HomeMy WebLinkAboutB14-0277_CCK1 Electrical Load Calc_1407170280.pdf I
Native Electric, Inc.
PO Box 1807
Eagle, CO 81631
LOAD CALC
Submitted to: David Cabin
2450 Chaminiox,Unit K-1,
Vail, Colorado
650 square feet @ 3 watts per ft.= 1950
Small appliance X 2 =3000
Dishwasher = 1500
Boiler = 1500
Fridge = 1500
Dryer =5000
Washer = 1500
Range =7000
TOTAL =22,950
First 10 KVA @ 100% = 10,000
Remaining Load @ 40% = 5,180
Total Load @ 15.180
15180/240= 64 AMPS
LOAD CALC =64 AMPS
NOTE: We will be adding recess lighting with LED lights. Upgrade devices to tamper proof.