HomeMy WebLinkAboutTAB report.pdf
TEST, ADJUST AND BALANCE REPORT
PROJECT
HUGHES RESIDENCE
#1265
PREPARED FOR
SKYLINE MECHANICAL
REPORT ISSUE DATE
1/26/2017
PREPARED BY
HVAC TAB llc
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB llc
DATE: 1/25/2017
INSTRUMENT
CALIBRATION REPORT
PROJECT : HUGHES RESIDENCE
PROJECT ALTITUDE: “HG
INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION
DATE
CALIBRATION
DUE DATE
SHORTRIDGE ADM-870C / #M09211 AIR FLOW READINGS 1/25/2017 06/02/2016 06/02/2017
ANEMOMETER #T57251515001 AIR FLOW READINGS 1/25/2017 05/06/2016 05/06/2017
SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * *
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/03/2016 06/03/2017
PITOT TUBE 18” PRES. READINGS 1/25/2017 N/A N/A
PITOT TUBE 24” PRES. READINGS 1/25/2017 N/A N/A
PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 48” PRES. READINGS NOT USED NA NA
SHIMPO TACHOMETER / #C105B0010 RPM READINGS 1/25/2017 06/02/2016 06/02/2017
FLUKE 375 / #21290229 VOLT / AMP 1/25/2017 06/02/2016 06/02/2017
SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS 1/25/2017 06/02/2016 06/02/2017
ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * *
FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 06/03/2016 06/03/2017
REFRACTOMETER RHA-100 / #RHA-
100
GLYCOL % READINGS NOT USED N/A N/A
* CHECKED TO CALIBRATED METER
REMARKS: AL L R E ADI NG S WITH SHORT R I DG E I NST R UMENT S AR E CORRECTED FOR
TEMPERATURE AND ALTITUDE. PAGE:
NOTES:
HVAC TAB llc
DATE: 1/25/2017
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER CARRIER
MODEL 42BHE201D3R2009EE
SERIAL 326071-10-1
FAN TYPE CENTRIFUGAL
RATING/OUTLET
TOTAL 2000CFM@0.4"ESP/2098CFM
MIN OSA CFM 500 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER MARATHON
HP R.P.M. 1 1725
PHASE FRAME 1 54Z
S.F. TYPE 1.0 -
VOLTS AMPS 115/208/230 14.4/7.2/7.2
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VP 3 3/4"
MOTOR BORE 5/8"
FAN DRIVE 1 AK 64"
FAN BORE 1"
NO. BELTS & SIZE 1 / A 30
ROTATION CORRECT
CENTERLINE
8 1/2"
MOTOR ADJ
+2 -1/2
PULLEY
SPEED + 2 1/2
TURNS
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (HERTZ) NONE
SET AT (HERTZ) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. 950 876
VOLTAGE 240 240
AMPERAGE 6.5 6.4
PAGE:
AIRFLOW DATA
SUPPLY CFM 2195
OSA CFM 475
RETURN CFM 1720
PROJECT: HUGHES RESIDENCE SYSTEM: FC-1
COIL
HW
DX
COIL
F
I
L
T
E
R
ATMOS 0.21" -0.38"
NOTES:
HVAC TAB llc
DATE: 1/25/2017
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER CARRIER
MODEL 42BHE201D3L82009EE
SERIAL 326071-20-1
FAN TYPE CENTRIFUGAL
RATING/OUTLET
