HomeMy WebLinkAboutB15-0252 TAB report.pdfNEBB Certi,fication #3235 TESTING, ADJUSTING AND BALANCING BUREAU THE PROf'ESSIONAL'S CHOICE .. JEDI Balancing, Inc. Certification !IBB009025C 568 Briggs Street (physical) P.O. Box 525 (mail) Erie. CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Testing, Adjusting & Balancing Certified Report Project Address Architect Mechanical Engineer Contractor TABB Certified Supervisors Date Job Number VAIL GOLF & NORDIC 1775 Sunburst Dr Vail, CO 81657 Unknown Unknown Climate Control Don Pittser & Bryan Hund & Daniel Pegues 11/18/2016 2016-7269 Instrumentation: Digital Manometer Flowhood Digital Pressure Gage Tachometer Digital Volt-Amp Meter Thermometer Method of Balancing: Alnor Balometer EBT-721 Alnor Balometer EBT-721 Alnor Hydronic Manometer HM-680 DT-36M Fluke 335 Alnor Balometer EBT-721 Supply, Return and Exhaust diffusers, grilles and registers were measured with an Alnor Balometer EBT-721. Heating and Chilled water flow rates were measured with an Alnor Hydronic Manometer HM-680 connected to the installed flow meters. Warranty Information: This project was completed according to NEBB Procedural Standards. The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for testing, adjusting, and balancing environmental systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test-Adjust-Balance Report Project Summary. If a Test-Adjust-Balance Report Project Summary is not issued directly following this cover page, all measurements met the design requirements as specified by the design mechanical engineer. This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date listed on this cover page. Don Pittser President NEBB Certified Professional TABB Certified Supervisor Abbreviation Index TAB: Testing, Adjusting & Balancing AHU: Air Handling Unit RTU: Roof Top Unit PACU: Packaged Air Conditioning Unit MAU: Make Up Air Unit FCU: Fan Coil Unit CRAC: Computer Room Air Conditioning Unit VAV: Variable Air Volume K Factor: Correction Factor FPB: Fan Powered Box AK: Area Correction Design D.P.: Design Differential Pressure Actual D.P.: Recorded Differential Pressure Ind.Imp.Dia. Indicated Impeller Diameter CUH: Cabinet Unit Heater UH: Unit Heater ERV: Energy Recovery Ventilator EF: Exhaust Fan KEF: Kitchen Exhaust Fan RF: Return Fan Diff.: Differential SPF: Stairwell Pressurization Fan SACU: Spilt Air Conditioner Unit TSP: Total Static Pressure ESP: External Static Pressure VP: Velocity Pressure SA: Supply Air RA: Return Air OSA: Outside Air OA: Outside Air MA: Mixed Air SD: Supply Diffuser CD: Ceiling Diffuser ER: Exhaust Register RG: Return Grille CFM: Cubic Feet Per Minute FPM: Feet Per Minute SSD: Square Supply Diffuser SRD: Square Return Diffuser TG: Transfer Grille Vs: Liters per Second mm: Millimeter kPa: Kilopascal Cx: Commissioning Motor FLA: Full Load Amperage S.F.: Service Factor OD: Outside Diameter P.F.: Power Factor Norn. Eff.: Nominal Efficiency RPM: Revolutions per Minute Tl: Terminal 1 T2: Terminal 2 T3: Terminal 3 PSI: Pounds per Square Inch TDH: Total Dynamic Head CS: Circuit Setter BV: Balance Valve Valve D.P.: Discharge Pressure Valve S.P.: Suction Pressure ERU: Energy Recovery Unit PEF: Power Exhaust Fan SF: Supply Fan TF: Transfer Fan SEF: Smoke Exhaust Fan DX: Direct Expansion SP: Static Pressure in. we: Inches Water Column HW: Heating Water CHW: Cooling Water CW: Condenser Water HX: Heat Exchanger SWD: Sidewall Diffuser EAT: Entering Air Temperature LAT: Leaving Air Temperature EWT: Entering Water Temperature LWT: Leaving Water Temperature MVD: Manual Volume Damper OBD: Opposed Blade Damper NAC: No Access NG: Not Given NIC: Not in Contract E: Existing cm: Centimeter M: Meter Pa: Pascal CMH: Cubic Meters per Hour GENERAL NOTES SEE ALL FIELD NOTES LOCATED BELOW EQlJIPMENT DAT A .lfiiLNCINc Table Of Contents PROJECT: VAIL GOLF & NORDIC LOCATION: VAIL, CO PROJECT#: 2016-7269 Table Of Contents ·-·~ til~1' .... #3 2 3 5 #BB009025C DATE: 11 /18/2016 CONTACT: Josh Cota 1 Air Handling Unit Rolling .............................................................................................................................................. . 1 . 1 AH-01 * F................................................................................................................................................................. 1 1.2 ERV-01.... ... ........ ......... ..... ......... ... . . . .......... .... . ... . ... . ..... ............ ..... ................... .. . . . ............. .......... .... ....... .... ..... ....... 3 1.3 F-01-0SA................................................................................................................................................................ 5 1.4 F-02* OSA........... ......... .. ............... ... .. .................... ... . . . .... ........ ..... ..... ... . . . . .. . . . .. . . . .. . . . .......... ......... .... .... ................ .... 6 1.5 F-03*....................................................................................................................................................................... 7 1.6 F-03*/ZD-01............................................................................................................................................................ 8 1.7 FC-01 F................................................................................................................................................................... 8 1.8 MAU-01... .... .. ... . . . .......... .......... .. . . . .......... ........................ ...... ......... ..... ........ ..... ......... ... .......... ....................... ..... .... . . 9 1.9 MAU-02................. ... ......... .... . . ......... .... . . ..... .......... .... ... . ... . . . ............... ......... .. . . . . .. . .... . . . .......... ....... ...... .... ....... .. . . ... . .. 10 2 Fan Unit Rolling............................................................................................................................................................ 11 2.1 EF-01....................... .......... ... .. ............... ..... .......... ... . . .. . . ... . . . ..... .. .. .. . . . .............. ... . . . . . . . . .......... ....... .. ... . . ... . ....... .... .. . . . 11 2.2 EF-02.... ... . ... . . ........ ...... ... .. . ............... .......... .... . .... . .. . . ... ...... ...... ....... .. ... . . . .. . . . .. . . . . . . . . ... . . ........ .. ............ ..... ........ ... . ... . . 12 2.3 EF-03...... ...... ....... ......... .. .. . ......... ... . . . .......... .... . ... . . ... . ... ..... ....... ......... ... . . . .. . . . . .. . . .. . . . . . . . . ..... ......... ..................... ... . ... . . 13 2.4 EF-04...................................................................................................................................................................... 13 2.5 EF-05-01................. ....... ....... ......... ....... ...... ..... ............................ ............. .. .. . . ... .......... ....... .. . . . ....... ............. .. . ........ 14 2.6 EF-05-02.......... ....... .... ........... ............... ....... ...... ... . .... ........... ....... ....... ... ............ .......... ... ........ ......... ..... ....... ... ........ 14 2.7 EF-05-03................................................................................................................................................................. 15 2.8 EF-05-04. ... ........ ....... .. . ......... ... . . . ........ .... . ... . . . .. .. . .. . ................. ....... ........ ..... ..... ... . . ......... ... .. .......... ..... ... . ... .......... .... 15 2.9 EF-05-05................................................................................................................................................................. 16 2.10 EF-05-06.......... ... . ..... . . .......... ... . ......... ... ........... ....... ..... ....... .. ... . . . ........ .. ..... ... . . ......... ..... ......... ......... ........... ........... 16 2.11 EF-06-01............................................................................................................................................................... 17 2.12 EF-06-02. ..... .......... .......... ... . . .......... ... . ..... .......... ..... ... . ...... ......... ... . . . ......... ... . .... ....... ..... .......... ................. ...... ....... 17 2.13 EF-06-03............................................................................................................................................................... 18 2.14 EF-06-04............................................................................................................................................................... 18 2.15 EF-06-05................ .............. ........ .... . . . ....... ..... ............. ............... ..... ..... ................. ........ ... . ...... ................. ......... ... 19 2.16EF-07.................................................................................................................................................................... 19 3 Hydronic Pump Rolling................................................................................................................................................. 20 3.1 P-01 BOILER.......................................................................................................................................................... 20 3.2 P-02 BOILER.......................................................................................................................................................... 20 3.3 P-03 HW GEN......................................................................................................................................................... 21 3.4 P-04 HEATING SYS............................................................................................................................................... 22 3.5 P-05 SNOWMEL T PRIMARY................................................................................................................................. 23 3.6 P-06 SNOWMEL T SECONDARY........................................................................................................................... 23 JEDI Balancing, Inc. 1/ifLNcnvc Air Handling Unit PROJECT: LOCATION: PROJECT#: VAIL GOLF & NORDIC VAIL, CO 2016-7269 SYSTEM/UNIT: AH-01* F Unit Manufacturer Unit Model Number Unit Serial Number Total CFM Design Design SP DAIKIN LAH020ADH SLPD160200104 10380 CFM Outside Air CFM Design Total Connected CFM 0.8 in. WC 2030 CFM 10380 CFM Starter Data AH-01* F/Suoo!y Fan Starter Manufacturer Starter Model No. Starter Size Installed Thermal Rating (Amps) Required Amps Total CFM Actual AH-01* F/Sypply Fan Fan RPM Actual Motor Volts 1 Motor Volts 2 Motor Volts 3 Motor Amps 1 Motor Amps 2 Motor Amps 3 Log: AH-01* F AH-01* F JEDI Balancing, Inc. SCHNEIDER LRD 32 ADJUSTABLE 23-32 32 29 Test Data' 10370 1600 211 213 213 20.3 22.2 23.9 10/19/2016 10/20/2016 Luke Scaggs Luke Scaggs NiFfi .. #3 2 3 5 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 11/8/2016 AH-01* F/Sypply Fan Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Nominal Efficiency Power Factor · .. . .. AH-01* F/Supply Fan Motor Sheave Model Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Motor Data , BALDOR 10 1770 215T 200 3 29.5 1.15 91.7 82 Sheave Data .·.. · ...• 1VP75 1 3/8 in. BK85 7/8 in. 1 BX62 .. Jest Pressures ; Filter SP In Filter SP Out Heat. Coil SP In Heat. Coil SP Out Cool. Coil SP In Cool. Coil SP Out Fan SP In Fan SP Out -0.60 in. WC -0.73 in. WC -0.73 in. WC NO ACCESS in. wc NO ACCESS in. wc -1.13 in. WC -1.13 in. WC 0.33 in. WC OUTLETS 11 & 12 DELETED, CFM VALUES ADDED TO OUTLET 13 AFTER PROPORTIONING OUTLET 5 IS WHISTLING, CLOSING OBD MAKES IT WORSE. OPENING TO GET RID OF WHISTLE LEAVES OUTLET AROUND 165% OF DESIGN AIRFLOW AND OTHER OUTLETS SHORT. Page 1of23 .lf;~CJNG Nl~.,. #3 2 3 5 #BB009025C Air Handling Unit PROJECT: DATE: 11/18/2016 LOCATION: VAIL GOLF & NORDIC VAIL, CO CONTACT: Josh Cota PROJECT#: 2016-7269 AH-01* F Supply Outlet Summary ~!:~Outlet> .. Fac.~~~ai A!< Factor Design Prellm. , .. "(o.Pr!itlim, ,· ... F111a11n•·····• o/o Final. •• i'vt.e;· ''Readina' Reaclina 'Deviation Readln •·• Devlatidn Outlet-01 SD 775 580 75 755 97 Outlet-02 SD 775 400 52 745 96 Outlet-03 SD 1210 875 72 1155 95 Outlet-04 SD 1210 1210 100 1260 104 Outlet-05 SD 775 780 101 815 105 Outlet-06 SD 775 965 125 780 101 Outlet-07 SD 580 775 134 620 107 Outlet-08 SD 580 725 125 555 96 Outlet-09 SD 580 720 124 555 96 Outlet-10 SD 580 820 141 555 96 Outlet-13 SD 1890 1355 72 1890 100 Outlet-14 SD 315 210 67 345 110 Outlet-15 SD 335 255 76 340 101 '.: ,];qJal.,1~;~.!' ••; ·.i ~.'ctd..Ai -' . ' i 10380 9670 ,;,,, ,93 .·· 10370 .•..... ,, '' 100 ',,.,, •• AH-01* F Return Inlet Summary ~:-::i-i::F7ac~e~·· . ..,.-:;TN'°:.7pe~o~fn---..~-"T-;-r.;:::":'l~-r".'!!";;~~::"'.T-.ro;:;-::::"l'l'=:-r-:".'";;';'::~!"':"'.'l"'."ll7'."'lrr.~M ~·•Area Readina A!< Ii. Design/;•!• ·•·Pf~lim •i ,% Pr~lim ·' · Fi~j~'!~::li!tl ~. Fln~!ii1: Factor Read Ina Rea!lina'' 'Deviation Readln Devlatfon lnlet-01 RG 260 lnlet-02 RG 3920 lnlet-03 RG 3920 lnlet-04 RG 2780 lnlet-05 RG 3040 lnlet-06 RG 2020 lnlet-07 RG 840 lnlet-08 RG 835 lnlet-09 RG 840 lnlet-10 RG 2515 ! I ':•~:JOtillJfi~'l.!:1:::p ''"''"''"' .•. ,.,., .... .. '' 20970 ··.·.·O 0 , ~:·::;!:~i:i:;::·,.O ,,:'0{ .1! JEDI Balancing, Inc. Page 2 of 23 .lfifLNCINc Air Handling Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: ERV-01 Unit Manufacturer Total CFM Design Design SP Outside Air CFM Design Total Connected CFM Return Fan CFM Design Return Fan Design SP Connected Return CFM Unit Data RENEWAi RE 1005 CFM 0.4 in. WC 1265 CFM 1005 CFM 805 CFM 0.4 in. WC 900 CFM startel'.Data Starter Size Installed Thermal Rating (Amps) Required Thermals ERV-01/Sypply Fan Starter Manufacturer Starter Model No. Starter Size Installed Thermal Rating (Amps) Required Thermals "h' ' . 11i!:.:<;.,< '': •:, ':'[:;,• ;:~: >0!, "::m.t~• <";' ''l:'j:,!!il / I Total CFM Actual Outside Air CFM Actual Return Air CFM Actual Exhaust Air CFM Actual Efil'.-!!1lB!lluCD Ei!D Fan RPM Actual Motor Volts 1 Motor Volts 2 Motor Volts 3 Motor Amps 1 Motor Amps 2 Motor Amps 3 EB~-!!1rauoPlv Ei!D Fan RPM Actual Motor Volts 1 Motor Volts 2 Motor Volts 3 Motor Amps 1 Motor Amps 2 Motor Amps 3 JEDI Balancing, Inc. C3 S0910E ADJUSTABLE 4-6.3 16 5 C3 S0910E ADJUSTABLE 4-6.3 16 5 Test Data .. · 1035 1035 930 930 1210 213 214 214 2.7 2.6 2.9 1355 213 214 214 2.6 2.5 2.8 ·· .. ~:@1.a #3 2 3 5 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 11/8/2016 Efil'.-!!1lBi:lurn Ei!D Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Nominal Efficiency Power Factor Efil'.-!!ll~IH!Pllo! Ei!D Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Nominal Efficiency Power Factor ,' ERV-!!1/Ri:lurn Fi!a Motor Sheave Model Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Sheave Center Line liifil'.