HomeMy WebLinkAboutB15-0250_M501_1442254080.pdfRADIANT MANIFOLD PIPING DIAGRAM
NO SCALE
A
B
HWR
HWS
NOTE:
PROVIDE
MANUFACTURER'S
MANIFOLDS WITH VALVES
EAGLE RIVER WATER ENTRANCE DIAGRAM
F
M
NO SCALE
2-WAY COIL PIPING DIAGRAM
NO SCALE
C
E
3-WAY COIL PIPING DIAGRAM
NO SCALE D
MANIFOLD BOX WITH ACCESS DOOR
MOUNTED IN WALL. FIRE RATED
ACCESS DOOR AS REQUIRED.
MANUFACTURER'S MANIFOLD ASSY.
WITH VALUES.
ZONE BALANCE VALVE
UNISTRUT SUPPORT
SERPENTINE TUBING. QUANTITY AS
REQUIRED.
TAPE PIPE AT UNISTRUT SUPPORT.
MANUFACTURER'S MANIFOLD ASSY.
WITH VALUES.
TO T-STAT.
TO PIPING MAINS
LOOP CONTROL VALVES, TYP.
SEE FIRE ENTRY DIAGRAM ,
THIS SHEET. _" LINE (VERIFY
WITH FIRE PROTECTION
CONTRACTOR).
DOMESTIC WATER SERVICE
SHUT-OFF VALVE.
_" IRRIGATION LINE WITH
APPROVED REDUCED PRESSURE
BACKFLOW PREVENTION DEVICE.
(VFY. WITH IRRIGATION
CONTRACTOR).
1-1/2" CW TO BUILDING.
REDUCED PRESSURE TYPE
BACKFLOW PREVENTER.
CERTIFIED TESTER TO TEST.
1" WATER METER WITH
REMOTE READOUT.
PRESSURE REDUCING VALVE, TYP.
WATTS 223, __" SET @ 60 PSI
WATTS 223, __" SET @ __ PSI
2" CW/FIRE SERVICE (VERIFY
SIZE WITH FIRE PROTECTION
CONTRACTOR).
NOTE:
WATER METER AND BACKFLOW
PREVENTER MUST BE MOUNTED
HORIZONTALLY.
DESIGNER NOTES:
1. VERIFY IF & WHERE BFP IS REQ'D.
2. VERIFY IF FIRE PIPING APPLIES TO JOB. 3.
LOCATE REMOTE METER READOUT.
4. IF ONLY ONE PRV IS USED, OMIT
a. SECOND PRV
b. ISOLATION VALVES ON PRV
5. COORDINATE PIPING AND VALVING WITH AHJ.
METER
BYPASS.
COIL
NOTES:
1. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENT
CONTAINING FANS OR COMPRESSORS, NOT REQ'D FOR
EQUIPMENT SUCH AS DUCT COILS.
2. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER
ENTERS MOST DOWNSTREAM COIL, LEAVES MOST
UPSTREAM COIL).
3. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL
INFORMATION.
4. 2-WAY VALVE NORMALLY OPEN FOR HEATING AND
NORMALLY CLOSED FOR COOLING.
MANIFOLD PIPING DIAGRAM
NO SCALE SMR
SMS
CONTROL VALVE. MANIFOLD BOX (WALL
MOUNTED FOR
RADIANT; LOCATED IN
SLAB FOR
SNOWMELT).
MANUFACTURER'S
MANIFOLD ASSY.
LOOP
BALANCE/ISOLATION
VALVE
MANUFACTURER'S
MANIFOLD ASSEMBLY
WITH REVERSE
RETURN PIPING.
RADIANT/SNOWMELT
TUBING. LOOP
QUANTIITY AS
REQUIRED.
NOTES:
1. PROVIDE MANUFACTURER'S MANIFOLDS AND ISOLATION VALVES WITH PIPING.
2. FOR EXTERIOR MANIFOLD LOCATIONS PROVIDE WATERPROOF MANIFOLD BOX OR
WATERPROOF CONTROL VALVE.
TO PIPING MAINS
AIR VENT AT HIGH
POINTS, TYPICAL.
MANIFOLD BALANCE
VALVE.
RETURN
SUPPLY
COIL
NOTES:
1. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENT
CONTAINING FANS OR COMPRESSORS, NOT REQ'D FOR
EQUIPMENT SUCH AS DUCT COILS.
2. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER
ENTERS MOST DOWNSTREAM COIL, LEAVES MOST
UPSTREAM COIL).
3. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL
INFORMATION.
4. 3-WAY VALVE WITH COIL RETURN PIPED TO NORMALLY
OPEN PORT FOR HEATING AND NORMALLY CLOSED PORT
FOR COOLING.
MANUAL AIR VENT
AT HIGHEST
POINT IN PIPING.
STRAINER
WITH
BLOWDOWN
VALVE AND
CAP.
SUPPLY
RETURN
STRAINER
WITH
BLOWDOWN
AND CAP.
MANUAL AIR VENT
AT HIGHEST
POINT IN PIPING.
NOT FOR CONSTRUCTION
Project number
Date
Drawn by
7/5/2015 6:41:32 PM
M501
MECHANICAL DIAGRAMS
HUGHES-1
LOT 3 / 994 PTARMIGAN RD
VAIL,CO
Hughes
Residence
06.29.15
DAL