TOTAL 2000CFM@0.4"ESP/2100CFM
MIN OSA CFM 500 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER MARATHON
HP R.P.M. 1 1725
PHASE FRAME 1 56Z
S.F. TYPE 1.0 -
VOLTS AMPS 115/208/230 14.4/7.2/7.2
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VP 3 3/4"
MOTOR BORE 5/8"
FAN DRIVE 1 AK 64
FAN BORE 1"
NO. BELTS & SIZE 1 / A 30
ROTATION CORRECT
CENTERLINE
8"
MOTOR ADJ
+ 2 - 2
PULLEY
SPEED + 0
TURNS
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (HERTZ) NONE
SET AT (HERTZ) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. 960 1035
VOLTAGE 241 241
AMPERAGE 6.3 6.6
PAGE:
AIRFLOW DATA
SUPPLY CFM 2038
OSA CFM 483
RETURN CFM 1555
PROJECT: HUGHES RESIDENCE SYSTEM: FC-2
COIL
HW
DX
COIL
F
I
L
T
E
R
ATMOS 0.42" -0.39"
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
FC-1 1 SR 13/5 200 68 219
2 SR 13/5 400 442 422
3 SR 13/5 400 339 413
4 SR 17/5 166 281 180
5 SR 17/5 166 80 168
6 SR 17/5 166 260 178
7 SR 23.5/3.5 200 397 203
8 SR 23.5/3.5 200 287 206
9 SR 23.5/3.5 200 316 207
2098 2470 2195 TOTAL
FC-2 1 SR 18/6.5 400 367 384
2 SR 18/6.5 400 454 388
3 SR 18/6.5 400 452 381
4 SR 18/6.5 400 413 380
5 SR 17/5 450 47 434
6 SR 13/5 50 0 71
2100 1733 2038 TOTAL
NOTES:
HVAC TAB llc
DATE: 1/22/2017
AIR TERMINAL
TEST REPORT
PAGE:
PROJECT: HUGHES RESIDENCE SYSTEM: FC-1 / FC-2
NOTES:
HVAC TAB llc
DATE: 1/25/2017
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER CARRIER
MODEL FV4CNF002L00ABAA
SERIAL 1316A84491
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1000CFM@0.25"ESP/
700CFM
MIN OSA CFM 200 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. 1/2 -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 208/230 4.3
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE DD
MOTOR BORE DD
FAN DRIVE DD
FAN BORE DD
NO. BELTS & SIZE DD
ROTATION CORRECT
CENTERLINE
MOTOR ADJ
PULLEY
SPEED
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (HERTZ) NONE
SET AT (HERTZ) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. DD DD
VOLTAGE NA NA
AMPERAGE NA NA
PAGE:
AIRFLOW DATA
SUPPLY CFM 730
OSA CFM 191
RETURN CFM 539
PROJECT: HUGHES RESIDENCE SYSTEM: FC-3
DX
COIL
F
I
L
T
E
R
ATMOS 0.09" -0.11"
HW
COIL
NOTES:
HVAC TAB llc
DATE: 1/20/2017
AIR AP PARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER CARRIER
MODEL FV4CNF002
SERIAL 2415A84944
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1000CFM@0.4"ESP/
600CFM
MIN OSA CFM 200 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. 1/2 -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 208/230 4.3
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE DD
MOTOR BORE DD
FAN DRIVE DD
