HomeMy WebLinkAboutB15-0274_Electrical Load Calcs_1438723560.pdfELECTRIC LOAD SUMMARY Client Name: Berglund Architects, LLC Load Tab Project Name: 165 Forest Road, Vail, CO Project No: 201535 Date: July 28, 2015 165 Forest Road TYPE SQ. FT. Residential 8723 VA/S.F. OR QTY.VA TOTAL NOTES GENERAL LIGHTING LOAD GENERAL LIGHTING 3 26,169 26,169 Per NEC 220.82(B)(1) SMALL APPLIANCE 2 1,500 3,000 Per NEC 220.82(B)(2) LAUNDRY 2 1,500 3,000 Per NEC 220.82(B)(2) TOTAL 32,169 APPLIANCE LOADS Per NEC 220.82(B)(3) & (4) REFRIGERATOR 2 1,440 2,880 REFRIGERATOR DRAWERS 2 1,440 2,880 WINE COOLER 1 1,440 1,440 ICE MAKER 1 1,440 1,440 DISHWASHER 2 1,440 2,880 DISPOSAL 2 1,127 2,254 RANGE HOOD 1 960 960 RANGETOP POWER SUPPLY 1 1,440 1,440 MICROWAVE 1 1,440 1,440 DRYER 2 5,000 10,000 DUAL OVEN 1 8,900 8,900 BOILERS 5 500 2,500 PUMPS 3 1,176 3,528 PUMPS 19 528 10,032 SUMP PUMP 1 650 650 HUMIDIFIERS 4 1,900 7,600 DE-HUMIDIFIERS 1 21,360 21,360 REMOTE CONDENSER 1 1,035 1,035 STEAM GENERATOR 1 1 24,000 24,000 STEAM GENERATOR 2 1 20,000 20,000 EXHAUST & SUPPLY FANS 6 76 456 ERV FANS 2 317 634 DUCT HEATERS 2 1,500 3,000 ELEVATOR 1 5,760 5,760 HOT TUB 2 9,600 19,200 WATER FEATURE 1 1,920 1,920 APPLIANCE TOTAL 158,189 GEN. LTG AND APPLIANCE LOAD 190,358 DEMAND FACTOR NOTES 100% FIRST 10,000 VA 10000 Per NEC 220.82(B) 40% FOR REMAINDER OF LOAD 72143 Per NEC 220.82(B) TOTAL 82,143 AIR CONDITIONING & COOLING CHILLERS 3 7,130 21,390 CHILLER MODULE 1 1,800 1,800 CONDENSING UNITS 2 4,000 8,000 FAN COILS 3 1,920 5,760 FAN COILS 3 1,176 3,528 FAN COILS 1 528 528 HEAT PUMP 1 4,248 4,248 TOTAL 45,254 OVERALL TOTAL (VA) 127,397 Gen. Ltg & Appl. Load + AC 531 AMPS @ 240V, 1-PH 600-AMPS SELECTED FEEDER BASED ON NEC OPTIONAL LOAD CALCULATION