Loading...
HomeMy WebLinkAboutinspector_summary_28647_02-01-2017-5294.pdfInspection Result:Fail Inspector:Charlie Davis Permit Type Inspection Type Address Construction Mechanical Final 756 FOREST RD (210107211012) (21010721101212) Inspection Date:02/01/2017 Permit #:B14-0363 TMK:21010721101212 Comments: 1. Balance report required for kitchen hoods (2) for make up air and exhaust air requirements are met. 2. Balance report required for kitchen hoods (2) for make up air and exhaust air requirements are met. 3. Label all condenser units 4. Applicant Signature 5. Inspector Signature 6. Label all condenser units 7. Inspector Signature 8. Applicant Signature Inspection Summary 9. Back draft dampers or terminations required at galvanized ducts on west side of unit 10. Back draft dampers or terminations required at galvanized ducts on west side of unit 11. Bird screens on all PVC. vents 12. Bird screens on all PVC. vents 13. Protection from snow shedding to condenser on east side 14. Protection from snow shedding to condenser on east side IMC Section 1101.3 15. Tamper resistant locking caps are required at refrigerant ports IMC Section 1101.10