HomeMy WebLinkAboutB15-0193_S010_1435611540.pdfx RETAINED BACKFILL: THE BACKFILL MATERIAL FOR THE "RETAINED BACKFILL ZONE" SHALL BE FREE OF ORGANICS AND DEBRIS AND CONSISTING OF EITHER GP, GM, GW, SP, SW, OR SM TYPE, CLASSIFIED IN ACCORDANCE WITH ASTM D2487 AND THE USCS CLASSIFICATION SYSTEM; FREE OF ROCK OR GRAVEL LARGER THAN 4 INCHES IN ANY DIMENSION. RETAINED BACKFILL MATERIAL SHALL BE TESTED BY A GEOTECHNICAL ENGINEER REGISTERED IN THE STATE OF COLORADO x VERIFY LOCATION OF EXISTING STRUCTURES AND UTILITIES PRIOR TO EXCAVATION. x PROTECT ADJACENT STRUCTURES AND UTILITIES FROM THE EFFECTS OF EXCAVATION AND CONSTRUCTION. EXCAVATION SUPPORT, IF REQUIRED, IS THE RESPONSIBILITY OF THE CONTRACTOR. x EXCAVATION AND BACKFILL: SHOULD THE EXCAVATION FOR THE PLACEMENT OF THE LEVELING PAD EXPOSE AN UNSATISFACTORY BEARING MATERIAL, THE WALL ENGINEER MAY REQUIRE REMOVAL AND REPLACEMENT OF THAT MATERIAL. THE REMOVED MATERIAL SHALL BE REPLACED WITH MATERIAL MEETING THE REQUIREMENTS SPECIFIED BY THE WALL GEOTECHNICAL ENGINEER COMPACTED IN CONFORMANCE WITH COMPACTION REQUIREMENTS SPECIFIED BY THE WALL GEOTECHNICAL ENGINEER. x MOISTURE CONTROL OF BACKFILL: UNIFORMLY MOISTEN OR AERATE SUBGRADE AND EACH SUBSEQUENT BACKFILL LAYER BEFORE COMPACTION TO WITHIN 2 PERCENT OF OPTIMUM MOISTURE CONTENT. x COMPACTION: EACH LAYER OF BACKFILL SHALL NOT EXCEED 8" BEFORE COMPACTING TO THE REQUIRED DENSITY AND BEFORE SUCCESSIVE LAYERS ARE PLACED. AT LEAST 6" OF MATERIAL SHALL BE IN PLACE PRIOR TO OPERATION OF TRACKED VEHICLES OVER THE SOIL REINFORCEMENT. ONLY HAND-OPERATED COMPACTION EQUIPMENT SHALL BE ALLOWED WITHIN 3' OF THE FRONT OF THE WALL FACE. O THE FILL AND COMPACTION OPERATION SHALL PROGRESS FROM THE FACE TOWARD THE BACK WORKING PARALLEL TO THE WALL FACE. O THE CONTRACTOR SHALL PLACE ADDITIONAL BLOCKS AND FILL MATERIAL, PROPERLY COMPACTED, TO RETURN THE FINISHED GRADE TO PLAN ELEVATIONS IF SETTLEMENT HAS OCCURRED. O COMPACT SOILS LEVELING PAD AND EACH LAYER OF BACKFILL (BOTH REINFORCED BACKFILL AND RETAINED BACKFILL) TO A MINIMUM OF 95 PERCENT OF THE MAXIMUM STANDARD PROCTOR DENSITY IN ACCORDANCE WITH AASHTO T-99 OR ASTM D698 AT MOISTURE CONTENT WITHIN 2 PERCENT OF OPTIMUM. x REINFORCEMENT: THE REINFORCEMENT SHALL BE LAID TO WITHIN 1" FROM THE FRONT FACE OF BLOCK. x LEVELING PAD: THE LEVELING PAD SHALL BE PLACED TO BE LEVEL TO WITHIN 1/4 INCH IN 10 FEET. x BLOCK FACING: AN OVERALL NEGATIVE BATTER (WALL FACE LEANING OUTWARD) BETWEEN BOTTOM AND TOP OF WALL IS NOT ALLOWED. THE FINAL WALL FACE SHALL HAVE A POSITIVE BATTER AS SHOWN ON THE CONTRACT PLANS AND IN NO CASE SHALL THE BATTER VARY MORE THAN 1.5%. THE