HomeMy WebLinkAboutinspector_summary_29510_03-08-2017-5926.pdfInspection Result:Fail Inspector:Charlie Davis Permit T ype Inspection T ype Address Construction Mechanical Final 223 BEAVER DAM RD (210107112004) (21010711200439) Inspection Date:03/08/2017 Permit #:B15-0065.001 TMK:21010711200439 Comme nts: 1. Access to equipment, access opening and equipment platform/head height not provided for fan coil unit in attic above bathroom per IMC Sections 306.1 306.3 2. T AB report does not confirm kitchen hood exhaust rate or interlocking capacity with FC 1a. 3. Inspector Signature 4. Applicant Signature 5. Confirm mech room size and approval from Town Inspecti on Summary