HomeMy WebLinkAboutB16-0021_ME1.pdfFACILITIES OFFICE, CODING OFFICE, SECURITY, AND GENERAL OFFICE - SUPPLEMENTAL COOLING - MECHANICAL/ELECTRICAL PLAN ME1
PERMIT 2/18/16
VVMC - EAST WING - SUPPLEMENTAL COOLING
OUTDOOR HEATPUMP,
MITSUBISHI MXZ-8C48NAHZ
MOUNTED ON PAD MOUNTED
FRAME TO SUPPORT UNIT 24"
ABOVE FINISH GRADE.
MAINTAIN MANUFACTURER
CLEARANCE REQUIREMENTS.
WALL MOUNTED, NEMA 3R, 50A,
208V, SINGLE PHASE,
NON-FUSED DISCONNECT, FOR
POWER TO HEATPUMP SYSTEM.
CIRCUIT TO LOCAL PANEL 'LPL
- 67,69' WITH 50A, 2-POLE C.B.
WALL MOUNTED INDOOR AIR
CONDITIONING UNIT,
MITSUBISHI MSZ-GE09NA-9
WITH INTEGRAL CONDENSATE
PUMP.
WALL MOUNTED INDOOR AIR
CONDITIONING UNIT,
MITSUBISHI MSZ-GE12NA-9
WITH INTEGRAL CONDENSATE
PUMP.
WALL MOUNTED INDOOR AIR
CONDITIONING UNIT,
MITSUBISHI MSZ-GE09NA-9
WITH INTEGRAL CONDENSATE
PUMP.
WALL MOUNTED INDOOR AIR
CONDITIONING UNIT,
MITSUBISHI MSZ-GE06NA-9
WITH INTEGRAL CONDENSATE
PUMP.
REFRIGERANT PIPING BRANCH
BOX MOUNTED ABOVE
CEILING.
GENERAL NOTES:
1. EXISTING HVAC SYSTEM TO REMAIN IN PLACE TO
PROVIDE VENTILATION AND GENERAL HEATING AND
COOLING TO THE AREA. NEW, SUPPLEMENTAL AIR
CONDITIONING SYSTEM TO SUPPLEMENT THE
EXISITNG SYSTEM.
2. INDOOR AIR CONDITIONING UNITS ARE POWERED
FROM THE OUTDOOR HEAT PUMP UNIT.
3. EXTERIOR HEAT PUMP IS LOCATED IN AN
EXISTING, BACK-OF-HOUSE AREA USED FOR
STORAGE IN THE EAST, ALLEY.
4. PROVIDE 30 DAY POWER MONITORING OF
EXISTING PANEL 'LPL' TO VERIFY CAPACITY.
WALL MOUNTED INDOOR AIR
CONDITIONING UNIT,
MITSUBISHI MSZ-GE06NA-9
WITH INTEGRAL CONDENSATE
PUMP.
ROUTE PUMPED CONDENSATE
LINE ABOVE CEILING FROM
EACH UNIT INDIRECT TO
EXISTING JANITOR SINK.
REFRIGERANT PIPING
ABOVE CEILING TO/FROM
BRANCH BOX TO EACH
INDOOR UNIT, TYP.
NORTH
EAST ELEVATION - HEAT PUMP AND DISCONNECT
- NOT TO SCALE
SOUTH ELEVATION - HEAT PUMP AND
DISCONNECT - NOT TO SCALE
EQUIPMENT MOUNTING
FRAME
HEAT PUMP
ELECTRICAL DISCONNECT
HEAT PUMP
EQUIPMENT MOUNTING FRAME
ELECTRICAL DISCONNECT
OFFICE
CODING OFFICE
FACILITIES
OFFICE
JANITOR
SECURITY
OFFICE
EXISTING GFIC RECEPTACLE.
(E) PANEL
'LPL'- 42
SPACE,
200A,
120/208V,
3 PHASE
PERMIT
COMMENTS
3/8/16
03/30/16