HomeMy WebLinkAboutinspector_summary_28647_02-01-2017-5294.pdfInspection Result:Fail
Inspector:Charlie Davis
Permit Type Inspection Type Address
Construction Mechanical Final 756 FOREST RD (210107211012) (21010721101212)
Inspection Date:02/01/2017
Permit #:B14-0363
TMK:21010721101212
Comments:
1. Balance report required for kitchen hoods (2) for make up air and exhaust air requirements are met.
2. Balance report required for kitchen hoods (2) for make up air and exhaust air requirements are met.
3. Label all condenser units
4. Applicant Signature
5. Inspector Signature
6. Label all condenser units
7. Inspector Signature
8. Applicant Signature
Inspection Summary
9. Back draft dampers or terminations required at galvanized ducts on west side of unit
10. Back draft dampers or terminations required at galvanized ducts on west side of unit
11. Bird screens on all PVC. vents
12. Bird screens on all PVC. vents
13. Protection from snow shedding to condenser on east side
14. Protection from snow shedding to condenser on east side IMC Section 1101.3
15. Tamper resistant locking caps are required at refrigerant ports IMC Section 1101.10