HomeMy WebLinkAboutB15-0308_Load calcs_1440024840.pdf t' P.O.Box 282 Traditional Service.,.today's technology Red Cliff,CO 81649 970-331.-5369 TESLA• ELECTRIC Single Family Optional Service Calculation Address: West Wind#302 _ .—_ Owner: Bill and Monika Markus General Lighting Load 1,050 Sq.Ft. 3 VA 3,150.00 Total Table 220.12,Table Code Refrence Small Appliance 2 QTY 1,500 VA 3,000.00 Total 220.42,220.52(0), Laundry Circuit 1 1,500 VA 1,500.00 Total 220.52(8), Range Demanded Load 1 QTY 8,000 VA 12 KW use SOW,if Demand Factor 8,000.00 Total Table 220.55 Coda Refrance greater than 12 KW add 5%far each Kw Dryer Demanded Load 1 QTY 5,000 VA 5,00 or name plate Demand Factor 5,000.00 Total 220.54,Table 220.54 Code Refrence rating which ever Is Fixed Appliance Demanded Dishwasher 1 QTY 1,200 VA 1,200.00 220.53 Code Refrence Trash Compactor QTY 800 VA 0.00 Ice Machine QTY 1,200 VA 0.00 Fridge 1 QTY 1,000 VA 1,000.00 Freezer 0 QTY 1,000 VA 0.00 Wine Fridge QTY 800 VA 0.00 Hot Tub QTY 4,500 VA 0.00 Juccurzi Tub 0 QTY 2,500 VA 0.00 Scone QTY 3,800 VA 0.00 Steamer QTY 5,000 VA 0.00 lnsta Hat QTY 3,200 VA 0.00 Attie Fan QTY 0.00 Micerwave 1 QTY 1,500 VA 1,500.00 Other: 3,700.00 Total fixed Appliance Heating and A/C Load 0 QTY 3,800 VA 40%of electric 0.00 Total 220.82,(C),(4) Code Refrence space heating if four or more seperatly controlled units 25%of Largest Motor 1QTY 375 VA Motor Load Only- 375.00 Total Code Refrence 100%is already 220.50,430.24,Annex() included in Example 01(b) 24.725-001'....':::,........1.4415.41.. ...:orE _ 10,000.00 First 10KVA of General Load at 100% 220.82 5,890.00 Remainder of General Load at 40% 15,890.00 :: T!} Dii184n+fadll . 240 Single Phase 66.21 Amps • Email:teslavail@gmail.com Phone:970-331-5369