Loading...
HomeMy WebLinkAboutTAB report.pdf TEST, ADJUST AND BALANCE REPORT PROJECT HUGHES RESIDENCE #1265 PREPARED FOR SKYLINE MECHANICAL REPORT ISSUE DATE 1/26/2017 PREPARED BY HVAC TAB llc P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB llc DATE: 1/25/2017 INSTRUMENT CALIBRATION REPORT PROJECT : HUGHES RESIDENCE PROJECT ALTITUDE: “HG INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE SHORTRIDGE ADM-870C / #M09211 AIR FLOW READINGS 1/25/2017 06/02/2016 06/02/2017 ANEMOMETER #T57251515001 AIR FLOW READINGS 1/25/2017 05/06/2016 05/06/2017 SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * * TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/03/2016 06/03/2017 PITOT TUBE 18” PRES. READINGS 1/25/2017 N/A N/A PITOT TUBE 24” PRES. READINGS 1/25/2017 N/A N/A PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A PITOT TUBE 48” PRES. READINGS NOT USED NA NA SHIMPO TACHOMETER / #C105B0010 RPM READINGS 1/25/2017 06/02/2016 06/02/2017 FLUKE 375 / #21290229 VOLT / AMP 1/25/2017 06/02/2016 06/02/2017 SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS 1/25/2017 06/02/2016 06/02/2017 ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * * FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 06/03/2016 06/03/2017 REFRACTOMETER RHA-100 / #RHA- 100 GLYCOL % READINGS NOT USED N/A N/A * CHECKED TO CALIBRATED METER REMARKS: AL L R E ADI NG S WITH SHORT R I DG E I NST R UMENT S AR E CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: NOTES: HVAC TAB llc DATE: 1/25/2017 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER CARRIER MODEL 42BHE201D3R2009EE SERIAL 326071-10-1 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 2000CFM@0.4"ESP/2098CFM MIN OSA CFM 500 CFM MOTOR NAMEPLATE DATA MANUFACTURER MARATHON HP R.P.M. 1 1725 PHASE FRAME 1 54Z S.F. TYPE 1.0 - VOLTS AMPS 115/208/230 14.4/7.2/7.2 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1 VP 3 3/4" MOTOR BORE 5/8" FAN DRIVE 1 AK 64" FAN BORE 1" NO. BELTS & SIZE 1 / A 30 ROTATION CORRECT CENTERLINE 8 1/2" MOTOR ADJ +2 -1/2 PULLEY SPEED + 2 1/2 TURNS STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (HERTZ) NONE SET AT (HERTZ) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. 950 876 VOLTAGE 240 240 AMPERAGE 6.5 6.4 PAGE: AIRFLOW DATA SUPPLY CFM 2195 OSA CFM 475 RETURN CFM 1720 PROJECT: HUGHES RESIDENCE SYSTEM: FC-1 COIL HW DX COIL F I L T E R ATMOS 0.21" -0.38" NOTES: HVAC TAB llc DATE: 1/25/2017 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER CARRIER MODEL 42BHE201D3L82009EE SERIAL 326071-20-1 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 2000CFM@0.4"ESP/2100CFM MIN OSA CFM 500 CFM MOTOR NAMEPLATE DATA MANUFACTURER MARATHON HP R.P.M. 1 1725 PHASE FRAME 1 56Z S.F. TYPE 1.0 - VOLTS AMPS 115/208/230 14.4/7.2/7.2 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1 VP 3 3/4" MOTOR BORE 5/8" FAN DRIVE 1 AK 64 FAN BORE 1" NO. BELTS & SIZE 1 / A 30 ROTATION CORRECT CENTERLINE 8" MOTOR ADJ + 2 - 2 PULLEY SPEED + 0 TURNS STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (HERTZ) NONE SET AT (HERTZ) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. 