SURFACE OF WALL FACE SHALL BE TESTED WITH A 10' STRAIGHTEDGE LAID ALONG THE SURFACE IN ALL DIRECTIONS. EXCEPT AS NECESSARY FOR HORIZONTAL ALIGNMENT OF THE WALL, CONVEX DEVIATION OF THE WALL FACE FROM THE STRAIGHTEDGE (BELLY WALL) SHALL NOT BE ALLOWED, AND CONCAVE DEVIATION FROM THE STRAIGHTEDGE SHALL BE LESS THAN ½". x PROTECTION: PREVENT DAMAGE TO WALL AND EARTHWORK BY SUBSEQUENT CONSTRUCTION AND UNCONTROLLED RUNOFF UNTIL SUBSTANTIAL COMPLETION. AT COMPLETION OF WALL CONSTRUCTION, IF OTHER WORK SUCH AS FINISH GRADING, PAVING, LANDSCAPING, OR STORM DRAINAGE ADJACENT TO THE WALL IS NOT TO BE INSTALLED IMMEDIATELY, GRADE THE TOP OF BACKFILL AND PROVIDE TEMPORARY DRAINAGE AS REQUIRED TO PREVENT WATER RUNOFF TOWARD THE WALL. x UNLESS OTHERWISE NOTED, ALL BLOCKS SHALL BE DRY STACKED AND PLACED WITH EACH BLOCK SPANNING THE JOINT IN THE ROW BELOW (RUNNING BOND). THE CAP BLOCK AND THE TOP TWO COURSES OF FULL SIZE BLOCK SHALL BE ATTACHED TO THE COURSES BELOW USING A MANUFACTURER'S RECOMMENDED ADHESIVE. x DISPOSAL: CONTRACTOR SHALL REMOVE SURPLUS WALL MATERIALS, INCLUDING BROKEN OR REJECTED BLOCKS, GEOGRID WASTE, TRASH, AND OTHER DEBRIS, AND LEGALLY DISPOSE OF IT OFF THE OWNER'S PROPERTY. ALL WORK SHALL CONFORM TO ACI 301-96. ALL STRUCTURAL CONCRETE TO BE FROM TYPE 1 PORTLAND CEMENT. STORE AGGREGATE, AND DEVELOP 3000 PSI MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS. SLAB-ON-GRADE SHALL DEVELOP 3000 PSI MINIMUM COMPRESSIVE STRENGTH AT 20 DAYS. SLUMP OF CONCRETE SHALL NOT EXCEED 4" UNLESS A HIGH RANGE WATER-REDUCING ADMIXTURE IS USED. THE SLUMP OF CONCRETE PRIOR TO ADDITION OF A HIGH RANGE WATER- REDUCING ADMIXTURE SHALL NOT EXCEED 4". THE SLUMP OF CONCRETE CONTAINING A HIGH RANGE WATER-REDUCING ADMIXTURE SHALL NOT EXCEED 10". AIR CONTENT SHALL BE BETWEEN 5 AND 7 PERCENT. NO HORIZONTAL CONSTRUCTION JOINTS SHALL BE MADE IN SLABS OR BEAMS. ALL CONCRETE SLABS-ON-GRADE TO HAVE CONTROL JOINTS NO GREATER THAN 12 FEET. THE OWNER IS HEREBY MADE AWARE OF THE CHANGE OF MOVEMENT AND CRACKING OF SLABS PLACED ON COMPACTED FILL OF NATIVE SOILS. THE RISKS OF SWELLING SOILS AND RESULTING HEAVING/CRACKING OF CONCRETE CAN BE MINIMIZED BUT NOT ELIMINATED WITH CAREFUL CONSTRUCTION AND MAINTENANCE PROCEDURES. PROVIDE A 3/4" CHAMBER AT ALL EXPOSED EDGES OF CONCRETE IN ACCORDANCE WITH ACI 301 SECTION 4.2.4 UNLESS NOTED OTHERWISE. AVOID CUTTING EXISTING REBAR WHEN DRILLING HOLES IN FORMED CONCRETE. ALL REINFORCING STEEL SHALL BE ASTM A615, GRADE 60 AND HAVE A MINIMUM OF 60,000 PSI YIELD STRENGTH. LAP SPLICES, WHERE PERMITTED BY THE ENGINEER, SHALL BE A MINIMUM OF 74 BAR DIAMETERS. WHERE PERMITTED, SPLICES