FAN BORE DD
NO. BELTS & SIZE DD
ROTATION CORRECT
CENTERLINE
MOTOR ADJ
PULLEY
SPEED
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (HERTZ) NONE
SET AT (HERTZ) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. DD DD
VOLTAGE NA NA
AMPERAGE NA NA
PAGE:
AIRFLOW DATA
SUPPLY CFM 579
OSA CFM 207
RETURN CFM 372
PROJECT: HUGHES RESIDENCE SYSTEM: FC-4
DX
COIL
F
I
L
T
E
R
ATMOS 0.16" -0.22"
HW
COIL
NOTES:
HVAC TAB llc
DATE: 1/22/2017
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER CARRIER
MODEL FV4CNF002
SERIAL 1316A84493
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 1200CFM@0.25"ESP/
800 CFM
MIN OSA CFM 200 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. 1/2 -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 208/230 4.3
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE DD
MOTOR BORE DD
FAN DRIVE DD
FAN BORE DD
NO. BELTS & SIZE DD
ROTATION CORRECT
CENTERLINE
MOTOR ADJ
PULLEY
SPEED
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (HERTZ) NONE
SET AT (HERTZ) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. DD DD
VOLTAGE NA NA
AMPERAGE NA NA
PAGE:
AIRFLOW DATA
SUPPLY CFM 815
OSA CFM 196
RETURN CFM 619
PROJECT: HUGHES RESIDENCE SYSTEM: FC-5
DX
COIL
F
I
L
T
E
R
ATMOS 0.12" -0.16"
HW
COIL
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
FC-3 1 SR 17/5 250 384 256
2 SR 17/5 150 275 161
3 SR 17/5 150 311 165
4 SR 9.25/9.25 150 295 148
700 1265 730 TOTAL
FC-4 1 SR 18/6.5 150 108 154
2 SR 18/6.5 150 70 126
3 SR 17/5 300 235 299
600 413 579 TOTAL
FC-5 1 SR 17/5 250 340 254
2 SR 13/13 250 476 243
3 SR 17/5 250 316 264
4 SR 9/3 50 611 54
800 1248 815 TOTAL
NOTES:
HVAC TAB llc
DATE: 1/25/2017
AIR TERMINAL
TEST REPORT
PAGE:
PROJECT: HUGHES RESIDENCE SYSTEM: FC-3 / FC-4 / FC-5
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
EF-1 1 ER 8.5/8.5 50 67 67 TOTAL
2 ER 8.5/8.5 50 36 36 TOTAL
3 ER 8.5/8.5 50 65 65 TOTAL
4 ER 8.5/8.5 50 50 50 TOTAL
5 ER 8.5/8.5 50 53 53 TOTAL
6 ER 8.5/8.5 50 56 56 TOTAL
7 ER 8.5/8.5 50 57 57 TOTAL
8 ER 8.5/8.5 50 64 64 TOTAL
9 ER 8.5/8.5 50 58 58 TOTAL
10 ER 8.5/8.5 50 28 28 TOTAL
11 ER 8.5/8.5 50 61 61 TOTAL
EF-2 1 ER 8.5/8.5 120 91 91 TOTAL
2 ER 8.5/8.5 120 142 142 TOTAL
3 ER 8.5/8.5 120 169 169 TOTAL
4 - - - - - - - - - DELETED
5 ER 8.5/8.5 120 174 174 TOTAL
6 ER 8.5/8.5 120 41 41 TOTAL
EF-3 1 ER 10/10 200 235 235 TOTAL
2 ER 10/10 200 280 280 TOTAL
3 ER 10/10 200 232 232 TOTAL
4 ER 10/10 200 202 202
NOTES:
HVAC TAB llc
DATE: 1/23/2017
AIR TERMINAL
TEST REPORT
PAGE:
PROJECT: HUGHES RESIDENCE SYSTEM: EF-1 / EF-2 / EF-3
HVAC TAB llc
DATE: 1/25/2017
FLOW METER DESIGN MEASURED