-!!ll~YPPllo! Ei!D Motor Sheave Model Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Sheave Center Line Pre Filter In Pre Filter Out Filter SP In Filter SP Out Fan SP In Fan SP Out Return Fan SP In Return Fan SP Out ""'' ,· ', Motor Data, i ,, BALDOR 1.5 1760 145T 230/460 3 4.4/2.2 1.15 86.5 73 BALDOR 1.5 1760 145T 230/460 3 4.4/2.2 1.15 86.5 73 ·., Sheav:e Data VL40 718 in. AK46 1 in. 1 A37 131/4in. VL40 718 in. AK46 1 in. 1 A37 131/4 in. -0.39 in. WC • 0.87 in. WC -0.42 in. WC -0.95 in. WC -0.95 in. WC 0.1 in. WC -0.87 in. WC 0.28 in. WC •\,.,:.,: .. '•'''', ,, ,: ,: Page 3 of 23 lj~CJNG ril~J .. #3 2 3 5 #BB009025C Air Handling Unit PROJECT: LOCATION: PROJECT#: VAIL GOLF & NORDIC VAIL, CO 2016-7269 SYSTEM/UNIT: ERV-01 Log: I ERV-01 11 /8/2016 ERV-01 Supply Outlet Summary Luke Scaggs ~)'~Je~ 1 putlt!•··•·· '· •• ,,. . ..1·,::. ;'J'vne····. Face Area AK Factor De15lgn ... ' ,•' ' ,, ~+ . i ,, .. ·· Read Ina FC-01 OA 35 Outlet-01 SD 30 Outlet-02 SD 40 Outlet-03 SD 20 Outlet-04 SD 60 Outlet-05 SD 30 Outlet-06 SD 50 Outlet-07 SD 35 Outlet-08 SD 205 Outlet-09 SD 75 Outlet-10 SD 200 Outlet-11 SD 75 Outlet-12 SD 75 Outlet-13 SD 75 .. ~'!l9~1.~1''·~ ... :. ·;!iji!.!i:•: ,.,,.1,/ /'' . ;,,,,,.,,,;,,:,,,; •, -1005 ERV-01 Return Inlet Summary ~~~.n~~,J~~e FaCIJ, ,Type e>f AK :'Design l·!l1r .. ;1:1:IP,;::·f \"'•~j;t•,'',.; .. 1::.,',!''"i Area Reading Factor '.Readlria lnlet-01 RG 115 lnlet-02 RG 110 lnlet-03 RG 175 lnlet-04 RG 120 lnlet-05 RG 70 lnlet-06 RG 30 lnlet-07 RG 120 lnlet-08 RG 70 lnlet-09 RG 30 lnlet-10 RG 30 lnlet-11 RG 30 ~~'.~:.~:;·:::lQtals·~~~~i~,,~::} 1.: .•::. ·-»~·"•:"" i . , •. ,,' '1: ... -. ,. 900 JEDI Balancing, Inc. DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 11/8/2016 NO UNIT TAG VISIBLE .Prelim · ... %i Pffl'!!h · Final ... 0k Final Readlna Deviation ReaCifna ·· Deviation 35 100 35 100 65 217 30 100 95 238 40 100 55 275 20 100 105 175 65 108 60 200 30 100 105 210 55 110 105 300 35 100 240 117 220 107 110 147 80 107 110 55 190 95 100 133 80 107 130 173 75 100 110 147 80 107 1425 142 1035 ' 103 >Prelim NoPrelim ,,:,>.Final, o/OA.palj1 Reading Deviation Reading Deviation 130 113 120 104 120 109 115 105 150 86 180 103 145 121 115 96 100 143 75 107 65 217 30 100 90 75 130 108 85 121 75 107 15 50 30 100 30 100 30 100 45 150 30 100 975 108 : : 930 . 103 Page 4 of23 lfiifANCJNc Air Handling Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: F-01-0SA Unit Manufacturer Unit Model Number Unit Serial Number Total CFM Design Design SP Outside Air CFM Design Total Connected CFM MODINE DFP125SMRNN40D2 0917091616-9083 1390 CFM 0.8 in. WC 565 CFM 1390 CFM Starter Data Starter Size Rating (Amps) Required Amps Motor Volts 2 Motor Volts 3 Motor Amps 1 Motor Amps 2 Motor Amps 3 SCHNEIDER LC1 D09 ADJUSTABLE 2.5-4 2.5 Test Data:·•.··· 1100 214 216 215 1.75 1.8 1.7 Face Area , AK Factor Design · Readln 105 100 Outlet-03 SD 395 Outlet-04 SD 395 395 535 455 610 1390 ' 1965·.' JEDI Balancing, Inc. Deslgnt Readin 1390 1390 Hi:@»"IB #3 2 3 5 #B8009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 10/20/2016 F-01-0SA/Supply Fan Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Nominal Efficiency Power Factor F-01-0SA/Supply Fan Motor Sheave Model Motor Sheave Bore Fan Sheave Model Fan Sheave Bore MARATHON 0.75 1725 56H 230/460 3 2.5/1.25 1.25 81.1 71.1 1VL40 518 in. AK44 3/4 in. Test Pressures Filter SP In Filter SP Out Heat. Coil SP In Heat. Coil SP Out Cool. Coil SP In Cool. Coil SP Out Fan SP In Fan SP Out ,,%1'.'relim Deviation 167 190 135 115 154 141 . ~inlll RaaC11n 110 110 430 430 425 1505 ' -0.24 in. we -0.28 in. WC 0.22 in. WC 0.32 in. WC 0.32 in. we 0.25 in. WC -0.28 in. we 0.22 in. WC .· n.% f'lnal Deviation 105 110 109 109 108 108 '•r··''"•·· Final '~ Readin %Final Devlatio''n 0 Page 5 of 23 ··' .lfj!iLJVCINc Air Handling Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: F-02* OSA Unit Manufacturer Unit Model Number Unit Serial Number Total CFM Design Design SP Outside Air CFM Design Total Connected CFM DFP350SMRNN40D2 0917091616-9084 4820 CFM 0.8 in. WC 525 CFM 4800 CFM Starter Data SCHNEIDER LC1 D18 Starter Size ADJUSTABLE Rating (Amps) 12-18 Required Amps 16 Thermal Set At 16 . ;c Test Data· Total CFM Actual 5120 F-02* OSA/Sypply Fan Fan RPM Actual 1400 Motor Volts 1 Motor Volts 2 Motor Volts 3 Motor Amps 1 Motor Amps 2 Motor Amps 3 213 212 213 13.3 14.3 13.3 F-02* OSA Supply Outlet Summary .. ~Y•~!l'f.1Ji1ii: F.O!:l:yet~t ·''.:Face .. Area: A,K Factor 1.: "',1.:·':··.f.::'.~11!{R:i<<a: ;'i) ..• iv·na.'1';.~ ,_ • •• ,; •••• ,:' ,,ki: Outlet-01 SD Outlet-02 SD Outlet-03 SD Outlet-04 SD 960 960 960 Outlet-05 SD ''".Totals)l:!:i:1:i:i11•i•!,r <,::11:1:::::•:•::::·~ hs • '·<:''' ' . 960 4800 ,~t\K Desl9n Factor Readln 1600 1620 1600 940 1220 1280 1200 : .. 5875J rk~t_. #3235 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 10/20/2016 F-02* OSA/Sypply Fan Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Nominal Efficiency Power Factor F-02* OSA/Supply Fan MARATHON 5 1755 184T 200 3 15.6 1.15 87.5 81.1 Motor Sheave Model VP56 Motor Sheave Bore 1 1/8 in. Fan Sheave Model AK64 Fan Sheave Bore 1 in . Number of Belts 1 Belt Size A4 7 Sheave Center Line 15 1/4 in. ' Test l:'ressures :,::, Filter SP In Filter SP Out Heat. Coil SP In Heat. Coil SP Out Cool. Coil SP In Cool. Coil SP Out Fan SP In Fan SP Out 98 127 133 125 ·:· ,., 122 '• 1005 1020 1045 1035 ·•'i·i'··'·•512o,· ,,, -0.33 in. WC -0.53 in. we 0.24 in. WC 0.65 in. WC 0.65 in. WC 0.55 in. WC -0.53 in. WC 0.24 in. WC 105 106 109 108 1011.i.1: llf' ".%\.Prelim • Flnal·1::111::,,:11:::;1: ,,),~ Fln~I·' Deviation , ReaClln Deviation .;:•:,,, ',• 4820 o. '·•,1:0 .. ::::::•;· JEDI Balancing, Inc. Page 6 of 23 • lfi!ifurCJNc Ni_@i.a #3 2 3 5 #BB009025C Air Handling Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: F-03* Unit Manufacturer Unit Model Number Unit Serial Number Total CFM Design Design SP Outside Air CFM Design Total Connected CFM unit Data MODINE DFP175SMLNN40D2 0917091616-9085 1555 CFM 0.8 in. WC 870 CFM 1555 CFM Starter Data F-03*/Supoly Fan Starter Manufacturer Starter Model No. Starter Size Rating (Amps) Thermal Set At Motor Volts 1 Motor Volts 2 Motor Volts 3 Motor Amps 1 Motor Amps 2 Motor Amps 3 SCHNEIDER LC1 D09 ADJUSTABLE 2.5-4 3.2 Test Data';. 1430 213 214 214 1.8 1.7 1.8 Log: F-03* 11/9/2016 Luke Scaggs F-03* Supply Outlet Summary ~l~,9utrat•• .Face Area AK Factor. Design "'1!·11'.vPe. · ,·,':f.,.,1: ; ·::,:i<~ ::r{~:;J''J~-::~~;,,, Readina Outlet-01 SD 130 Outlet-02 SD 130 Outlet-03 SD 125 Outlet-04 SD 120 Outlet-05 SD 120 Outlet-06 SD 50 Outlet-07 SD 100 Outlet-08 SD 100 Outlet-09 SD 150 J"pfal,t;: g; . ,,,."'; ~,,. : . 1025 F-03* Return Inlet Summary 11 DATE: CONTACT: 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 10/14/2016 . ' .· F-03*/Sypply Fan Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Motor Data,, ·· ..•. · MARATHON 0.75 1725 56H 230/460 3 2.5/1.25 1.25 Nominal Efficiency 81.1 Power Factor 71.1 SheJVe Data F-03*/Supply Fan Motor Sheave Model VP40 Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Sheave Center Line 5/8 in. 0.D. 4 1/2 314 in. 1 A34 12 in. OUTLET 5 MISSING GRILLE, NO WAY TO RESTRICT AIRFLOW TO BRING IN DESIGN FLOW. Prell mi; Readln~' %Prelim • :· Final "lo Final:,,:. Deviation Riladlna 'o~v1at1on 125 96 95 73 105 81 90 69 150 120 95 76 235 196 140 117 140 117 165 138 70 140 80 160 120 120 95 95 115 115 85 85 180 120 135 90 1240 ·, 121 1: ·.980 · .. 96 . . :' Oi!~lefTYPe ~1!,F=a~, .. ,i: ·Typ8.of , ·•·A~,:, 1;i1Deflgn,; Prelim ,,, ·:.··%,,erellm1:1, ,,,·,1,1::'~:•filnal ··~•jf!Pll-!.: ;:;;w··•,:, ' .!:Area11!:11' Readlri Factor'' •"·Readin ·;.. Readin ·' :11111:~&~1atloh )Readlrl Deviation RG 1~ 1170 260 .... 