HomeMy WebLinkAboutB15-0308_Load calcs_1440024840.pdf t' P.O.Box 282 Traditional Service.,.today's technology
Red Cliff,CO 81649
970-331.-5369
TESLA•
ELECTRIC
Single Family Optional Service Calculation
Address: West Wind#302 _ .—_
Owner: Bill and Monika Markus
General Lighting Load 1,050 Sq.Ft. 3 VA 3,150.00 Total Table 220.12,Table Code Refrence
Small Appliance 2 QTY 1,500 VA 3,000.00 Total 220.42,220.52(0),
Laundry Circuit 1 1,500 VA 1,500.00 Total 220.52(8),
Range Demanded Load 1 QTY 8,000 VA 12 KW use SOW,if Demand Factor 8,000.00 Total Table 220.55 Coda Refrance
greater than 12 KW
add 5%far each Kw
Dryer Demanded Load 1 QTY 5,000 VA 5,00 or name plate Demand Factor 5,000.00 Total 220.54,Table 220.54 Code Refrence
rating which ever Is
Fixed Appliance Demanded
Dishwasher 1 QTY 1,200 VA 1,200.00 220.53 Code Refrence
Trash Compactor QTY 800 VA 0.00
Ice Machine QTY 1,200 VA 0.00
Fridge 1 QTY 1,000 VA 1,000.00
Freezer 0 QTY 1,000 VA 0.00
Wine Fridge QTY 800 VA 0.00
Hot Tub QTY 4,500 VA 0.00
Juccurzi Tub 0 QTY 2,500 VA 0.00
Scone QTY 3,800 VA 0.00
Steamer QTY 5,000 VA 0.00
lnsta Hat QTY 3,200 VA 0.00
Attie Fan QTY 0.00
Micerwave 1 QTY 1,500 VA 1,500.00
Other:
3,700.00 Total fixed Appliance
Heating and A/C Load 0 QTY 3,800 VA 40%of electric 0.00 Total 220.82,(C),(4) Code Refrence
space heating if
four or more
seperatly
controlled units
25%of Largest Motor 1QTY 375 VA Motor Load Only- 375.00 Total Code Refrence
100%is already 220.50,430.24,Annex()
included in Example 01(b)
24.725-001'....':::,........1.4415.41.. ...:orE _
10,000.00 First 10KVA of General Load at 100% 220.82
5,890.00 Remainder of General Load at 40%
15,890.00 :: T!} Dii184n+fadll .
240 Single Phase
66.21 Amps
•
Email:teslavail@gmail.com Phone:970-331-5369