RZ2-2a
RZ2-2b
RZ2-1
RZ2-3
RZ2-4
RZ2-5
5 6 2 7
3 4
A
B
C
G
H
K
L
M
E
D
J
F
RM2-1
RM2-2a RM2-3
RM2-5
RM2-4
RM2-5
NOT FOR CONSTRUCTION
Project number
Date
Drawn by
7/5/2015 6:40:41 PM
M102
LEVEL 2 PIPING PLAN
HUGHES-1
LOT 3 / 994 PTARMIGAN RD
VAIL,CO
Hughes
Residence
06.29.15
DAL
No. Description Date
1/4" = 1'-0"
1
LEVEL 2 PIPING PLAN
RE: _/M_ FOR RADIANT/SNOWMELT
MANIFOLD PIPING.
RE: _/M_ FOR ZONE HEATING COIL
ASSEMBLIES.
RE: _/M_ FOR CUH & UH PIPING.
COORDINATE ROUTING OF
CONDENSATE DRAIN LINES WITH
ARCHITECT PRIOR TO INSTALLATION.
PIPING ON EXTERIOR WALLS OR PRE-
CAST CONCRETE WALLS TO BE
ROUTED IN FRAMED WALL ON INTERIOR
SIDE OF INSULATION.
AVOID ROUTING PIPING OVER
ELECTRICAL ROOMS OR ELECTRICAL
PANELS; MAINTAIN N.E.C.
CLEARANCES. COORDINATE ROUTINGS
WITH ELECTRICAL CONTRACTOR.
CONTRACTOR TO MAINTAIN 8'-6" CLEAR
HEAD HEIGHT IN GARAGE AND INFORM
THE ENGINEER AND ARCHITECT OF
ANY AREAS THAT MAY NOT MEET 8'-6"
PRIOR TO INSTALLATION, MINIMUM 8'-2"
CLEAR HEAD HEIGHT MUST BE
MAINTAINED IN ACCESSIBLE VAN
AREAS.
PROVIDE FLEXIBLE PIPE CONNECTIONS
TO ALL MOTORIZED EQUIPMENT.
VERIFY ALL EQUIPMENT ACCESS
PANELS WITH MANUFACTURER AND
ARCHITECT.
PROTECT PIPING ROUTED ALONG
COLUMNS, WALLS, ETC. FROM DAMAGE
AS NECESSARY WITH CAGES.
COORDINATE WITH ARCHITECT.
PEX PIPING SHALL NOT BE ALLOWED
TO PENETRATE FIRE BARRIERS
WHERE FIRE CAULKING IS REQUIRED.
ALL BRANCH HEATING WATER PIPE TO
VAV BOXES ARE 3/4" PIPE, UNO
ALL BRANCH HEATING WATER PIPING
TO CABINET UNIT HEATERS AND UNIT
HEATERS SHALL BE 3/4" U.N.O.
ALL BRANCH CHILLED AND HEATING
WATER PIPING TO FAN COIL UNITS
SHALL BE 3/4" UNO
ALL VALVES SHALL BE INSTALLED
ABOVE DROP-IN CEILINGS IN
ACCESSIBLE LOCATIONS, OR WITH
ACCESS PANELS IN HARD-LID
CEILINGS.
ALL PIPING SHALL BE ROUTED AS HIGH
AS POSSIBLE IN THE CEILING SPACE.
UTILIZE JOIST SPACE WHEN POSSIBLE,
ESPECIALLY WHERE CROSSING OTHER
PIPES, DUCTS, AND ELECTRICAL.
ACCESS PANELS SHALL BE 24x24, UNO
LOCATIONS SHOWN ARE
APPROXIMATE, EXACT LOCATIONS
SHALL BE COORDINATED WITH THE
ARCHITECTS DRAWINGS AND WITH
THE LOCATIONS OF THE EQUIPMENT
OR APPARATUS THAT THEY SERVE.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
NOTES:
PERMIT SET
09/14/15