Loading...
HomeMy WebLinkAbout223 BEAVER DAM RD TAB.pdf TEST, ADJUST AND BALANCE REPORT PROJECT 223 BEAVER DAM RD #1271 PREPARED FOR SKYLINE MECHANICAL REPORT ISSUE DATE 3/8/2017 PREPARED BY HVAC TAB llc P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB llc DATE: 3/8/2017 INSTRUMENT CALIBRATION REPORT PROJECT : 223 BEAVER DAM RD PROJECT ALTITUDE: “HG INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE SHORTRIDGE ADM-870C / #M09211 AIR FLOW READINGS 3/8/2017 06/02/2016 06/02/2017 ANEMOMETER #T57251515001 AIR FLOW READINGS NOT USED 05/06/2016 05/06/2017 SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * * TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/03/2016 06/03/2017 PITOT TUBE 18” PRES. READINGS 3/8/2017 N/A N/A PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A PITOT TUBE 48” PRES. READINGS NOT USED NA NA SHIMPO TACHOMETER / #C105B0010 RPM READINGS NOT USED 06/02/2016 06/02/2017 FLUKE 375 / #21290229 VOLT / AMP NOT USED 06/02/2016 06/02/2017 SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS NOT USED 06/02/2016 06/02/2017 ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * * FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 06/03/2016 06/03/2017 REFRACTOMETER RHA-100 / #RHA- 100 GLYCOL % READINGS NOT USED N/A N/A * CHECKED TO CALIBRATED METER REMARKS: AL L R E ADI NG S WITH SHORT R I DG E I NST R UMENT S AR E CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: HVAC TAB llc DATE: 3/8/2017 FAN NUMBER FC-1A MUA KEF-1 UNIT DATA UNIT DATA UNIT DATA MANUFACTURER CARRIER MIELE MODEL 39SVA07MZL432EBSXF DA 2210 SERIAL 2516R45949 FABR-NR 126960081 SCHEDULE RATING/OUTLET TOTAL 1000CFM OSA - ACTUAL CFM 1080 CFM 678 CFM FC-1A MUA IS INTERLOCKED WITH KEF-1 FAN TEST REPORT PROJECT: 223 BEAVER DAM RD SYSTEM: FC-1A MUA / KEF-1 SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-1A MUA 1 PITOT 16/10 1000 1080 1080 TOTAL KEF-1 1 ER 37.5/11 - 686 686 TOTAL NOTES: HVAC TAB llc DATE: 3/8/2017 AIR TERMINAL TEST REPORT PAGE: PROJECT: 223 BEAVER DAM RD SYSTEM: FC-1A MUA / KEF-1