960 1035 VOLTAGE 241 241 AMPERAGE 6.3 6.6 PAGE: AIRFLOW DATA SUPPLY CFM 2038 OSA CFM 483 RETURN CFM 1555 PROJECT: HUGHES RESIDENCE SYSTEM: FC-2 COIL HW DX COIL F I L T E R ATMOS 0.42" -0.39" SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-1 1 SR 13/5 200 68 219 2 SR 13/5 400 442 422 3 SR 13/5 400 339 413 4 SR 17/5 166 281 180 5 SR 17/5 166 80 168 6 SR 17/5 166 260 178 7 SR 23.5/3.5 200 397 203 8 SR 23.5/3.5 200 287 206 9 SR 23.5/3.5 200 316 207 2098 2470 2195 TOTAL FC-2 1 SR 18/6.5 400 367 384 2 SR 18/6.5 400 454 388 3 SR 18/6.5 400 452 381 4 SR 18/6.5 400 413 380 5 SR 17/5 450 47 434 6 SR 13/5 50 0 71 2100 1733 2038 TOTAL NOTES: HVAC TAB llc DATE: 1/22/2017 AIR TERMINAL TEST REPORT PAGE: PROJECT: HUGHES RESIDENCE SYSTEM: FC-1 / FC-2 NOTES: HVAC TAB llc DATE: 1/25/2017 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER CARRIER MODEL FV4CNF002L00ABAA SERIAL 1316A84491 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 1000CFM@0.25"ESP/ 700CFM MIN OSA CFM 200 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. 1/2 - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 208/230 4.3 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE DD MOTOR BORE DD FAN DRIVE DD FAN BORE DD NO. BELTS & SIZE DD ROTATION CORRECT CENTERLINE MOTOR ADJ PULLEY SPEED STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (HERTZ) NONE SET AT (HERTZ) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. DD DD VOLTAGE NA NA AMPERAGE NA NA PAGE: AIRFLOW DATA SUPPLY CFM 730 OSA CFM 191 RETURN CFM 539 PROJECT: HUGHES RESIDENCE SYSTEM: FC-3 DX COIL F I L T E R ATMOS 0.09" -0.11" HW COIL NOTES: HVAC TAB llc DATE: 1/20/2017 AIR AP PARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER CARRIER MODEL FV4CNF002 SERIAL 2415A84944 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 1000CFM@0.4"ESP/ 600CFM MIN OSA CFM 200 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. 1/2 - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 208/230 4.3 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE DD MOTOR BORE DD FAN DRIVE DD FAN BORE DD NO. BELTS & SIZE DD ROTATION CORRECT CENTERLINE MOTOR ADJ PULLEY SPEED STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (HERTZ) NONE SET AT (HERTZ) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. DD DD VOLTAGE NA NA AMPERAGE NA NA PAGE: AIRFLOW DATA SUPPLY CFM 579 OSA CFM 207 RETURN CFM 372 PROJECT: HUGHES RESIDENCE SYSTEM: FC-4 DX COIL F I L T E R ATMOS 0.16" -0.22" HW COIL NOTES: HVAC TAB llc DATE: 1/22/2017 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER CARRIER MODEL FV4CNF002 SERIAL 1316A84493 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 1200CFM@0.25"ESP/ 800 CFM MIN OSA CFM 200 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. 