1555 0 ' ...... Q 0 0 JEDI Balancing, Inc. Page 7 of 23 .l/iifANCJNc ~J:EIJ.,. #3 2 3 5 #BB009025C Air Handling Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: F-03*/ZD-01 ·· ···· ·· 'Test Data .• 530 CFM F-03*/ZD-01 Supply Outlet Summary Face Area>< AK Factor . ··<·; c.; : .. Outlet-01 SD Outlet-02 SD Outlet-03 SD SYSTEM/UNIT: FC-01 F Unit Data Unit Manufacturer Unit Model Number Unit Serial Number Total CFM Design Design SP Outside Air CFM Design Total Connected CFM FCU160421-04 6EDM005410 555 CFM 0.5 in. WC 35CFM 555 CFM Design Read Ina 165 165 200 530 THERMALLY PROTECTED Total CFM Actual 535 Outside Air CFM Actual 40 Return Air CFM Actual 495 OA Damper Pos 10 % FC-01 F/Sypply Fan Fan RPM Actual DIRECT DRIVE log: FC-01 F 10/18/2016 Luke Scaggs FC-01 F Supply Outlet Summary .·s~., :\.{:-- JEDI Balancing, Inc. Prelif1l.1.,.. , ' % .Prelim Readina ·· Deviation DATE: CONTACT: 11/18/2016 Josh Cota ·+Flm~V %.Final · Readina , Deviation 90 55 105 64 75 38 270 :,' .. 51 0 0 Tested By: Luke Scaggs Date: 10/18/2016 FC-01 F/Supply Fan Motor Manufacturer Motor HP Motor RPM Motor Rated Volts Motor Phase Motor FL Amps FC-01 F/Sypply Fan Motor Sheave Model FASCO 1/6 1350-1200-1000 208-230 0.9 Sheave. Data · DIRECT DRIVE OSA SET AND MARKED WITH BLACK MARKER, MISSING ACTUATOR FOR DAMPER. Page 8 of 23 .l/iifANCJNc Air Handling Unit PROJECT: VAIL GOLF & NORDIC LOCATION: VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: MAU-01 Unit Data: Unit Manufacturer Unit Model Number Unit Serial Number Total CFM Design Design SP CAPTIVE AIRE A1-D.250-G10 Outside Air CFM Design Total Connected CFM log: MAU-01 MAU-01 JEDI Balancing, Inc. 2658967-4 1354 CFM 0.5 in. WC 1354 CFM 1354 CFM 11/14/2016 11/14/2016 1.:. Luke Scaggs Luke Scaggs Design. Read in 677 677 '.1354 .0 rUj!iJ1111B #3 2 3 5 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 11/8/2016 Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Nominal Efficiency Power Factor MAU-01/Supply Fan Motor Sheave Model Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Sheave Center Line MOTOR RUNNING BACKWARDS WEG 1760 56H 208-230/460 3 3.47-3.14/1.57 1.15 83.5 72 1VL40 5/8 in. AK54 3/4 in. 1 AX38 13 3/8 in. MOTOR RUNNING BACKWARDS, TRIED SWAPPING LEADS. NO CHANGE. % Prelli:r!,':,. Final t,;, % Fln<1l Deviation • R'e~(l1il · Deviation 0' 0 0 Page 9 of 23 .lfi~CING Air Handling Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: MAU-02 UnltDf~· Unit Manufacturer Unit Model Number Unit Serial Number Total CFM Design Design SP Outside Air CFM Design Total Connected CFM CAPTIVE AIRE A2-D.500-G15 2658967-5 2650 CFM 0.5 in. WC 2650 CFM 2650 CFM Starter Data LENZE VFD Total CFM Actual 2465 Outside Air CFM Actual 2465 MA!.1::!!2~1.!ooll! Eil!l Fan RPM Actual 905 Motor Volts 1 211 Motor Volts 2 212 Motor Volts 3 213 Motor Amps 1 3.1 Motor Amps 2 3.1 Motor Amps 3 2.3 JEDI Balancing, Inc. ~~~ ... #3 2 3 5 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 11/14/2016 MA!.1::!!2/Suooll! Ean Motor Manufacturer Motor HP Motor RPM Motor Frame Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Nominal Efficiency Power Factor MAU::!!2/S1,1pplJ! Eaa Motor Data,,;, WEG 1.5 1760 56H 208-230/460 3 4.64-4.2/2.1 1.15 86.5 76 Sheave Data' Motor Sheave Model VL40 Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Sheave Center Line 5/8 in. AK66 1 in. 1 AX48 17 1/8 in. Page 10 of 23 .lfiifANCINc Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-01 Fan Serial Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Volts 2 Actual Motor Volts 3 Actual Motor Amps 1 Actual Motor Amps 2 Actual Motor Amps 3 Actual Log: EF-01 JEDI Balancing, Inc. Unit Data CAPTIVE AIRE USBl15BD-RM 2658967-1 1575 1.5 in. WC 1575 Starter.Data LENZE VFD Test Data 1595 1730 211 210 211 3.5 3.6 3.5 11/14/2016 Luke Scaggs Ni~!'~ #3 2 3 5 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 11/14/2016 Motor Data Motor Manufacturer WEG Motor HP 1.5 Motor RPM 1760 Motor Rated Volts 208-230/460 Motor Phase 3 Motor FL Amps 4.64-4.2/2.1 Motor Service Factor 1.15 Motor Frame 56H Nominal Efficiency 86.5 % Power Factor 76 ··· SMavfl Data '· ·· Motor Sheave Model 1VL40 Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size 5/8 in. AK32H 1 in. 1 AX41 in. · ... Test Pressures .· .. . . .. Fan SP In Actual Fan SP Out Actual NO ACCESS in. we ATMOSPHERE in. we READING INLET VELOCITY AT GREASE FILTERS, 78" x 18" = 9.75 s ft x 182 f m x 0.9 AREA CORRECTION FOR GREASE FILTERS Page 11 of 23 lfj!lfuvCINc Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-02 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Volts 2 Actual Motor Volts 3 Actual Motor Amps 1 Actual Motor Amps 2 Actual Motor Amps 3 Actual Log: EF-02 JEDI Balancing, Inc. untt'.Data CAPTIVE AIRE USBl18BD-RM 2658967-2 2704 1.5 in. WC 2704 LENZE VFD Test Data 2955 1730 203 204 204 4.35 4.23 4.2 11/14/2016 Luke Scaggs H~@B .... #3235 #BB009025C DATE: CONTACT: 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 11/14/2016 . Motor Data" Motor Manufacturer WEG Motor HP 3 Motor RPM 1735 Motor Rated Volts 208-230/460 Motor Phase 3 Motor FL Amps 8.78-7 .94/3.97 Motor Service Factor 1.15 Motor Frame 56HZ Nominal Efficiency 86.9% Power Factor 80 . . Sheave Data · .· Motor Sheave Model 2VL42 Motor Sheave Bore 718 in. Fan Sheave Model 2BK45H Fan Sheave Bore 718 Hin. Number of Belts 2 Belt Size BX44 in. Sheave Center Line 17 in. · .. Test Pressuretf' .... ·. ' Fan SP In Actual Fan SP Out Actual NO ACCESS in. wc ATMOSPHERE in. wc READ INTAKE VELOCITY AT GREASE FILTERS, 109" x 18" = 13.625 s ft x 0.90 AREA CORRECTION x 241 f m Page 12 of 23 ·. l!iJlLwCJNc Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-03 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Unit Data ' CAPTIVE AIRE USBl11 BO-RM 2658967-3 600 0.5 in. WC 600 Starter Data LENZEVFD Test Data 655 Fan RPM Actual 1475 Motor Volts 1 Actual 211 Motor Volts 2 Actual 210 Motor Volts 3 Actual 212 Motor Amps 1 Actual 3.6 Motor Amps 2 Actual 3.8 Motor Amps 3 Actual 3.7 SYSTEM/UNIT: EF-04 Fan Manufacturer Fan Model Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Volts 2 Actual Motor Volts 3 Actual Motor Amps 1 Actual Motor Amps 2 Actual Motor Amps 3 Actual JEDI Balancing, Inc. Unit Data COOK 30XMW 4800 0.25 in. WC 4800 1038 211 213 212 2.5 2.4 2.55 ~:i"@»"IB DATE: CONTACT: #3235 #BB009025C 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 11/14/2016 Motor Manufacturer Motor HP Motor RPM Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Motor Frame Nominal Efficiency Power Factor Motor Data t: , , WEG 1/2 1765 208-230/460 3 1.9-1.72/0.86 1.25 56 78.2 % 69 .. ··· , > ..... Sheave Data Motor Sheave Model 1VL40 Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Sheave Center Line 5/8 in. AK39 1 in. 1 AX30 in. 11 in. Fan SP In Actual NO ACCESS in. wc Fan SP Out Actual ATMOSPHERE in. wc Tested By: Luke Scaggs Date: 11 /9/2016 Motor Manufacturer Motor HP Motor RPM Motor Rated Volts Motor Phase Motor FL Amps Motor Service Factor Motor Frame Motor Sheave Bore Fan Sheave Model Fan Sheave Bore Number of Belts Belt Size Fan SP In Actual Fan SP Out Actual MARATHON 3/4 1725 208-230/460 3 2.6-2.8/1.4 1.25 56 SheaveDaia ':,.'.;,:; ·· VL34 5/8 in. AK82 1 in. 1 A50 in. NO ACCESS in. wc Page 13 of 23 ·1/i~CING Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-05-01 UnltDatac Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM FV-05VQ5 404 75 0.1 in. WC 75 ' Starter .. Data ·. Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual THERMALLY PROTECTED 65 DIRECT DRIVE 121 0.05 SYSTEM/UNIT: EF-05-02 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual JEDI Balancing, Inc. Unit Data PANASONIC FV-05VQ5 501 75 0.1 in. we 75 Teet.Data 80 DIRECT DRIVE 121 0.05 Hij@.1 .. #3 2 3 5 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts 115 Motor Phase Motor FL Amps 0.09 Sheavepata Te$t Pre$$uree ".