HomeMy WebLinkAboutB14-0443_B14-0443 load calcs_1415116260.pdf A-Phase Electric, LLC 5194 Main Gore Drive Load Calculation
East Vail, CO
General Lighting and Receptacle Demand Load:
6367 sq. ft. x 3VA= 19101
1,500 VA x 2= 3000
1,500 VA x 1 = 1500
Total connected load: 23,601
3,000 VA @ 100%= 3,000
VA@35%= 7,210.4
2523.62
Total general lighting and
Receptacle demand load: 5,524
Range demand load:
12,000VA 8,000
Dryer Load:
5,000
Fixed appliance load:
Dishwasher 1 1,200
Garbage disposal 1 800
microwave 1 1,200
UC refrigerator 1 1,200
steam shower 1 8,000
subtotal 12,400
demand factor -25% 3,100
Total fixed appliance load: 9,300
Heating load:
heat tape 4800
Total heating load: 4,800
25% of largest motor: 200
continued next page
www.aphaseelectriclic.com
A-Phase Electric, LLC 5194 Main Gore Drive Load Calculation
East Vail, CO
Totals:
General lighting and receptacles: 5,524
Range: 8,000
Dryer: 5,000
Fixed appliance: 9,300
Heating: 4,800
25%of largest motor: 200
Total: VA 32,824
AMPS 136.77
Installed Service Size: 200A single phase
www.aphaseelectriclic.com