LOCATION TYPE SIZE DESIGN
P
DESIGN
GPM FINAL P
VALVE
POSITION
% OPEN
FINAL GPM
RFZ-1-1 UPONOR 3/4" 2 - - 2.0
RFZ-1-2 TA 3/4" 1 4.66 0.7 1.0
RFZ-1-3 UPONOR 3/4" 1.6 - - 1.6
RFZ-1-4A UPONOR 3/4" 0.7 - - 0.7
RFZ-1--4B UPONOR 3/4" 0.5 - - 0.5
RFZ-1-5A UPONOR 3/4" 0.7 - - 0.7
RFZ-1-5B UPONOR 3/4" 0.4 - - 0.4
RFZ-2-1 UPONOR 3/4" 1.0 - - 1.0
RFZ-2-2A UPONOR 3/4" 0.4 - - 0.4
RFZ-2-2B UPONOR 3/4" 0.3 - - 0.3
RFZ-2-3 UPONOR 3/4" 0.8 - - 0.8
RFZ-2-4A UPONOR 3/4" 1.0 - - 1.0
RFZ-2-4B UPONOR 3/4" 1.8 - - 1.8
RFZ-2-5 UPONOR 3/4" 0.8 - - 0.8
RFZ-3-1A UPONOR 3/4" 0.5 - - 0.5
RFZ-3-1B UPONOR 3/4" 0.5 - - 0.5
RFZ-3-1C UPONOR 3/4" 0.3 - - 0.3
RFZ-3-2 UPONOR 3/4" 1.0 - - 1.0
RFZ-3-3A UPONOR 3/4" 0.3 - - 0.3
RFZ-3-3B UPONOR 3/4" 0.6 - - 0.6
RFZ-3-3C UPONOR 3/4" 0.3 - - 0.3
RFZ-3-4A UPONOR 3/4" 0.5 - - 0.5
RFZ-3-4B UPONOR 3/4" 0.4 - - 0.4
RFZ-3-5A UPONOR 3/4" 0.9 - - 0.9
RFZ-3-5B UPONOR 3/4" 0.4 - - 0.4
BALANCE VALVE
TEST REPORT
PROJECT: HUGHES RESIDENCE SYSTEM: RFZ-1-1 - 3-5B
PAGE:
HVAC TAB llc
DATE: 1/25/2017
FLOW METER DESIGN MEASURED
LOCATION TYPE SIZE DESIGN
P
DESIGN
GPM FINAL P
VALVE
POSITION
% OPEN
FINAL GPM
SMZ-1 - - - 12 - - *2
SMZ-2 - - - 12 - - *2
SMZ-3 - - - 8 - - *2
SMZ-4 - - - 4 - - *2
SMZ-5 - - - 4 - - *2
SMZ-6 - - - 8 - - *2
SMZ-7 - - - 4 - - *2
SMZ-8 - - - 8 - - *2
SMZ-9 - - - 2 - - *2
FC-1 TA 3/4 5.0 10.0 2.15 5.03
FC-2 TA 3/4 5.0 9.13 2.20 5.01
FC-3 TA 3/4 3.0 11.0 1.50 3.01
FC-4 TA 3/4 3.0 9.27 1.55 3.03
FC-5 TA 3/4 3.0 7.98 1.63 3.00
BALANCE VALVE
TEST REPORT
PROJECT: HUGHES RESIDENCE
PAGE:
NOTES:*2 DENOTES NO CIRCUIT SETTER INSTALLED
SYSTEM: SMZ-1-8 / FC-1-5
PAGE:
SYSTEM: BL-1A / BL-1B
PROJECT: HUGHES RESIDENCE
PUMP IDENTIFICATION BL-1A BL-1B PUMP MANUFACTURER GRUNDFOS GRUNDFOS
MODEL NUMBER TYPE UPS 26-99 FC UPS 26-99 FC
SERIAL NUMBER PC 1438 PC 1345
RATING GPM RATING Ft. Hd. 30 GPM Ft. Hd. 30 GPM Ft. Hd. MOTOR MANUFACTURER - -
MOTOR HP
(KW) RPM - - - -
PHASE FRAME 1 - 1 -
S.F. TYPE - - - -
VOLTS AMPS 115 1.3/1.5/1.8 115 1.3/1.5/1.8 STARTER MANUFACTURER NONE NONE
MODEL NONE NONE
SIZE NONE NONE
RANGE NONE NONE
SETTING (AMPS) NONE NONE
REQUIRED THERMAL NONE NONE
RATING AMPS NONE NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD.
VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD.
INDICATED/ACTUAL IMPELLER DIAMETER
VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD.
VALVE OPEN GPM *1 *1
DISCHARGE PRESSURE PSI/Ft.Hd P1
SUCTION PRESSURE PSI/Ft.Hd P2
P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD.
SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD.
P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD.