1/2 - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 208/230 4.3 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE DD MOTOR BORE DD FAN DRIVE DD FAN BORE DD NO. BELTS & SIZE DD ROTATION CORRECT CENTERLINE MOTOR ADJ PULLEY SPEED STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (HERTZ) NONE SET AT (HERTZ) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. DD DD VOLTAGE NA NA AMPERAGE NA NA PAGE: AIRFLOW DATA SUPPLY CFM 815 OSA CFM 196 RETURN CFM 619 PROJECT: HUGHES RESIDENCE SYSTEM: FC-5 DX COIL F I L T E R ATMOS 0.12" -0.16" HW COIL SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-3 1 SR 17/5 250 384 256 2 SR 17/5 150 275 161 3 SR 17/5 150 311 165 4 SR 9.25/9.25 150 295 148 700 1265 730 TOTAL FC-4 1 SR 18/6.5 150 108 154 2 SR 18/6.5 150 70 126 3 SR 17/5 300 235 299 600 413 579 TOTAL FC-5 1 SR 17/5 250 340 254 2 SR 13/13 250 476 243 3 SR 17/5 250 316 264 4 SR 9/3 50 611 54 800 1248 815 TOTAL NOTES: HVAC TAB llc DATE: 1/25/2017 AIR TERMINAL TEST REPORT PAGE: PROJECT: HUGHES RESIDENCE SYSTEM: FC-3 / FC-4 / FC-5 SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM EF-1 1 ER 8.5/8.5 50 67 67 TOTAL 2 ER 8.5/8.5 50 36 36 TOTAL 3 ER 8.5/8.5 50 65 65 TOTAL 4 ER 8.5/8.5 50 50 50 TOTAL 5 ER 8.5/8.5 50 53 53 TOTAL 6 ER 8.5/8.5 50 56 56 TOTAL 7 ER 8.5/8.5 50 57 57 TOTAL 8 ER 8.5/8.5 50 64 64 TOTAL 9 ER 8.5/8.5 50 58 58 TOTAL 10 ER 8.5/8.5 50 28 28 TOTAL 11 ER 8.5/8.5 50 61 61 TOTAL EF-2 1 ER 8.5/8.5 120 91 91 TOTAL 2 ER 8.5/8.5 120 142 142 TOTAL 3 ER 8.5/8.5 120 169 169 TOTAL 4 - - - - - - - - - DELETED 5 ER 8.5/8.5 120 174 174 TOTAL 6 ER 8.5/8.5 120 41 41 TOTAL EF-3 1 ER 10/10 200 235 235 TOTAL 2 ER 10/10 200 280 280 TOTAL 3 ER 10/10 200 232 232 TOTAL 4 ER 10/10 200 202 202 NOTES: HVAC TAB llc DATE: 1/23/2017 AIR TERMINAL TEST REPORT PAGE: PROJECT: HUGHES RESIDENCE SYSTEM: EF-1 / EF-2 / EF-3 HVAC TAB llc DATE: 1/25/2017 FLOW METER DESIGN MEASURED LOCATION TYPE SIZE DESIGN P DESIGN GPM FINAL P VALVE POSITION % OPEN FINAL GPM RFZ-1-1 UPONOR 3/4" 2 - - 2.0 RFZ-1-2 TA 3/4" 1 4.66 0.7 1.0 RFZ-1-3 UPONOR 3/4" 1.6 - - 1.6 RFZ-1-4A UPONOR 3/4" 0.7 - - 0.7 RFZ-1--4B UPONOR 3/4" 0.5 - - 0.5 RFZ-1-5A UPONOR 3/4" 0.7 - - 0.7 RFZ-1-5B UPONOR 3/4" 0.4 - - 0.4 RFZ-2-1 UPONOR 3/4" 1.0 - - 1.0 RFZ-2-2A UPONOR 3/4" 0.4 - - 0.4 RFZ-2-2B UPONOR 3/4" 0.3 - - 0.3 RFZ-2-3 UPONOR 3/4" 0.8 - - 0.8 RFZ-2-4A UPONOR 3/4" 1.0 - - 1.0 RFZ-2-4B UPONOR 3/4" 1.8 - - 1.8 RFZ-2-5 UPONOR 3/4" 0.8 - - 0.8 RFZ-3-1A UPONOR 3/4" 0.5 - - 0.5 RFZ-3-1B UPONOR 3/4" 0.5 - - 0.5 RFZ-3-1C