Loading...
HomeMy WebLinkAboutHughes Blower Door Report - Final.pdf Page 1 of 1 1/19/2017 P.O. Box 7627, Avon, CO 81620 | P: 970.306.4233 | F: 866.403.3485 | www.activeenergies.com Hughes Residence Blower Door Report Test Date: January 19, 2017 Builder: R.A. Nelson & Associates Contact: Jeff Beacom Site Address: 994 Ptarmigan Road, Vail, CO Site Visit By: Megan Gilman Background The project goal is to undergo testing at the final point in construction to determine if the home meets the IECC requirements for infiltratoin. Active Energies was contracted to perform a final blower door test to determine total air infiltration. The home is permitted under the Town of Vail and requires blower door testing per the IECC. The blower door testing must show a tested value of 3 ACH50 or lower in order to comply with the IECC. The project does not have outside air going directly into any ductwork and does not have ductwork run outside of conditioned space, so it is our determination that this home should meet the exemption for duct leakage testing requirements and, therefore, was not tested for duct leakage at the final phase. Site Observations Construction of the building envelope was complete. All exterior openings were shut and locked and interior doors were open. The blower door test was performed in the doorway between the home and garage. The pressure probe place outside. Blower Door Test The home was depressurized, utilizing blower door testing equipment to a pressure of -50 Pa. At the test pressure, the CFM50 was recorded, in order to determine the ACH50. The blower door air leakage resulted in the following measurements: 2.02 ACH50 Congratulations on a wonderful final testing result. Please call with any questions or concerns. Megan Gilman LEED® QAD, LEED Green Rater, RESNET QAD