HomeMy WebLinkAboutB15-0101_Load Calcs_1428948240.pdfLOAD CALCULATION
PER N.E.C. EXAMPLE D1 ( a )
VAIL MT. HAUS UNIT 679 - 04/09/15
208-V / 1-PHASE SUPPLY
GENERAL LOAD -LOAD IN VOLT-AMPS
936 SQ. FT. @ 3W/FT 2,808.00
SMALL APPLIANCE 3,000.00
LAUNDRY / APPLIANCES 1,500.00
TOTAL 7,308.00
3000VA @ 100%3,000.00
7,308VA - 3,000VA = 4,308VA @ 35%1,508.00
NET LOAD 4,508.00
RANGE - 1 @ 8 KVA EACH 8,000.00
MICROWAVE - 1 @ 1200 VA EACH 1,200.00
SUB ZERO - 1 @ 1200 VA EACH 1,200.00
DISHWASHER - 1 @ 1200 VA EACH 1,200.00
DISPOSAL - 1 @ 800 VA EACH 800.00
NET CALCULATED LOAD 16,908.00
MINIMUM FEEDER AMPS 81.29
SERVICE BUSSING / MAIN AMPACITY 90.00