MAY BE CLASS B CONTACT SPLICES. REINFORCEMENT TO HAVE THE FOLLOWING COVER: UNIFORMED SURFACE IN CONTACT WITH THE EARTH 3 IN. FORMED SURFACES EXPOSED TO EARTH OR WEATHER 1-1/2 IN. REINFORCING PLACING TOLERANCES: PER IBC 2003. DETAIL BARS IN ACCORDANCE WITH THE LATEST EDITIONS OF "ACI DETAILING MANUAL", PUBLICATION SP-66, AND "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", ACI 318. PROVIDE ACCESSORIES NECESSARY TO PROPERLY SUPPORT REINFORCING AT POSITIONS SHOWN ON PLANS. ALL DOWELS, BOLTS AND EMBEDDED PLATES SHALL BE SET AND TIED IN PLACE BEFORE THE CONCRETE IS POURED. "STABBING" DOWELS, BOLTS OR PLATES INTO PREVIOUSLY PLACED CONCRETE IS NOT PERMITTED. x LEVELING PAD: THE LEVELING PAD SHALL BE CONSTRUCTED OF CONCRETE AND SHALL BEAR NATIVE MATERIAL. THE SOILS BELOW THE LEVELING FOOTING ARE TO BE OBSERVED AND APPROVED BY THE ENGINEER PRIOR TO PLACEMENT OF THE FOOTING. SIEVE SIZE PERCENT PASSING 3/4" 100 NO. 4 30-65 NO. 8 25-55 NO. 200 3-12 x UNIT FILL: THE FILL MATERIAL PLACED INSIDE THE BLOCK UNITS SHALL CONSIST OF A WELL GRADED CLEAN 1 INCH MINUS CRUSHED STONE OR GRANULAR FILL MEETING THE FOLLOWING GRADATION: SIEVE SIZE PERCENT PASSING 1" 100 3/4" 50-90 NO. 4 0-60 NO. 40 0-50 NO. 100 0-5 NO. 200 0-2 x REINFORCED BACKFILL: O REINFORCED BACKFILL SHALL MEET THE FOLLOWING GRADATION TESTED IN ACCORDANCE WITH ASTM D-422: SIEVE SIZE PERCENT PASSING 2 INCH 100 -75 NO. 4 100 - 20 NO. 40 0 - 60 NO. 200 0 - 15 O THE MAXIMUM AGGREGATE SIZE SHALL BE LIMITED TO 3/4 INCH UNLESS FULL SCALE CONSTRUCTION DAMAGE TESTS HAVE BEEN PERFORMED TO EVALUATE THE INSTALLATION DAMAGE TO THE GEOSYNTHETIC. THE EFFECT OF THE CONSTRUCTION DAMAGE TESTS SHALL BE INCORPORATED INTO THE INSTALLATION DAMAGE REDUCTION FACTOR (RFID). O SUITABLE REINFORCED BACKFILL SOILS SHALL BE FREE OF ORGANICS AND DEBRIS AND CONSISTING OF EITHER GP, GW, SP, SW, OR SM TYPE, CLASSIFIED IN ACCORDANCE WITH ASTM D2487 AND THE USCS CLASSIFICATION SYSTEM. THE PLASTICITY OF THE FINE FRACTION OF THE REINFORCED SOIL SHALL BE LESS THAN 20. REINFORCED BACKFILL MATERIAL SHALL BE TESTED BY A GEOTECHNICAL ENGINEER REGISTERED IN THE STATE OF COLORADO. x PHYSICAL REQUIREMENTS: AT THE TIME OF DELIVERY TO THE WORK SITE, THE UNITS SHALL CONFORM TO THE FOLLOWING PHYSICAL REQUIREMENTS: O EITHER A FULL BLOCK OR A SAW CUT COUPON COMPRESSIVE TEST IS ACCEPTABLE TO VERIFY THE 28-DAY CONCRETE STRENGTH. THE LOCATION OF CUT FOR THE COUPON SHALL BE APPROVED BY THE OWNER'S ENGINEER. O THE AVERAGE COMPRESSIVE STRENGTH OF THREE (3) TESTS SHALL BE EQUAL OR GREATER THAN 4,500 PSI WITH THE MINIMUM OF 4,000 PSI FOR INDIVIDUAL TEST IN ACCORDANCE WITH ASTM C140 SECTIONS 