Nedbo Construction October 1,2015
P.O. Box 3419
Vail. CO 81658
ATTN: JimFoley
RE: 380 E. Lionshead Permit # B15-0289
Unit # 320
Vail, Colorado
* Field Inspection
Dear Mr. Foley.
As requested, structural steel special inspection was conducted at the above
referenced project per the IBC 2012 Edition - Chapter 17: Structural Tests and Special
Inspection and the requirements of the Town of Vail. I arrived at the jobsite at 9:00 AM
and again at 2:30 PM. I met with you and Mr. Pat Fox to review areas ready for
inspection and project requirements. The Welding Procedure Specification PAT-FOX-
WPS-TC-U4A dated 3/16/2015. Welder Qualification Test Reports: PAT-F 3 -PAT
ENTERP dated 12/2/2014, and PAT F 1-PAT FOX ENT dated 9/3/2014 for Fox Welding
Inc.. the steel erector for this project, were reviewed and found to be in compliance with
project specifications. Copies are on file with Mr. Fox.
Visual welding inspection was conducted at the Loft Floor Framing Plan Level on
field welded connections on the steel framing for the loft addition in Unit # 320.
Placement of steel can be located on the approved structural drawings provided by KRM
Consultants, Inc.: Job # 1210-04 dated 8-6-15 on Sheet S2. The detail utilized for
inspected was Section 1 on Sheet S1. Inspection revealed that welds had not been
chipped and cleaned so I instructed Mr. Pat Fox on the necessary action needed so
inspection could be properly performed. I returned to the site at 2:30PM after the
corrections had been made. It was found that connections at transfer angles to embed
angles, 2" pipe to transfer angles, and 2"pipe to channel were all fabricated and welded as
detailed and in accordance with project specifications.
PAGE 2
Respectfully Submitted,Revie
Scott Hartzell
AWS CWI #14090301
Thunder Mountain Testing
ScoMDHvtHl
CWI
OC1 EXP*
lax-wen^'
AWS CWI #91040201
ICC Certified #0863569-81 & S2
ASNT NOT Level III #30242
Thunder Mountain Testing
Scon L Maxwell
CWI 91040201
QC1 EXP. 4/1/2018
Reviewed by,
GLENW00D STOUCTURAL AND CIVIL. INC.
AdolWGorra. M.S., P.E.
President