Loading...
HomeMy WebLinkAboutinspector_summary_27321_12-01-2016-3876.pdfInspection Result:Fail Inspector:Charlie Davis Permit Type Inspection Type Address Construction Building Final 1775 SUNBURST DR (210109200006) (210109200006See Plats) Inspection Date:12/01/2016 Permit #:B15-0252 TMK:210109200006See Plats Comments: 1. Balance report on site submit to Town Fire sprinkler and alarm finals required,Fire approval required and on site submit to Town. ANSUL system test docs on site, submit to Town Clear all corridors of construction materials. Second exit and exit sign required out lower level storage. Common path of travel exceeded. Clear exit path at golf cart storage. Elevator must be complete and approved Safety tethers required at kitchen gas appliances on wheels. Hardware required on main level hall exit door Relocate exit sign and install at great room east exit. Check egress/occupant load at bar patio area if occupant load is greater than 50 door swing issues. All temp locks removed at means of egress doors. 2. Inspector Signature 3. Applicant Signature Inspection Summary