HomeMy WebLinkAboutB15-0068_stallion electrical load calcs_1429050540.pdf Tim Barany From: Nick Lunn <nicklunncec@yahoo.com> Sent: Friday, March 27, 2015 1:43 PM To: Tim Barany Subject: Load calc for service at 355 forest road Optional Residential Load Calculation Results: Multifamily Dwelling: Dwelling Units: Demand Factor: 100% Step 1: General Lighting and Recepticles: Total General Load @ 3VA: 18300 VA Step I Total: 18300 VA Step 2: AC System: 220.82(C)1 Total: 1500 220.82(C)2 Total: 0 220.82(C)3 Total: 0 220.82(C)4 Total: 3120 220.82(C)5 Total: 0 220.82(C)6 Total: 2400 Largest Load Per 220.82(C) Step 2 Total: 3120 VA Step 3: Fixed in Place Appliances: Step 3 Total: 6200VA Step 4: Dryers: Step 4 Total: 3500 kW Step 5: Cooking Appliances: Step 5 Total: 7000 kW General Load: First 10k @ 100%: 10000 Remainder over 10k @ 40%: 10000 Total General Load: 20000 Final Totals: Feeder Load: 23120 VA Feeder Amperage: 96.333333333333 Amps Neutral Load: 31 850 VA Neutral Amperage: 132.70833333333 Amps Service Size: 1 100 Amps Conductor Size: Feeders per Table 310.15(B)7: Copper: 4 AWG Aluminum: 2 AWG Neutral per Table 310.15(B)7: Copper: 4 AWG Aluminum: 2 AWG Ground per Table 250.66: Copper: 8 AWG Aluminum: 6 AWG It is highly recommended to double check the calculations before submitting them on any professional level. This calculation was generated with the ReiWare, LLC Service Load Calculation Tool Available on the Apple App Store, Google Play and Amazon App Store. Sent from my iPhone 2