GPM *1 (HI SPD) *1 (HI SPD)
VOLTS NA NA
AMPS NA NA
HVAC TAB llc
DATE: 1/25/2017
PUMP TEST REPORT
PAGE:
NOTES:
NA DENOTES NO ACCESS
*1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER
SYSTEM: HWP-1A / HWP-1B
PROJECT: HUGHES RESIDENCE
PUMP IDENTIFICATION HWP-1A HWP-1B PUMP MANUFACTURER GRUNDFOS GRUNDFOS
MODEL NUMBER TYPE MAGNA 3 40-180-F-216 MAGNA 3 40-180-F-216
SERIAL NUMBER 10001586 10001566
RATING GPM RATING F t. Hd. 30 GPM Ft. Hd. 30 GPM Ft. Hd. MOTOR MANUFACTURER - -
MOTOR HP
(KW) RPM - - - -
PHASE FRAME 1 - 1 -
S.F. TYPE - - - -
VOLTS AMPS 208/230 0.18 / 2.61 208/230 0.18 / 2.61 STARTER MANUFACTURER NONE NONE
MODEL NONE NONE
SIZE NONE NONE
RANGE NONE NONE
SETTING (AMPS) NONE NONE
REQUIRED THERMAL NONE NONE
RATING AMPS NONE NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD.
VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD.
INDICATED/ACTUAL IMPELLER DIAMETER
VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD.
VALVE OPEN GPM *1 *1
DISCHARGE PRESSURE PSI/Ft.Hd P1
SUCTION PRESSURE PSI/Ft.Hd P2
P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD.
SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD.
P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD.
GPM *1 *1
VOLTS NA NA
AMPS NA NA
HVAC TAB llc
DATE: 1/25/2017
PUMP TEST REPORT
PAGE:
NOTES:
NA DENOTES NO ACCESS
*1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER
SYSTEM: SMP-1 / DHWP-1
PROJECT: HUGHES RESIDENCE
PUMP IDENTIFICATION SMP-1 DHWP-1 PUMP MANUFACTURER GRUNDFOS GRUNDFOS
MODEL NUMBER TYPE MAGNA 3 65-150-F-340 ALPHA 15-55F/LC
SERIAL NUMBER 10002839 PC 1536
RATING GPM RATING Ft. Hd. 45 GPM Ft. Hd. 5 GPM Ft. Hd. MOTOR MANUFACTURER - -
MOTOR HP
(KW) RPM - - - -
PHASE FRAME 1 - 1 -
S.F. TYPE - - - -
VOLTS AMPS 208/230 0.30/5.68 115 - STARTER MANUFACTURER NONE NONE
MODEL NONE NONE
SIZE NONE NONE
RANGE NONE NONE
SETTING (AMPS) NONE NONE
REQUIRED THERMAL NONE NONE
RATING AMPS NONE NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD.
VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD.
INDICATED/ACTUAL IMPELLER DIAMETER
VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD.
VALVE OPEN GPM *1 *1
DISCHARGE PRESSURE PSI/Ft.Hd P1
SUCTION PRESSURE PSI/Ft.Hd P2
P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD.
SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD.
P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD.
GPM *1 *1
VOLTS NA NA
AMPS NA NA
HVAC TAB llc
DATE: 1/25/2017
PUMP TEST REPORT
PAGE:
NOTES:
NA DENOTES NO ACCESS
*1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER
SYSTEM: WHCP-1A
PROJECT: HUGHES RESIDENCE
PUMP IDENTIFICATION WHCP-1A NOT USED PUMP MANUFACTURER GRUNDFOS
MODEL NUMBER TYPE UPS 43-100 F
SERIAL NUMBER PC 1627
RATING GPM RATING Ft. Hd. 14 GPM Ft. Hd. GPM Ft. Hd. MOTOR MANUFACTURER -
MOTOR HP
(KW) RPM - -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 115 2.5/3.1/3.5 STARTER MANUFACTURER NONE
MODEL NONE
SIZE NONE
RANGE NONE
SETTING (AMPS) NONE
REQUIRED THERMAL NONE
RATING AMPS NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD.
VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD.
INDICATED/ACTUAL IMPELLER DIAMETER
VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD.
VALVE OPEN GPM *1
DISCHARGE PRESSURE PSI/Ft.Hd P1
SUCTION PRESSURE PSI/Ft.Hd P2
P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD.
SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD.
P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD.
GPM *1 (SPD-3)
VOLTS NA
AMPS NA
HVAC TAB llc
DATE: 1/25/2017
PUMP TEST REPORT
PAGE:
NOTES:
NA DENOTES NO ACCESS
*1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER