ETC.. VERIFY MOUNTING HEIGHTS OF DEVICES AND ENSURE
MINIMUM 24" HORIZONTAL SEPARATION PER UBC IN FIRE RATED
DEMISING WALLS. PROVIDE FIRE-STOP OR ADDITIONAL RATED GYP
BOARD AS REQUIRED. COORDINATE WITH FIRE DEPT./INSPECTOR AND
G.C.
2. UNIT LIGHT FIXTURES TO BE SELECTED BY OWNER, RATED FOR
INSULATED CEILINGS. ENSURE PROPER LOCAL SWITCHING. LIGHTING
FURNISHED BY E.C. TO BE COORDINATED WITH CEILING TYPES,
MECHANICAL WORK, STRUCTURAL MEMBERS, ETC. VERIFY FINISHES
AND LOCATIONS OF CONTROLS.
3. COORDINATE PRE-WIRING OF T.V. COAX AND TELEPHONE JACKS WITH
G.C. AND OWNER. VERIFY ALL WALL LOCATIONS WITH ARCHITECT
PRIOR TO ROUGH-IN.
4. PROVIDE RECEPTACLE LOCATIONS AND SPACING PER N.E.C. 210-52
THROUGHOUT. FIELD ADJUSTMENTS / MEASUREMENTS ARE REQUIRED
TO COMPLY. COORDINATE ADDITIONAL STUD WALL BRACING IF
REQUIRED FOR RECEPTACLE PLACEMENTS WITH G.C. IF APPLICABLE,
VERIFY FLOOR OUTLET LOCATIONS WITH ARCHITECT. PROVIDE GFI
RECEPTACLES WHERE REQUIRED BY CODE PER NEC 210.8.
5. PROVIDE ARC-FAULT CIRCUIT INTERRUPTER PROTECTION IN DWELLING
UNITS PER NEC 210.12. FAMILY ROOMS, DINING ROOMS, LIVING
ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR
AREAS SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
INTERRUPTER TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
VERIFY WITH LOCAL AUTHORITY HAVING JURISDICTION IF EXISTING
BRANCH CIRCUITS SHALL COMPLY WITH NEC 210.12.
6. ALL CLOSET LIGHTING SHALL COMPLY WITH NEC 410.16.
7. ALL ELECTRICAL DEVICES AND LIGHT FIXTURE MOUNTING HEIGHTS
SHALL COMPLY TO THE "FAIR HOUSING ACT": DUPLEXES +15" A.F.F.,
SWITCHES AT +46" A.F.F. VERIFY WITH OWNER.
8. FOR NEW RECEPTACLES, PROVIDE TAMPER RESISTANT RECEPTACLES
THROUGHOUT DWELLING UNIT AS REQUIRED BY NEC 406.12
9. PROVIDE ACCURATE AND LEGIBLE PANEL INDEXES IDENTIFYING
SPECIFIC PURPOSE OR USE OF CIRCUIT BREAKERS PER NEC 408.4.
NOTE: UNLESS OTHERWISE NOTED, ALL NEW RECEPTACLES
SHALL MATCH EXISTING ELEVATIONS (AFF)
NOTE: NOT ALL EXISTING RECEPTACLES ARE SHOWN. THOSE SHOWN
ARE FOR REFERENCE AND ARE IN THE AREA OF CONSTRUCTION.
DETAIL NOTES - POWER:
LEGEND - POWER:
GENERAL NOTES - POWER:
1 EXISTING RECEPTACLES FOR TV AND A/V EQUIPMENT TO BE
RELOCATED AS SHOWN. EXTEND CONDUITS AND FEEDERS
AS NECESSARY FOR NEW LOCATION.
N = NEW FIXTURE R = RELOCATED
"PP-P9B"
(CONDO)
"PP-CD16"
"PP-CD15" "PP-CD12" "PP-CD11" "PP-CD10" "PP-CD7" "PP-CD6" "PP-CD5" "PP-CD3" "PP-CD2"
1000 AMPS
DISTRIBUTION PANEL
"DP-DC2"
208/120V., 3ɐ, 4 WIRE
ISC = 18,000
100A3P
100A3P
100A3P
100A3P
100A3P
100A3P
100A3P
100A3P
100A3P
200A3P
60A3P
100A3P
100A3P
SPARE
SPARE
1000A3P
30A3P
300 KVA
TRANSFORMER
"TR-5"
480/208/120V., 3ɐ, 4 WIRE
(K-4 RATED)
TO 500A3P BREAKER IN 3000
AMP MAIN SWITCHBOARD
"MSB-B", 480/277V., 3ɐ, 4 WIRE
UNIT 1024
UNIT 8203
POWER PLAN
1 of 2
E-100
SCALE: 1/4" = 1'-0"
1 POWER PLAN
SCALE: NONE 2 (PARTIAL) EXISTING ONE-LINE DIAGRAM
ISSUE DATE
UNIT 8203
FOUR SEASONS
RESORT & RESIDENCES
VAIL, CO
c3s
CHK BY:
SCALE:
SHEET:
JOB #:
DRW BY:
TITLE:
DATE:
COMMENT
AS NOTED
c3s
UNIT 8203
REMODEL
SEAL & SIGNATURE:
CLIENT:
Dr. Robert A. Behar
Unit 8203
FOUR SEASONS VAIL
1 Vail Road
VAIL, CO 81657
ARCHITECT:
Creative Design Associates
434 BROADWAY, 5TH FLOOR
NEW YORK, NY 10013
t. 212-748-8900
f. 212-748-7950
WESTERN US
4700 E BROMLEY LN, SUITE 105
BRIGHTON, CO 80601
t. 646-747-2171
c. 917-756-0057
dsorenson@ralcompanies.com
INTERIOR DESIGN:
Worth Interiors
30 BENCHMARK ROAD, SUITE 103
AVON, CO 81920
t. 970-949-9794
eddy@worthinteriors.com
ELECTRICAL ENGINEER:
C3S Incorporated
3212 WEST 45TH AVENUE
DENVER, CO 80211
t. 303-480-5144
theresa@c3sengineeringinc.com
15-27
1 FOR PERMIT
04/17/2015
04/27/15
05/11/15