· ·.....•• " : .":. Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Motor Sheave Model Motor Data /. FACTORY INSTALL 115 0.09 Sheave .. Da~ \ ,, DIRECT DRIVE , THt Pressure's' Fan SP In Actual Fan SP Out Actual Page 14 of 23 'J~..I. • Tli'TlT BALANCING Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-05-03 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual unit oata PANASONIC FV-05VQ5 501 75 0.1 in. WC 75 THERMALLY PROTECTED :test Data 80 DIRECT DRIVE 121 0.05 SYSTEM/UNIT: EF-05-04 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual JEDI Balancing, Inc. Unit Data PANASONIC FV-05VQ5 501 75 0.1 in. WC 75 TestDa.~. 70 DIRECT DRIVE 121 0.05 Ni~J .... #3 2 3 5 #88009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Fan SP In Actual Fan SP Out Actual Motor Data , : FACTORY INSTALL 115 1 0.09 Test•·'Pressures ATMOSPHERE in. wc NO ACCESS in. wc Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Motor Sheave Model Fan SP In Actual Fan SP Out Actual 115 1 0.09 NO ACCESS in. wc Page 15 of 23 ,: • .l//ifANCJNc Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-05-05 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Unit Data PANASONIC FV-05VQ5 501 75 Total SP Design 0.1 in. we Total Connected CFM 75 Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual Starter: Data Test Data 70 DIRECT DRIVE 121 0.05 SYSTEM/UNIT: EF-05-06 Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual JEDI Balancing, Inc. ·Unit Da~i '' , ·, PANASONIC FV-05VQ5 501 75 0.1 in. we 75 S~r;ter .. Data.· •. · THERMALLY PROTECTED restData• 68 DIRECT DRIVE 121 0.05 NiY.1 .... #3 2 3 5 #88009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 10/18/2016 ,··.•~otor·Data Motor Manufacturer Motor Rated Volts 115 Motor Phase Motor FL Amps 0.09 Motor Sheave Model DIRECT DRIVE ., i: Test Pressures , , ,: ,,, .· Fan SP In Actual ATMOSPHERE in. we Fan SP Out Actual NO ACCESS in. we Tested By: Luke Scaggs Date: 10/18/2016 '•, : Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Fan SP In Actual Fan SP Out Actual .·Motor Data f FACTORY INSTALL 115 1 0.09 Sheave Oat~'{· rest Pressu'res · NO ACCESS in. we Page 16 of 23 ~CJNG Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-06-01 Unit Data Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual SYSTEM/UNIT: EF-06-02 PANASONIC FV-30VQ3 501 260 0.25 in. we 260 DIRECT DRIVE 122 0.49 Unit Data Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM PANASONIC FV-30VQ3 602 260 0.25 in. we 260 DATE: CONTACT: Hi~J"IB #3 2 3 5 #8B009025C 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Fan SP In Actual Fan SP Out Actual 120 1 0.61 'Sheave Data DIRECT DRIVE ATMOSPHERE in. we NO ACCESS in. we Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Motor .. ~Illa· 120 0.61 Starter Manufacturer THERMALLY PROTECTED Tesf~re$$.ifr~!I Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual JEDI Balancing, Inc. DIRECT DRIVE 122 0.39 Fan SP In Actual Fan SP Out Actual NO ACCESS in. we Page 17 of 23 .IJ~CING Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-06-03 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual Log: EF-06-03 EF-06-03 U~lt Data PANASONIC FV-30VQ3 512 260 0.25 in. WC 260 Sta.rter Oat!- THERMALLY PROTECTED Test Data 340 DIRECT DRIVE 122 0.45 10/18/2016 Luke Scaggs 10/18/2016 Luke Scaggs SYSTEM/UNIT: EF-06-04 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual Log: EF-06-04 EF-06-04 JEDI Balancing, Inc. Unl~pata~ PANASONIC FV-30VQ3 410 260 0.25 in. WC 260 320 DIRECT DRIVE 121 0.43 10/18/2016 Luke Scaggs 10/18/2016 Luke Scaggs NI~~ ... #3 2 3 5 #BB009025C DATE: 11/18/2016 CONTACT: Josh Cota Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Fan SP In Actual Fan SP Out Actual FACTORY INSTALL 120 0.61 Sheitve Data Test Pressures' .... ATMOSPHERE in. wc NO ACCESS in. wc FANS RATED FOR NO LESS THAN 290 CFM ACCORDING TO SPECS NO ACCES TO MOTOR TAG, ALL MOTOR INFO PULLED FROM FAN NAMEPLATE Tested By: Luke Scaggs Date: 10/18/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Fan SP Out Actual 120 1 0.61 Test Pressures'''~ , ATMOSPHERE in. wc NO ACCESS in. wc NO ACCES TO MOTOR TAG, ALL MOTOR INFO PULLED FROM FAN NAMEPLATE FANS RATED FOR NO LESS THAN 290 CFM ACCORDING TO SPECS Page 18 of 23 ~CJNG Fan Unit PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: EF-06-05 Fan Manufacturer Fan Model Number Fan Serial Number Rated CFM Total SP Design Total Connected CFM Total CFM Actual Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual SYSTEM/UNIT: EF-07 Fan Manufacturer Un.It Data PANASONIC FV-30VQ3 602 260 0.25 in. WC 260 Starter Data THERMALLY PROTECTED 310 DIRECT DRIVE 121 0.47 unit Datil Fan Model Number GC180 Rated CFM 250 Total SP Design 0.25 in. wc Total Connected CFM 250 Fan RPM Actual Motor Volts 1 Actual Motor Amps 1 Actual JEDI Balancing, Inc. DIRECT DRIVE 121 0.35 DATE: CONTACT: ~11'i .. #3 2 3 5 #BB009025C 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 10/18/2016 ,... . ... Motor Manufacturer Motor Rated Volts Motor Phase Motor FL Amps Fan SP In Actual Fan SP Out Actual Motor Data" FACTORY INSTALL 120 0.61 Te•f Pr~ssures .•••·•··· · 1 .. ·.· ··· ATMOSPHERE in. wc NO ACCESS in. wc Tested By: Luke Scaggs Date: 10/18/2016 •. Motor Manufacturer Motor RPM Motor Rated Volts Motor Phase Motor FL Amps Motor Sheave Model Fan SP In Actual Fan SP Out Actual Motor Data ·· .. · ·· .. FACTORY INSTALL 877 115 0.5 NO ACCESS in. wc Page 19 of23 .l/J~CING Hydronic Pump PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: P-01 BOILER Unit Data Pump Manufacturer Pump Model Number Pump Serial Number Pump Flowrate (GPM) Required TOH Total Connected GPM GRUNDFOS UPS50-60F 97523134 35 10 35 THERMALLY PROTECTED Final Test Data Final GPM Actual 38 Motor Volts 1 122 Motor Amps 1 2.8 P-01 BOILER Balance Valve Summary Size GPM , % Flnjll •·•Desi an;, · Devlatloh Valve-01 T&A TA-STAG 2 1/2 N 35 108.571 : --' ,', SYSTEM/UNIT: P-02 BOILER Unit Data Pump Manufacturer Pump Model Number Pump Serial Number Pump Flowrate (GPM) Required TOH GRUNDFOS UPS50-60F 97523134 35 10 Total Connected GPM 35 ··Starter Data Final GPM Actual 38 Motor Volts 1 122 Motor Amps 1 2.93 P-02 BOILER Balance Valve Summary .GPM .6:ctua1 38 ~l~B .... #3 2 3 5 #BB009025C DATE: CONTACT: 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 11/9/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor F.L. Amps 115 2.7-3.6 ''!:Me~sured Data Pump Off Pressure 13.5 PSI Valve Shut D.P. 23.81 PSI Valve Shut S.P. 14.23 PSI Valve Shut Diff. 9.58 PSI Valve Open D.P. 21.34 PSI Valve Open S.P. 13.77 PSI Valve Open Diff. 7.57 PSI Valve Open GPM 38 ' ,' Valve D:f>; Valve D.P. Valve ',,,,,,, Coil Water• Desian Actual, Position D.P. Actllal 11.2 12.8 2.9 Tested By: Luke Scaggs Date: 11/9/2016 Motor Manufacturer Motor Rated Volts Motor Phase Motor F.L. Amps Pump Off Pressure Valve Shut D.P. Valve Shut S.P. Valve Shut Diff. Valve Open D.P. Valve Open S.P. Valve Open Diff. Valve Open GPM 115 1 2.7-3.6 24.26 PSI 15.13PSI 9.13 PSI 22.56 PSI 14.03 PSI 8.53 PSI 38 ,',, M ~~;;-::".T.'T~~Srr.iz~e:--r-:;::;;:;-;o;-~•%1/op~~ip~~~,..,.~;;:;;;,.,...r.vr-aT.~~,,~•p~.~P~.'TT-~-;:;"';:;-i---t7::11:":-:::~~'='rr"m::T:::~ ,'!:,,,,, r.:. i Deviation ·Desi n, JEDI Balancing, Inc. Page 20 of 23 .lfi!llwCINc Hydronic Pump PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: P-03 HW GEN Pump Manufacturer Pump Model Number Pump Serial Number Pump Flowrate (GPM) Required TDH Total Connected GPM .. UnitData GRUNDFOS UPS 80-80 F 96402908 108 10.7 108 \: ........