UPONOR 3/4" 0.3 - - 0.3 RFZ-3-2 UPONOR 3/4" 1.0 - - 1.0 RFZ-3-3A UPONOR 3/4" 0.3 - - 0.3 RFZ-3-3B UPONOR 3/4" 0.6 - - 0.6 RFZ-3-3C UPONOR 3/4" 0.3 - - 0.3 RFZ-3-4A UPONOR 3/4" 0.5 - - 0.5 RFZ-3-4B UPONOR 3/4" 0.4 - - 0.4 RFZ-3-5A UPONOR 3/4" 0.9 - - 0.9 RFZ-3-5B UPONOR 3/4" 0.4 - - 0.4 BALANCE VALVE TEST REPORT PROJECT: HUGHES RESIDENCE SYSTEM: RFZ-1-1 - 3-5B PAGE: HVAC TAB llc DATE: 1/25/2017 FLOW METER DESIGN MEASURED LOCATION TYPE SIZE DESIGN P DESIGN GPM FINAL P VALVE POSITION % OPEN FINAL GPM SMZ-1 - - - 12 - - *2 SMZ-2 - - - 12 - - *2 SMZ-3 - - - 8 - - *2 SMZ-4 - - - 4 - - *2 SMZ-5 - - - 4 - - *2 SMZ-6 - - - 8 - - *2 SMZ-7 - - - 4 - - *2 SMZ-8 - - - 8 - - *2 SMZ-9 - - - 2 - - *2 FC-1 TA 3/4 5.0 10.0 2.15 5.03 FC-2 TA 3/4 5.0 9.13 2.20 5.01 FC-3 TA 3/4 3.0 11.0 1.50 3.01 FC-4 TA 3/4 3.0 9.27 1.55 3.03 FC-5 TA 3/4 3.0 7.98 1.63 3.00 BALANCE VALVE TEST REPORT PROJECT: HUGHES RESIDENCE PAGE: NOTES:*2 DENOTES NO CIRCUIT SETTER INSTALLED SYSTEM: SMZ-1-8 / FC-1-5 PAGE: SYSTEM: BL-1A / BL-1B PROJECT: HUGHES RESIDENCE PUMP IDENTIFICATION BL-1A BL-1B PUMP MANUFACTURER GRUNDFOS GRUNDFOS MODEL NUMBER TYPE UPS 26-99 FC UPS 26-99 FC SERIAL NUMBER PC 1438 PC 1345 RATING GPM RATING Ft. Hd. 30 GPM Ft. Hd. 30 GPM Ft. Hd. MOTOR MANUFACTURER - - MOTOR HP (KW) RPM - - - - PHASE FRAME 1 - 1 - S.F. TYPE - - - - VOLTS AMPS 115 1.3/1.5/1.8 115 1.3/1.5/1.8 STARTER MANUFACTURER NONE NONE MODEL NONE NONE SIZE NONE NONE RANGE NONE NONE SETTING (AMPS) NONE NONE REQUIRED THERMAL NONE NONE RATING AMPS NONE NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD. VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD. INDICATED/ACTUAL IMPELLER DIAMETER VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD. VALVE OPEN GPM *1 *1 DISCHARGE PRESSURE PSI/Ft.Hd P1 SUCTION PRESSURE PSI/Ft.Hd P2 P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD. SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD. P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD. GPM *1 (HI SPD) *1 (HI SPD) VOLTS NA NA AMPS NA NA HVAC TAB llc DATE: 1/25/2017 PUMP TEST REPORT PAGE: NOTES: NA DENOTES NO ACCESS *1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER SYSTEM: HWP-1A / HWP-1B PROJECT: HUGHES RESIDENCE PUMP IDENTIFICATION HWP-1A HWP-1B PUMP MANUFACTURER GRUNDFOS GRUNDFOS MODEL NUMBER TYPE MAGNA 3 40-180-F-216 MAGNA 3 40-180-F-216 SERIAL NUMBER 10001586 10001566 RATING GPM RATING F t. Hd. 30 GPM Ft. Hd. 30 GPM Ft. Hd. MOTOR MANUFACTURER - - MOTOR HP (KW) RPM - - - - PHASE FRAME 1 - 1 - S.F. TYPE - - - - VOLTS AMPS 208/230 0.18 / 2.61 208/230 0.18 / 2.61 STARTER MANUFACTURER NONE NONE MODEL NONE NONE SIZE NONE NONE RANGE NONE NONE SETTING (AMPS) NONE NONE REQUIRED THERMAL NONE NONE RATING AMPS NONE NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD. VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD. INDICATED/ACTUAL IMPELLER DIAMETER VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD. VALVE OPEN GPM *1 *1 DISCHARGE PRESSURE PSI/Ft.Hd P1 SUCTION PRESSURE PSI/Ft.Hd P2 P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD. SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD. P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD. GPM *1 *1 VOLTS NA NA AMPS NA NA HVAC TAB llc DATE: 1/25/2017 PUMP TEST REPORT PAGE: NOTES: NA DENOTES NO ACCESS *1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER SYSTEM: SMP-1 / DHWP-1 PROJECT: HUGHES RESIDENCE PUMP IDENTIFICATION SMP-1 DHWP-1 PUMP MANUFACTURER GRUNDFOS GRUNDFOS MODEL NUMBER TYPE MAGNA 3 65-150-F-340 ALPHA 15-55F/LC SERIAL NUMBER 10002839 PC 1536 RATING GPM RATING Ft. Hd. 45 GPM Ft. Hd. 5 GPM Ft. Hd. MOTOR MANUFACTURER - - MOTOR HP (KW) RPM - - - - PHASE FRAME 1 - 1 - S.F. TYPE - - - - VOLTS AMPS 208/230 0.30/5.68 115 - STARTER MANUFACTURER NONE NONE MODEL NONE NONE SIZE NONE NONE RANGE NONE NONE SETTING (AMPS) NONE NONE REQUIRED THERMAL NONE NONE RATING AMPS NONE NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD. VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD. INDICATED/ACTUAL IMPELLER DIAMETER VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD. VALVE OPEN GPM *1 *1 DISCHARGE PRESSURE PSI/Ft.Hd P1 SUCTION PRESSURE PSI/Ft.Hd P2 P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD. SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD. P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD. GPM *1 *1 VOLTS NA NA AMPS NA NA HVAC TAB llc DATE: 1/25/2017 PUMP TEST REPORT PAGE: NOTES: NA DENOTES NO ACCESS *1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER SYSTEM: WHCP-1A PROJECT: HUGHES RESIDENCE PUMP IDENTIFICATION WHCP-1A NOT USED PUMP MANUFACTURER GRUNDFOS MODEL NUMBER TYPE UPS 43-100 F SERIAL NUMBER PC 1627 RATING GPM RATING Ft. Hd. 14 GPM Ft. Hd. GPM Ft. Hd. MOTOR MANUFACTURER - MOTOR HP (KW) RPM - - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 115 2.5/3.1/3.5 STARTER MANUFACTURER NONE MODEL NONE SIZE NONE RANGE NONE SETTING (AMPS) NONE REQUIRED THERMAL NONE RATING AMPS NONE MEASURED PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD. VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD. INDICATED/ACTUAL IMPELLER DIAMETER VALVE OPEN DIFFERENTIAL PSI FT. HD. PSI FT. HD. VALVE OPEN GPM *1 DISCHARGE PRESSURE PSI/Ft.Hd P1 SUCTION PRESSURE PSI/Ft.Hd P2 P PSI / Ft. Hd. FINAL DISCHARGE PRESSURE PSI / Ft. Hd. P1 PSI FT. HD. PSI FT. HD. SUCTION PRESSURE PSI / Ft. Hd. P2 PSI FT. HD. PSI FT. HD. P PSI / Ft. Hd. PSI FT. HD. PSI FT. HD. GPM *1 (SPD-3) VOLTS NA AMPS NA HVAC TAB llc DATE: 1/25/2017 PUMP TEST REPORT PAGE: NOTES: NA DENOTES NO ACCESS *1 DENOTES NO PETES PLUGS / NO CIRCUIT SETTER