6, 8 AND 9. O THE MINIMUM OVEN DRY WEIGHT OF CONCRETE BLOCK SHALL BE 125 PCF WITH A MAXIMUM WATER ABSORPTION RATE BY WEIGHT OF 6 PERCENT DETERMINED IN ACCORDANCE WITH THE REQUIREMENT OF ASTM C 140. O THE BLOCK WEIGHT (EXCLUDING CORE FILL) SHALL BE A MINIMUM OF 72 LBS. PER SQUARE FOOT OF WALL FACE. x FINISH AND APPEARANCE: ALL UNITS SHALL BE IN GOOD CONDITION. CRACKS, CHIPS AND/OR OTHER IMPERFECTIONS MAY BE CAUSE FOR REJECTION, AS DETERMINED BY THE OWNER'S ENGINEER. O ARCHITECTURAL TREATMENT SHALL MEET THE REQUIREMENTS SHOWN ON THE PLANS. O THE PERMISSIBLE VARIATIONS IN THE EXTERIOR DIMENSIONS OF THE CONCRETE BLOCK SHALL NOT DIFFER MORE THAN ± 1/8", EXCEPT THE HEIGHT OF THE BLOCK SHALL BE WITHIN ± 1/16" FROM THE SPECIFIED DIMENSIONS FOR AN INDIVIDUAL BLOCK. THE MINIMUM THICKNESS OF ANY WALLS OR WEBS WITHIN THE BLOCK SHALL BE ON AVERAGE 3" AT THE FACE AND 2" AT STEM AND BACK. x GEOSYNTHETIC SOIL REINFORCEMENT: SOIL REINFORCEMENT SHALL BE A GEOGRID OF HIGH- DENSITY POLYETHYLENE (HDPE) EXPANDED SHEET OR POLYESTER WOVEN FIBER MATERIALS, SPECIFICALLY FABRICATED FOR USE AS SOIL REINFORCEMENT. ACCEPTABLE PRODUCTS: O TENSAR UX1100, UX1400, UX1500, UX1600 GEOGRIDS O STRATA SYSTEMS 200, 300, 500, 600 GEOGRIDS O TC MIRAFI 2XT, 3XT, 5XT, 7XT, 8XT,1OXT GEOGRIDS O LONG TERM DESIGN STRENGTH (LTDS): THE LTDS OF MATERIAL SHALL BE DETERMINED USING THE FOLLOWING REDUCTION FACTORS TO ENSURE THE REQUIRED DESIGN LIFE. MANUFACTURERRFDRF1D*RFCRFSUNCSTRATA1.101.101.611.50TENSAR1.001.082.381.50TC MIRAFI1.101.151.671.50* THE INSTALLATION DAMAGE REDUCTION FACTORS (RFID) LISTED ARE FOR SAND BACKFILL. THE WALL DESIGNER SHALL BE RESPONSIBLE FOR VERIFYING THE APPLICABILITY OF THE REDUCTION FACTOR FOR THE SPECIFIC MATERIAL(S) USED AS REINFORCED BACKFILL. O THE LONG-TERM DESIGN STRENGTH (LTDS) OF THE GEOSYNTHETIC SHALL BE DETERMINED AS FOLLOWS: LTDS = TULT / (RFID * FRCR) O THE ALLOWABLE STRENGTH OF THE GEOSYNTHETIC SHALL BE DETERMINED AS FOLLOWS: TA = LTDS / (FSUNC) O WHERE: TULT = ULTIMATE TENSILE STRENGTH BASED ON THE MINIMUM AVERAGE ROLL VALUE (MARV). RFD = DURABILITY REDUCTION FACTOR. RFID = INSTALLATION DAMAGE REDUCTION FACTOR. RFCR = CREEP REDUCTION FACTOR. FSUNC = LOAD REDUCTION FACTOR TO ACCOUNT FOR DESIGN UNCERTAINTIES. TA = ALLOWABLE TENSILE STRENGTH. S0.10 NOTES SHEET 5082 E. HAMPDEN AVE. SUITE 145 DENVER, CO. 80222 (303)229-1234 TIMBER FALLS CONDOMINIUMS PARTIAL PROPERTY WALL RECONSTRUCTION 4500 MEADOW DRIVE (BLDG'S 1 & 2) VAIL , COLORADO 8 1657 SHEET NUMBER: SHEET TITLE: REVISIONS: JOB NUMBER: DESIGNED BY: DRAWN BY: CHECKED BY: DATE: DEC26052015-01 R. DAVIS M. WINGERTER R. DAVIS JUNE 7, 2015 06/29/15