•.. · .. ;i .. . . Star:ter Pata Starter Manufacturer SCHNEIDER Starter Model LRD 1 O Starter Size Installed Thermal Rating (Amps) Required Amps Thermals Set at: Motor Volts 1 Motor Volts 2 Motor Volts 3 Motor Amps 1 Motor Amps 2 Motor Amps 3 ADJUSTABLE 4-6 6 3.6 4.5 Data 109 106 212 106 3.0 2.9 2.95 P-03 HW GEN Balance Valve Summary Manufacture ·Model .• ·•·· ~!~ ••.1.t.,:n,:,.1;· Hn1 •• ·, · · ··"Nlimbiti' · · "· .. ·. ··•·''" •'•!, " JEDI Balancing, Inc. GPM Desi n 108 NJ~~ DATE: CONTACT: #3 2 3 5 #BB009025C 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 11/9/2016 Motor Manufacturer Motor Phase 3 Motor F .L. Amps 1. 72/2.08/3.6 Measured Data ··· · .': Valve Shut D.P. 19.7 PSI Valve Shut S.P. Valve Shut Diff. Valve Open D.P. Valve Open S.P. Valve Open Diff. Valve Open GPM 14.9 PSI 4.8 PSI 26.07 PSI 14.2 PSI 11.87 PSI 115 '. CoiPJllat~r O)•. Actiiat' Page 21of23 .lfi!llwCJNc Hydronic Pump PROJECT: LOCATION: VAIL GOLF & NORDIC VAIL, CO PROJECT#: 2016-7269 SYSTEM/UNIT: P-04 HEATING SYS Pump Manufacturer Pump Model Number Pump Serial Number Pump Flowrate (GPM) Required TDH Total Connected GPM MAGNA3 40-120F216 10002764 56 23 56.2 Starter.Data THERMALLY PROTECTED . ,,.,;}Final test Data Final GPM Actual Final Press. Diff. Actual Motor Volts 1 Motor Amps 1 47.8 30.2 PSI 122 3.15 P-04 HEATING SYS Balance Valve Summary ~Map.urac;tur.e ti,;Mode1 i Size G~ll/I • '.'.:i,•i ~t~ti!c.'• ;~Number .Deslan AH-01 T&A TA-ST AD 2 32 HC-01 (ERV-T&A TA-ST AD 3/4 2.7 01\ UH-01 T&A TA-ST AD 5.1 UH-02 T&A TA-ST AD 5.1 UH-03 T&A TA-ST AD 5.1 UH-04 T&A TA-ST AD 3/4 1.55 UH-05* T&A TA-ST AD 3/4 1.55 UH-06* T&A TA-ST AD 3/4 1.55 UH-07 1.55 % Flnal,1 . 'Deviation. 107.813 100.000 98.039 101.961 107.843 109.677 138.710 135.484 109.677 I (;fM, Actual 34.5 2.7 5.0 5.2 5.5 1.7 2.15 2.1 1.70 til~.1 .... #3 2 3 5 #BB009025C DATE: CONTACT: Tested By: Date: 11/18/2016 Josh Cota Luke Scaggs 11/9/2016 Motor.Data '' .!'' ··.•' ' <, ,·Ii ' Motor Manufacturer FACTORY INSTALL Motor RPM VARABLE SPEED Motor Rated Volts 115 Motor Phase 1 Motor F.L. Amps 0.26-3.88 Measured Data Valve Shut Diff. 40 ft Valve Open D.P . 30.2 ft , 1¥alv(;I D.f. :: •'Design V~ly~~ '··Act , •... ,,va1\/e 'i'• ·,Position • .. Coll vyater i'.D;P.; Actual 2.45 2.7 12 12.0 1.3 9.5 9 1.5 14.2 14.5 9 10.5 1.5 14 18.5 0.5 11 20.85 10.5 20.0 13.75 17.6 0.5 ,' :· ~Z'•,,J'.o,~l~~!'il'!iii1:!IJ!' .. l'·i!it i;,~·:,'·: ,, ''·· -' ,. ."I•!";!::• ':' :: -·'; ', ·<-' .,,:::!.:. ,1,::·~ .",:.:!·c.•j:· ~ ,: log: P-04 HEATING SYS/UH-05 11/8/2016 P-04 HEATING SYS/UH-06 11 /8/2016 JEDI Balancing, Inc. Luke Scaggs Luke Scaggs CANNOT CLOSE VALVE ANY FURTHER. CANNOT CLOSE VALVE ANY FURTHER Page 22 of 23 .lffiLNCJNc Hydronic Pump PROJECT: LOCATION: PROJECT#: VAIL GOLF & NORDIC VAIL, CO 2016-7269 SYSTEM/UNIT: P-05 SNOWMEL T PRIMARY Pump Manufacturer Pump Model Number Pump Serial Number Pump Flowrate (GPM) Required TOH Total Connected GPM .unit Data GRUNDFOS UPS543-44FC 52722514-P 1 16.6 9.9 14.7 Star:ter Data Fl11al Test Data Motor Volts 1 Motor Amps 1 15.5 121 1.62 P-05 SNOWMEL T PRIMARY Balance Valve Summary Systjl~Uql~1iii!: .>:!;.::'i.:'iiL': ::i!f' SM-01 , ''Model Number TA-ST AD Size 2 . GPM %.final< Desi n' Deviat1oi1: 14.7 105.442 . SYSTEM/UNIT: P-06 SNOWMEL T SECONDARY Pump Manufacturer Pump Model Number Pump Serial Number Pump Flowrate (GPM) Required TOH Total Connected GPM Final Press. Diff. Actual Final D.P. Final S.P. Motor Volts 1 Motor Amps 1 Log: P-06 SNOWMEL T SECONDARY P-06 SNOWMEL T SECONDARY JEDI Balancing, Inc. Unit Data\'·· GRUNDFOS UPS50-44F 5272257P1 15 15 15 5.58 PSI 26.75 PSI 21.17PSI 121 1.45 11/8/2016 11/8/2016 Luke Scaggs Luke Scaggs GPM Actual 15.5 H:i~J .. #3 2 3 5 #BB009025C DATE: CONTACT: 11/18/2016 Josh Cota Tested By: Luke Scaggs Date: 11/8/2016 Motor Manufacturer Motor RPM Motor Rated Volts Motor Phase Motor F.L. Amps VARIABLE SPEED 115 1.4/1.7/1.8 ,·· ...... Measured.Data .. ' r:., ' ,.,· Valve Open D.P. Valve Open S.P. Valve Open Diff. 15.74 PSI 12.79 PSI 2.95 PSI CoUW11,ter D.P;Actual Tested By: Luke Scaggs Date: 11/8/2016 Motor Manufacturer Motor RPM Motor Rated Volts Motor Phase Motor F.L. Amps Pump Off Pressure Valve Shut D.P. Valve Shut S.P. Valve Shut Diff. Valve Open D.P. Valve Open S.P. Valve Open Diff. VARIABLE SPEED 115 1.33/1.62/1. 72 0.05 PSI 28.22 PSI 22.25 PSI 5.97 PSI 26.75 PSI 21.17 PSI 5.58 PSI !', NO FLOW METER ON THIS PUMP. NO WAY TO QUANTIFY FLOW READINGS TAKEN N MEDIUM SPEED SETTING Page 23 of 23 f!Hlin ·' 1 i ' ' ·' ' ~ I ~ ! ' ~ " ~ !1 I< " " 1 I.I ' i ! ' ~ ~ ! I i!;i:. I ~ ~ ~ ,. ~ •! t ,, ~ >i ! I~ ~ ,• d ~ H. ~ FH ~I H ~ ~ ,\ i ~ ~ ~ I> ~ ~ Ir~ ! ., ~H Ii 1!11 ! ·l hU ' H ! "' ! z ' 0 !! I= " !,2 !i !: u ,, UJ 1i .. "' ·' _J 10 " ll u z 1H ~ ~ .. :c ·'' o~ ~:: r. t"l'-' "'' l· ;· "" ' Ii I li:i !~::I!! i I!! I ' i 11 ~ ! ~ ~ ' 'i' ! g. '" i i' !I! § ~ ,, ~ ~ ~ !I ~n ~i ~'" i ~ 'i ~g ~ ~ ~ ~ !ill !! 1! 1' !! !•b ~ ~ H ~ ~ ~ £:, t, ,, !I :HI ,, f ~ ~ ~ Hii !I r !hi -1 il'' I! 118 ~ .. ts .. 1'!1 H~~ ~~ i H~~ ~ ~ ~d f. l ,j ~ i ~H II '.I ~h ,1 h:H a~ ~ i '" H Ill j! ;I ~ ~ !) ~ ~ '• ; ~ ~; "' ~ ~ ~ i ~ g ~ i r· iiH " ~@Q~ 1'' ~ 2 ~ ~ ~ 1!! ! a g ~ ~ ~ ~ ~ 15~ ~ ~H l ' ' ;J ! ' i I ~ ; ' ~ l ' I ' ~ ' ' ~ ~ i( ~ i ~ ! i~ [! ! 1: i ~ 1! ~ ~ !; '~ l ., ; l' ,, !I ,i ! ~ l ,, I! l ~ e !i ! ~ t 'I ,, ' !: H ·' ~' ' '.;: ~ ~ ~ ; a !i ;lU H l'' i ·'' -.· ~~ ,, 4i ., ii I! ! !! ii ,Ii ii iii n 1· jc OOVllOl<Xl 'WVA 1300W3~ 3SnOH9nl:> :JIO~ON ONV :llOG llVA 11 ~ &{ " r .. ~ ~ .. ::. .. ·:·::·'.': ~""~r-..• FURNACE WI DX COIL SCHEDULE I·~;:-l•A'"H"'·"I ·~ k-·I ~;'.• lonl c•n 1~·•1:·:q ·;~ l":::"l '::.T~;T:~· 1 ";,T"'~' l"":''"l•~•=l ••ce~••• I I I I" .,, '"''""'~'""" ~·-''"''"'~ Tl '.l .. lo-:&<.>"'~"""-"'OIJ<.l>IO' ... TED~5~0"" m ~O:!:~~,!,~;~:,';;;<,.~~ aec '>rdllle.,_t~r"I Eng1r,tem1g ('~,,ult~nc' "-""~·"" l~''"''' ~ l ,,...,~ °'""' """"~ ,:nn ~·Y""""'"·'""'""~'rn'"• ~ ENERGY RECOVERY UNIT SCHEDULE ~ ::: 1"-:::;:::··1 "~· 1,~-1 =T=r~I ::i·fYE.~ ,~;L;?I~ 1:.~1.~1 ::·r::·.::;:~~1 .• , ::·,,·, ="· 1·::'j'::::::1 .. ~j:,1:.~1:.::.1 ·-" '""-··"·+ ...... !~;;.';"'·I· l·+I · H··l++H .. l···[~ .. jw-:;·[ .. I· I ~ ...... w I·~ H·-~·"l·,.l··l .. ·I ··I·" I t ---EXPANSION TANK SCHEDULE I ~rn~"'"1 G:T----AIR COOLED CONDENSING UNIT SCHEDULE 1 ~;::I -~-;::::;" I ··~· I ·~·=· I·~.::;, I;;::;:_~·~~"'+~· .::~ .. 1 ;::. I ,._., ~ -:.'.:':;;;'"• i •w ! .oc .. ~ ~ ffl>• "'~' ;.:;:::·~··""''.,,,,. ~ ''""'""", ,, •••• "" : .:::;:, .. -•~>' : ~·. ..~~ 1.=~~FJ'.::::"™I:::: I :: I :: I :: I::: I :: I : I :: r::-r --71 :::. .. ~ HYDRONIC UNIT HEATER SCHEDULE '<'•1';.:..-::,"'"'' ····! •. 1 .. ,,3'!.>0 '1uC !OJ-<l 1~:.~;,•il<l" ifC• iRO-"" '" !••=I . ., I woo '"" I ., o ~ '"' o ! , • _, ~ ... " /~::&~ 1<0 ~\;' ~~;J$l I "" -~_l ,.~ FAN COIL UNIT SCH~ ---~ ~': •• "'.":,'." '~" '"'~ ~;~ i~ ~ <W ':: ,~,,,"::7:_,.::::::,. '\~m ·~~ ~ • •-• ~:·::•:::;E;':;·~~~:;;;:~-· :'.::• .::,:.:.. ;.;~1 •-•· ... /.~ . .,.,.. / . .," I ..... I]/. l,.J .. l ,,.J'tJt(f · 1 i · J,, fJF · 1 .. 1 ... I .... f ..... / .. 1 .. 1 .. ,/,..f 1 ··· ~·~·~-I ~"· 1~ j ,., I '" I "'I'"' I "'"'"I" I" I" I R=-=i ~ AIR HANDLING UNIT SCHEDULE ·-·j·"00•:'="~-"C.,. :,,.: ,., '" "''"''""" " " " c >1-:;;:~~· I ... , / •X'>> /z;:,.:::1::: .. , .. , .. "T: 1· .. ''~~·~·~.. . ,fo~f ~~r·-o;:,.~ r"•«• .. 1-··~· 1·:::1 •• • m - -··=· . -..... ···· .. ·· ::::· :.:: ·:: 1-:.T::·r:~·r:.-r.:· .~'. ·:::· :: .. ~.::r::~··1:r:, ,.:;:~. ·:r'.f.~ .'.::: Mt<U.Al.""'1 LOUVER SCHEDULE """,.,.,.,.,l!\.~l~~"j ;...,., •".iJM '" !•'"""'·El'"'"~~ 01.11.Dt•Gl>•cul-.ER'°"">V<-I Z.O>O ·~·•=>< G'~'"0& """~·-"""'"" I ....,.~.,.. 1PN<'Of"1HMK.Soor.lr.,...ow.11E><EFOO•EFE0<1<~E "'"'"""'" ,,:::!;:"~ lm··~·~I\.·~ 1 ;.:;::;, PUMP SCHEDULE ~~ I ~:·:.:· 1::,. ,:, ""'~ '"""'J o::::T!sEEF1.0'Jflrc•«$ s~~~~'. I m: r1.<><>11 F><...,s i--GLYCOL FEEDER SCHEDULE -. ~ ~~ 1..::.::'"' , ... ::~~+:~: I ;,;~ I :,:: r::r ::: !'''.:'I : r"'.'.~:~· I::· [ ·=~ ,.._, ..,..__... • .,.-><•> "''·'"'""E"T ... ChAOC... '7 •1.7' ''·" 30.00 07 OO lZOl•'•O "" I ! ~: -· ---·----·· ... AIR DEVICE SCHEDULE f= I ~<IS/1 fw..' Dll'~~suo '';!"I'..:;:'.'" FORMl<U-1.MAU-~ Kf--1.KH-2 r<H-J.E.F-1 2.&JSELEC"'lOI>< AND SPECIFICAll()N"""S"°P.L;:['RJQKi!~N f>LAN.s. All RffER!:NCE:S SHO¥,"l l--IERE ARE FOR REFERENCE Ol"<l Y. f ---HEATING COIL SCHEDULE ... ---;;-c°'"'"'j :: J,;~~:·~" 1 ... : .. ~· 1":::~ ... 1;',;;;,~""l"::t::~·1·::t~"l~~'I:: I:: I ~:T:l·~, 1: 1·:~1·:·1mmoc••"0"''"~~::: -·~·-~··-··· t mo"' CA~n"o~GER SCHEDULE '"~"'"~ :l:::·:· .. I~::· b,.:::~~ 1·:1"~~t:·:~·:1~::·!":·:f:~r:·1~.~1:::::f ·-~ -··-·····-· ---··--··· -I -· ·· -----· ""~~•mou -~ ;t~~k:fftfitttf~l~t§~~it: L~ --::,:.:::;:,,E~• SER'A.< ''"°~'~ ~~~~ ~~", ~... ~~~ :::.'"~":~·.: :~r'."'"'""~~:'J 1~~ ;::~~';'~, _.:,~~J """"'" I --"""""'""''°"'"'WU ···1 :~: ~ blJl:JIJ=IJldiliU • I EXHAUST FAN SCHt:.UULt:. l\o;:;I ·-;;;.;;:-:.:·,. '™I ;:"; l•w·" l".::·1"":::~ 1,;E.;J.::•.~.;, ~!;::C::!' ... ,, .. I;~:;~ I=•·~•~·"~~' '•·• 1~.!;!'.,':'!",,,.~l~o~;= I=•·~''""'~ ,~. 1~~.::-~,::·.,,m~I~.~·" ''""~''"'"'~' !«-< I':·~. le,..,.....,. !s"'"'"""-"'l""'-'~•MI •""" ju-s lf'~<JS I"·' 1 ... , ,.,.~ ... ~ i•• b::, ~~~';":~_,';""''lsE-< "·"""'"""Im_,.~ BYPASS OR ZONE DAMPER SCHEDULE ';~I -,;,,,~::.';;" I ... ~. I ···~ 1 ·~; l·~;c:f.;;l';;;=t~ le.SI:~, I '"'<>'~Ef'IEcO .. sr•urn•...: .... Nl~!:P'"-"l>P-"-TER~~TE""'WIO<•"' l"'~a.«0•.!!P"8C-Sft"'"qcvc<•"™""'"""""""'" """"""""'""u; .. STALlffi8 .. 0<!ll""~""'f0 ... l<>()..._,.,.~,_,_,,,,_,D!"""'<' IN't:G0,._.,.-._.,~,,-,-,,_00 '"' 1:~.~~" 1~"""~' l"•R=••·I ,,. I '" I • I'" I '"' I ' I " 1~~croo_,. ~· 1:::::~"' I" l'""~"•l «-1 "" I • I"" I '·' I " I •• 1~=m•-"•mcoc.,•-M'~"~°"'oc"m'"""~ ,...,,,...,...., .,,roo .. f":AU ,...,...,. ''"'"'""" ,...,...,,_..,.,,, -~I .I ~i!11 ~1! -~ ·1· ~i 1 Ii f i ~~M!~ul z ~~~~ UJ 11!1 ~ ~ Cr! Ui ~ i i!J • ~ I U-ii UJ •n ! i NI~ " . .~. ~ 1 "~hi ~~~m u -....J D LU ~D oo z~ , D ~1j Z LU ~ < V) ~ u.. ::J ~ ....J 0 J• 0 I~j lJ cc ,.. ....J ::J ~d MECHANICAL SCHEDULES ~---»112145 07/13115 --~--"' 10C ""' M1.1 -"'"""" o. J TJ ro rr·1 r1J c ... , lJl x !JI ) 0 d·) ii I U:J lJl '----5· ).~ J ~ ~~ ~ __,..+fl) d ;:-0 0 0 lJl ~ :5? s· ro Q.. Q .. dQ .. e ~ :1g~~~ ~:~ g-s--<-9 (1 -r1J :;~~ Lil ~ (1 '.~ ~A 9 :::> 0 ~ p c+ IJl -t; , .. -p i-:J ~ Lil < {{) r1J s-)_) r. Q_ ,+ n 0 p " ' CD r'l1-'lr § -~ i . rr ! rr~l·ff j n ~ 'l' LL -;LL.-<_. r] : r "1 i 1---J -··'i ,, // -1---,.._ , ~ ---r r ~ I ; -; ' ~ I ""~~·2 ""~ l_ ~ J, lJ~-----x --------+-----' ~ r~p ---~ ~ ---'==-'==-" ' ______ " ___ j ll-1 !L '~ ~ 11111 11111 .., ... " i~lliP m ib,!1 '!m' j;; ~!;J m '' i i o:;~--<lj!O::"'~ l!l!!i ~i~~~; ":'.:; ;; d l I ' 'cc~~ ~ ~ i""!i ~ ~ p~ ~ ' ~ d~ -----=--r==o I ... j !!~!''.; ~ ~ ~ m' ·oo!!§< ~ d F ·~ ~' 1!!1~ ili !l' ~ .;f. qi ~ ;s ~ ~< ',, -5 ; ~~coe ~ ~~~i~ ~ ~ ;c ~ Pi ;~ -T~ --r--~~-! ~ 1J ~ ~ ·-~1~1 ~; z • ,, " '' ~.~I ··1·11 c·1·i 81'''7 I -ti:' I I ~"' ....... '/"\ .. ' - ' I._),_, --~--~ ~-.1.:~-----------~-~--\/nil Golf ClJbhou~,e--Vu.il, CJJ R.'.~ ~ m "~ ~ --e;u-, •.• ::.,;;--_ff4-i;-~ -~~~]:"Ilr ;1 _.., === . i ............. ~-~:-~.~~-~'.~.~~-~-~--~-~--'.~~-~-~-~~~~~-=~-~~~~~~:~!~:::! F~-~~-~!-~~~-~-~-~-~~-~:~:;:_;ri_~~ l. -.:'. 1-J:j w °' . c...v t:!_bl ~ E. g.] ~ g Vail Golf Clubhouse Vail, Colorado . : ii ·~r I ,if!<}lo 3 \f :.i.a ~ ij !i! 5'" S"~ ~~ ~ !ff![r; !•i~t1~ •t,,f,J i~q~ ' ii 8£ ~l~ ~{~ ~.~ i'I ·1;----1 11~ J!~ --· ot!;M)'.l(Ol&I ~"OllOllftlS'J3V i9lL'i'it>i5(0L6J lfl"'ds_,UWH'llWMNP'llO<llUOW """"""" """""""' otSG"'1U•L(Ol61 ~U~7sv "aG°9t-'tfU61 upnwwo1'iu~1.11::urw 19:lllMOM ""' lrll'196lftlltMOllHll-OIOl ... ~K'!'1~Gll8 .. , .. .....,__ ,.,~......,--....... '()', ~ -u• .. .,.. _ _,_.,.,.~ I :At'\DJJHlW MV'JSONV'I ., ~I· !Jt.INNVW •i111U:B1JH:lW I I 'JNI 'S31VIJOSSV ONV N 3 ~ H 3 z i "'!'"'.''""' Y"'"l-'L'q1f(I, •If!·'"''"'.) O<JVll<)lCXl 'YN/\ 1300W3'M 3SnOH8nl:) I )IO'MON ONV :110~ llVA Ii I• I ll , R 1 G 1-1 I L--~ I " I "- I ®§ l L ___ l I l _________ J ~ I I \.e I I I L _____________ _J ~uZ ...J z :5 o<Oo.. 3:"' 0.. 9~~ z ~ a.. """ z w ::;; a.. 5 0 w (.) z 0 0::: c >-:c ..J w > w ..J 0::: w 3: 0 ..J z < ..J a.. ~ w ::;; 3: 0 z (/) ..J < ~ < a.. ;~ ,~ Iii 11 q~ "--"--t'l'l ~ ·~ .~~ '" Ji f l I GENERAL NOTES: 1 N..ll~" "''""'r"'-"'"s""0 '"£>l<L>"""""°'rn11<'llt>E , N..<R<)l"'°D<ICTC<l .... E'TIONST.;>R,J•JNC'CV'.TN"lf''S+•~;c""""';; • "'·~'l',,\l<C'1"1'•b~H'L!!,'W:<s~r"-'-""'""'''~W>;<3 (.. N.L r,;-:;nv,-~<L' ""R'"'fl'"'TlOllN·--1-"-....,"r'>FSTffj ~·C~k,<Jf'3'1'""F STft"C'<-V""'RflThl>TS•JO<-FS-~nT><FH....,SF,K>TF;, • N.!<W'·"'"""'P·'"""'''""'~""'""'-""""''-"""""'ll"S S...,,., F>t";tUOFRAF r.At_,.,ff>SAA!'HlT<•'-ir<;~'l<~T(,Ff~F~> ' ;tM..,,,. .. ;;rFA, A•~ F"'°P~ .. , <~_.,, • ...,.wn-~···~·HIJI;'! < '-''"""'"'-' TFMP ••o'tl<"'~F'l.'o""-~""·''''N'<W,-•,•c SHEET DETAIL t!,OTES: 0 :.:::;.,-:::~~~:::::;'~'::.~';'~:·;,'.~ ;~ .. Q ~.~~/:.!'~~~~~11<w •. c~>•<~ 0 =:m~\~:;;::;:;:::::::::i::::s::~::s, @•co~'"""~ @ ~~~~~~~;;.;~·.~:-~;;~:·~.··~rn .. c @@S.t'"~"''"·'"'~'~'''"""'~.) 0 ""'~""'''"~·~·,,., © ~~;.':"~;;~~~;.;~·,~;:p~~;::c~~,;:~:"' ~~"·'"~"''"'"'""'~ @ ::~,;,,':;'.'.'~~~~~~::,~:;::::.·.;;;~·~· 0 '"" .·.~ ..• '""''"" @ •m• '"'"'"'""~'""'"""' e ~~,.-~:~;:::: :~.'.':;;,c;;::;:;;;:.::;,::c.:rr":t,;,'.. e ·~•o•~~'""'"""~"·~·,~·= 0~·····'·'1'<''"''""" ~l""'.><':-~:.s~ci,,~fufo8 0 r"" iJ, -~-u~lr(~ffi ~-· A r.-. i•,, ·=""""' la,! IEF-06-031 10'' ii¥--"' I \V \lb 'i lJ_ G ,,.~ @Gfu IUii02L ~ lw ~ ~~·/.''."_~ . . ~=J • ··~ l t~ ..,'e:.:-c ,....,.p,,,,,x~:,f.F'_!_!.! 0».t.@-'" NORTH LOWER LEVEL HVAC PLAN ~ ®Q,, aec l\rd11ro..1~rnl Eni:io~cnu;: ('-111,ulwn:' >.\.""'°'"' l•-.-"'''"-L""'"''°"'"•"•"-"'"~' 1:.rci·~, ... -1.~•h1• ... -<•''"'•• ~ ~ -~ ~~': ,Z.'" _r '"'~"" )EF-D4i i · .~ '. i~-m j6 ~r-,m~, ' ~' ~I ' ;,~M•;,:;~;;;,'@ i 1t:::..! _:;>t;,,,,,, I ~:';;:;';~:~~:'~~ _..J!tl-1. l ~i In -g g ~ivt &! a e ~!iii ii o~~d1 Id d ~h;n iii z ~s LU li!i ;; ~ ci::: m ~ i :ih R ~ I H: : i LU j§§ I ! N 1•! ! ! •~a ~ J ~~iii u _...J 0 LU a,::O oo z~ 0 ~1' Z LU ~ < Vl ~ 1.1..::::>.i:" ...J 0 ;(' O:c,.., lJ co (' ...J ::::> <...J >u LOWER LEVEL HVACPLAN ---...... 20112145 07/ll/15 -· ...... _ .. <C TIX AIC -~ M2.0 ~ OlSHl>.l.(CU:61 ~·oUO!UWIS':sv i9i..!"6.S(IU6) t,...is:-.i~'ll'"""JN~lllll"°W ,.., •'l"/'u"i '? ""'f,l·"i 1/lt; '1'r~u,,fo: """""" ~ OCl\'ll010:> 'rtA OZSIHl•l(0£61 ~·ollllltWIG":aV •.ao-9t'l(lllfil lll~WDl'ilJ~UpJJ'W ~ = IDl""1CSolllPl~OllHM-*ll ...... t:u:~~Olle 1300W3'M 3SnOHsni:::> won......,__ .... ......, '""'"'"'' '-..:::Ii -u• .. .,.....,,_,_..,,.~ I :illruJlll-CW JN.>SONV'l ., JIO'MON ONV :llOG llVA CllOABJ.Nl•!)f<INMl(W·JWU.:11JJHJW I 'JNI 'SllVIJOSSVONV N 3 }:! H 3 z • I «I I• z ~ 11. (.) ~ J: u. 0 0 et:: ...J z ~ :s ...JO. 8~ "":c l~ ,~ ~ ,~ ~ ~ ...J ~ a z 0 ~ w ...J w C> z j::: :::> ~ 1-(.) :::> a, N' . ' u.. ~ . ~ ·~ 'ii I ~~ ~~ i ! OlSHl"l(Ot.fi:I OZ:SHi"l(0£61 "'I,,,,,.,'~''' 1' ""1"1 '1 Siii< • "!"''"h J OCl\lllOlOJ '"IVA 1300W3~ 3sn0Hsni::> ::>IO~ON ONV :JlOD llVA I 0 .. .. ~~ ~~ z :5 a. (.) ~ :i: ...J w > w ...J z <( :::;: ' ~u1 QJ.!~! ~rn ~r !l ~ l~i 1 !1 ~ il ~ l!li ' 1q ~ ~ ; ~ ! Ji ' ~ ~ ~ ~ ~ t ~ .. ~~ ~ 5 ' ~! f' ~~ ~ ~ ~E ii ~ i !i 1l h ii ~ ~ a~ ii ; ~ ~ ~ ~~ ~~ ~;\ ,, " g~ ~ ~ .;:o n ,, ~" ! ' l ! ~ i I• , 6 ~ " W• "1 5 ~i! ; ~ i ! o' ~ ~~~ " ' " 0" <IL ~ ~i~ ! ! ! < j:::; I/ :5 ~ l ~ ,, ! ;:: z ~ ' w • > I! !! I h i !!. I 5 ~ 1 ' l j i . ' . :·:~':"' :';,;::::;;~"~r -,,-,,, I ~~~~ ':[i111~~ii=;-~~~~1m1 ~;:;;;"' J'f'\YM-·~~''"-'-....--.... r H.-nt.'<-"'-~"'-... UUk,~.\fHokh '""'-•<'>.-, <~L"'-'1C;;lLJ>'(lf """"""""""~Sver..,-;> 1"'3u;•,)C' L'l"" .,,....,..~ • .._,,,.,, T"'° '":l\J"1 ""'"''' .i;'<X,[ ~'~"'"w~ ~::::::·~~ 0 <"H(;f<[>;'~>fT'V""<)~· l~~~~~2~\r¥~; ~;f§~:.f£1:~ifi~i:~; '~"'"" 'k ~~-OWMEL T TUBING OET Al~~" C{'« ~•~• O$ "<> Rrn -°'"•h.;<.:lt> ~~~.or.<> mT,.,.,IT» S.JPPLYftflpjr,,TW, SNOWMELT MANIFOLD DETAIL UPBLAST KITCHEN EXHAUST FAN DETAIL ·••~•·•e>m\ •~ '"'= ·s~;~ "°"" -U.\IYl''"' ce>~t. ~ VD r·~"'"°'" /"'~~" TYPICAL FLOOR GRILLE CONNECTION DETAIL SNOWMELT REVERSE RETURN LAYOUT SNOWMELT TUBING STAIR PATTERN <'<>Ul.&Tl"'!L>NC~• l'.-Rr/CNAT ;· STA~C'-"~ RIC.ll:<INS<.JCOI>~~ \>NOCR'~'<.KW~f$•~CCECl<S-DISHWASHER ROOF EXHAUST FAN DETAIL I +•"~ M ' '""'~'"" ''"" " I ·~•·•~T:>Pl<f''!:.tc~u~.;"""~ 1"-"" Wl•El•CO~:RFTFIS'-ovREO ;~M"~.>M> ~~;;,~;:~~~' rM•/IDCAf'"~'LL>. '-~~>-;: P l~C,'-"A>l(».,;><Of'R~P~""y r:;r<>o::,:.;:nonlD<'"'''-"n'iN c~.OFRW"'-<W•<'Sl\>ICDE'.X>. TYPICAL,_ ~~SUL R-102 SYSTEM LAYQ_~T zV0f .1}}J)i~:\aJ1 ;~~;:~~[~'o, UFANSIONJ•,...,-p(TC,0.:C"''>O,'t.lA·:• ,"'.~£'"1\.'< SNOWMELT SYSTEM INSTALLATION DETAIL (PENETRATING JOINTS) SNOWMEL T SYSTEM INSTALLATION DETAIL (SLAB ON GRADE) ;c~.g~~:;;;:.;5~:~~ "~~~~~~7·~ I .,... -'T"'.. "~··"· ~:~. ~ :;r.}DlJCT " ~ .... , * "~"''"'""' hY5TF'.!I''>'>!' --I 1 ~!'E;;;~~;:·.;~., ·~ , ~~~-·· ~ !ONV•••'L -........ ± 1 ~ Ek-r.f'RA~GEF>i<'1~c;oo-1 ~ -I ~;;:::,'~N~ T--M'<'C~ g~~;:~~~~E:lt.G ,,.. • .,, ... ~<~D ROOF DUCT SUPPORT DETAIL ROUND DUCT TAKE-OFF RADIUS ELBOW DETAIL AH-1 3-WAY HEATING COIL PIPING DIAGRAM CLOSELY SPACED TEES DETAIL aec l\rdnte,,~r:il Eni::m~erm~ C"'"''h"'"~' i .lfR•ll.<W,f'"""'l>.TAAi' ' "' ""''""'""''·""""~" '· t,YF.,()1.1~• ... F~r'i'.~"' SLOPED ROOF TERMINATION DETAIL FLAT ROOF TERMINATION DETAIL "-'-'~··•l Lr,·n-•t ~ L••"''''"""'""'-""'' ,:.fr[> '"'""'"c""•"=•"~JC"'··• ~R/., \~m"'·''.'"'"'"' 4~ _,, .~;:l!;.'<,~•.';!1~,,,,:" ~·1 ' ~":·'!:~~~~;~'~ .... AFF i~.gij~~ '\ T TYPE I HOOD DETAIL ·"IMCO!m>OL\'~l"1' ":>l< ...... ll'' ~~~~~~~'"' ~ :,:,·:.~o::Ccc,,, n ~ ~~ ~ ~::::•:;:~ I E,. 1J} ,,,(/:~:~~:;:;;;c , . ~,,,~,~~ce USEASC00..01,,IN -'l<---""">-t• _...... ~ , ~~"i=:2~P.,.,1'ft ~~~~t~if~~~; / •;;::;;,:~:c:~~r~~!~ r IN-LINE PUMP OIAG~~~~}~~~.~~ s:2~~~~~ j ~~~;;~:--,,,, •• ,.,,.._,,,.lti ... 5T,'ll<',Dl~"F<"N"-•~-o:"'cfl"'C.SR•'l·.-;F'·R>.ID~CTJC:• AA:>R,.,-.0-""1~TRFUOTFO~W'FR-.;:.t."r:W, ER TYPICAL DIFFUSER CONNECTION DIAGRAM 45° DUCT TAKE-OFF 2-WAY COIL PIPING DIAGRAM --~; ffl' • ~11 ~1 i f ~' 1~ ~1un i!i! z Ll.J ~ii i ~ ~ •p ' . i ! n I H~ I 1 Ll.J ·~1 d Nill .~ jl ~ ~111 -~...J ow ci::O ~~I o~ Zw <Vl LI.. ::) 1 ....10::-0 :I: lJ a:l ...J ::) ~d -.. ---MECHANICAL DETAILS -=1~45 1-:/1-;.S -;; l°;;:I~ --Ml.3 -""""" HP LaserJet P3005 printers Clear Jams )J!ffit-F~ Elakadasok elharitasa y crpaHeHHe 3aM~H1H Eliminer les bourrages Odstraneni uviznutych medii ~p:1 ~~ oH-?§! Rensa trassel 0 0 0 Staus beseitigen Afhjcelp papirstop Fjerne fastkj0rt papir )fi~-tti£ e e e Eliminazione degli inceppamenti Storingen verhelpen Usuwanie zaci~c Kag1t S1b;malann1 Giderme e~ OJ] Eliminaci6n de atascos Tukosten poistaminen Limpar atolamentos e PPl® i n v e n t Ot---- HP LaserJet P3005 printers Clear Jams iW~~~ Elakadasok elharitasa YcrpaHeH11e JaMS1T11H Eliminer les bourrages Odstranenf uvfznutych medif §Al~~ 5H~ Rensa trassel 0 o~~ 0 Staus beseitigen Afhjrelp papirstop Fjerne fastkj0rt papir JW~-F~ e e e e~ Eliminazione degli inceppamenti Storingen verhelpen Usuwanie zaci~c Kag1t S1h;malann1 Giderme Eliminaci6n de atascos Tukosten poistaminen Limpar atolamentos -~ ~~® i n v e n t er-------------e i----------[[]] Range Hood Fire Systems Report Inspection Agreement Terms and Conditions DATE OF s~Rv1g,E I /' TIME AM PM \I I ? 11'./ TRI tOUNTr/ i_ ANNUAL SEMI-ANNUAL RECHARGE INSTALLATION RENOVATION O r.LI_FIRE ~~1~~~~~~0N LOCATION OF SYSTEM CYLINDERS 1 V ~ Frisco, CO 80443 DRY CHEMICAL 1708 Copper Ridge Spur, Unit A Steamboat Springs, CO 80487 970-879-3732 970-479-0319 3159 Baron Ln. Rifle CO, 81650 970-625-4533 • 800-640-4007 CYLINDER SIZE SLAVE FUSE LINKS 360' F FUSE LINKS 500' F OTHER I C\J$TOMER Name \L<t t \ to I i c 1 viz h{/1/:(9 '") 6l. Addres.s /""') ) S' 5w .b Vi' 5 '+ I;:' {. ELECTRIC COOKING EQUIPMENT GAS COOKING.EQUIPMENT t., /., GAS VALVE TYPE ELEC, Fe) City }le! I I { (C 8l 65 -7 FUSE LINK MANF DATE LAST HYDRr T';JJ DATE LAST RECHARGE DATE ) 6 SYSTEM MONITORED BY PHONE NUMBER ACCOUNT NUMBER LEFT TO RIGHT Bfu ONo DNIA l3~0No ON/A D'Yes D tlo D NIA S'Yes D No D NIA eYes D No D NJA erves D No D N 0 Yes CJ No El NIA f;J1es 0 No 0 NIA fa'Yes 0 No 0 NIA CYes 0 No Cl NIA :':,'ii'111i:,i::,::i:l1i''1~; g .~'', ~ ~:~. . ' · .. l!J'No, [J NIA ,,, ,Cl,Nlk 1:1'111"1'" 17. Replaced fuse links 18. Piping & conduit securely bracketed 19. All filters reinstalled 20. Fuel shut-off in on position 21. Manual & remote seVseals in place 22. Reinstall system covers 23. System operational & seals in place 24. Personnel instructed in manual operation of system 25. Portable extinguishers properly serviced 26. Service tag on system ?7.)nternal Tank Inspection (If Applicable) l;JY'es 0 No Erv~s ONo r::G.es ONo dYes 0 Nn GfYes 0 i\'o ~0Nu Gl'Yes 0 No i:rY::s 0 i\'o Elves D '.'lo crY,i;.1 0 No er'~ DNo CJ Yes 0 No 28. q~eck Regulator Manufacture Date (If Applicable) ~?~iit!?n of Gas Valve · VVic:J ':f I"" h G:f:''.k( ,TE,,blscREPANCIES OR DEFICIENCIES BELOW 1:;1:::::!1::!:'.; 0 NIA CJ NIA DNIA DNIA ON/A DNIA ON/A ON/A ONIA ON/1\ ONIA DNIA Range Hood Fire Systems Report ..--------------'-"_8_P_e_c_t_i_o...:n:...A:.::.::g~r=e.::ement Terms and Conditions r:----------......---------.----.----. DITE r,sErlCE TIME AM PM TRI tOUNTrt i n ,lI_flRE P7~1~~~~~~~N ANNUAL SEMI-ANNUAL RECHARGE IN TAL TION RENOVATION LOCATION OF SYSTEM CYLINDERS 1 V ~ Frisco, CO 80443 970-479-0319 1>1 DRY CHEMICAL MO L NUMBER " --)O,, 1708 Copper Ridge Spur, Unit A Steamboat Springs, CO 80487 970-879-3732 31 S9 Baron Ln. CYLINDER SIZE MASTER CYLINDER SIZE SLAVE CYLINDER SIZE SLAVE Rifle CO, 81650 970-625-4533 • 800-640-4007 3 ' l I 5 c ( ' CUSTOMER , ( b FUS LINKS 380' F. OTHER Name __.._\l ...... a ...... '__.._--&_;:O::....:l;......;{_..i....{,.:s..d)..i.:::V:.....i.""-!..l.Jh 0-.utA::L..::::::. Address r 7 1 s > VhbcJ( ~ + Dr ELECTRIC COOKING EQUIPMENT GAS COOKING EQUIPMENT GAS VALVE TYPE )( CcJ gtG51 FUSE LINK MANF. DATE 16 LAST HYDRO LT DATE Iv .T~l~~hone-..· ·---'------Work Order No ____ _ SYSTEM MONITORED BY PHONE NUMBER ACCOUNT NUMBER !~E!~ag~r .,.......,. _____________ _ G APPL/ANGE LOCATIONS: LEFT TO RIGHT les cew/MFG UL listing 'd wJweld or UL device of tampering ,~!'(If gauged) plicable) Ef~s 0 No 0 NIA Ef Jes CJ :-lo 0 NIA 0Ycs 0 No ON/A 0-Yes 0 :-lo CJ NIA EJYes CJ No CJ NIA Efvcs 0 ;.io 0 D)'.es 0 No ef Yes 0 No EfYes 0 No 0 NIA 13'Yes 0 No 0 NIA aYes 0 No 0 NIA l:fYes 0 No 0 NIA : G:l"Y;s, 0 No 0 NIA ? :';'BY~~:'dJ No: .CJ NIA ~'':CJ ONIA 4'.-)' 17. Replaced fuse links ~~O No 0 NIA 18. Piping & conduit securely bracketed CJ;p 0 No 0 NIA 19. All filters reinstalled c:f Yes 0 No 0 NIA 20. Fuel shut-off in on position OY;:s 0 No 0 NIA 21. Manual & remote set/seals in place E(yes 0 No 0 NIA 22. Reinstall system covers Ef Yes 0 No 0 NIA 23. System operational & seals in place d)es 0 No 0 NIA 24. Personnel instructed in manual operation of system Oyes 0 No 0 NIA 25. Portable extinguishers properly serviced e:l Y~s 0 No 0 NIA 26. Service tag on system EJles 0 No 0 NIA 27. Internal Tank Inspection (If Applicable) ~es 0 No D NIA 28. Check Regulator Manufacture Date (If Applicable) 0 Yes D No 0 NIA Location of Gas Valve b eb1' I\ C fv Y "\' ( NOlE DISCREPANCIES OR DEFICIENCIES BELOW