HomeMy WebLinkAboutB16-0056 Test & Balance.pdf TEST, ADJUST AND BALANCE REPORT
PROJECT
VAIL MOUNTAIN SCHOOL
#1217
PREPARED FOR
SKYLINE MECHANICAL
REPORT ISSUE DATE
8/9/2016
PREPARED BY
HVAC TAB I l c
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB IIc
TEST, ADJUST AND BALANCE REPORT
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF
SYSTEM PERFORMANCE AND WAS OBTAINED IN COMPLIANCE WITH
NBC PROCEDURAL STANDARDS. ANY VARIANCES FROM THE DESIGN
REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS
REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE,TO THE
EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED THROUGH-
OUT THIS SURVEY.
THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN
COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING,
ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE
PROJECT SPECIFICATIONS.
CERTIFIED BY: /r7 DATE.: 5/////,'''
/G
THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEASUREMENTS
ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR
TESTING,ADUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS
AND THE PROJECT SPECIFICATIONS.
CERTIFIED BY: s DATE:
HVAC TAB IIc WARRANTS THAT THE AIR AND HYDRONIC SYSTEM
EVALUATED DURING THIS SURVEY IS OPERATING AT THE SPECIFIED LEVELS
AS SHOWN WITHIN THIS REPORT,AT AND ONLY AT THIS TIME. HVAC TAB IIc
MAKES NO OTHER WARRANTIES, STATED OR IMPLIED, CONCERNING THE
CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS
EQUIPMENT PASS THIS TIME.
CERTIFIED
Michael T.Richardson Page: 1
HVAC TAB.LLC
1113.0M-03 Eapke. V22tZil
NATIONAL BALANCING CoUNCil.
HVAC TAB I I c INSTRUMENT
CALIBRATION REPORT
DATE: 8/8/2016
PROJECT: VAIL MOUNTAIN SCHOOL
PROJECT ALTITUDE: 22.4"HG
INSTRUMENT/SERIAL# APPLICATION DATE OF USE CALIBRATION CALIBRATION
DATE DUE DATE
SHORTRIDGE ADM-870C/#M00483 AIR FLOW READINGS 8/8/2016 06/08/2015 06/08/2016
ANEMOMETER WIRE#95351535017 AIR FLOW READINGS 8/8/2016 8/28/2015 8/28/2016
SHORTRIDGE FLOW HOOD AIF FLOW READINGS 8/8/2016 * *
TH-720 HYGROMETER/#TH7200950003 AIR TEMP/HUMIDITY NOT USED 06/03/2015 06/03/2016
PITOT TUBE 18" PRES.READINGS NOT USED N/A N/A
PITOT TUBE 24" PRES.READINGS NOT USED N/A N/A
PITOT TUBE 36" PRES.READINGS NOT USED N/A N/A
PITOT TUBE 48" PRES.READINGS NOT USED NA NA
SHIMPO TACHOMETER /#C 105B0010 RPM READINGS 8/8/2016 06/03/2015 06/03/2016
FLUKE 375/#21290229 VOLT/AMP 8/8/2016 06/03/2015 06/03/2016
SHORTRIDGE HDM-250/#W11037 WATER PRES.READINGS NOT USED 06/08/2015 06/08/2016
ASCROFT/0-100 PSI/#DO68332-06 WATER PRES.READINGS NOT USED * *
FLUKE 52 II THERMOMETER/99780167 TEMP.READINGS NOT USED 06/11/2015 06/11/2016
REFRACTOMETER RHA-100 /#RHA- GLYCOL%READINGS NOT USED N/A N/A
100
•CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR
TEMPERATURE AND ALTITUDE.
PAGE:
MVAC TAB Ilc AIR APPARATUS
TEST REPORT
DATE: 8/8/2016
PROJECT: VAIL MOUNTAIN SCHOOL SYSTEM: AHU-5
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER TRANE MANUFACTURER AO SMITH
MODEL MCCB040UA0A0UA HP R.P.M. 20 1745
SERIAL K04A07216 PHASE FRAME 3 5256T
FAN TYPE CENTRIFUGAL S.F. TYPE 1.15 MOGB
RATING/OUTLET TOTAL - VOLTS AMPS 230/460 49.6/24.8
MIN OSA CFM - THERMALLY PROTECTED -
STARTER DATA DRIVE DATA
MANUFACTURER NONE MOTOR DRIVE 1 FP 6 1/4" S
MODEL NONE MOTOR BORE 1 5/8" S
SIZE/THERMAL NO. NONE FAN DRIVE 2 FP 7 1/8" S
RANGE (HERTZ) NONE FAN BORE 2 1/8" S
SET AT (HERTZ) NONE NO. BELTS & SIZE 2 / 5VX630
REQ. THERMAL NONE ROTATION CORRECT
RATING (AMPS) NONE CENTERLINE MOTOR ADJ PULLEY
21" +9 -4 SPEED -
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY CFM 5318 FAN R.P.M. 1368 1368
OSA CFM - VOLTAGE 479/482/482 479/482/482
RETURN CFM - AMPERAGE 20.1/19.4/20.1 20.1/19.4/20.1
F SWAMP
COI
-1.41" L -1.49" HL -1.57" -2.02" rJ 0.93"
T
E
R
NOTES:
PAGE:
HVAC TAB Ilc AIR TERMINAL
TEST REPORT
DATE: 8/8/2016
PROJECT: VAIL MOUNTAIN SCHOOL SYSTEM: AHU-5A
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
PRE-TAB
NO TYPE SIZE AK VEL CFM ! VEL CFM VEL CFM
AHU-5A 1 CD 15/15 - 238 218
2 CD 15/15 - 250 218
3 CD 15/15 - 264 230
4 CD 15/15 - 266 236
5 CD 15/15 - 270 226
6 15/15 -
CD
-
252 222
7 CD 15/15 - 252 183
8 CD 15/15 - 222 212
9 CD 15/15 - 248 222
10 CD 15/15 - 252 205
11 SR 13/5.5 - 768 608
12 SR 13/5.5 - 569 553
13 SR 13/5.5 - 537 571
14 SR 13/5.5 - 600 608
15 CD 15/15 - 146 152 DAMPER 1000/0
OPEN
16 CD 15/15 - 316 181
17 CD 15/15 - 0 103
18 SR 11/5 - - 146 DAMPER
15/15 CLOSED
19 CD - 224
- 5450 5318 TOTAL
NOTES:
PAGE:
NIV1Nf OV 1IHn
.: :: .94 'U1 j 4";ortm11
t 0 0 0
''' r 6/ 0 I\ 0 t
7
7 10 7.'
‘.. , ----tr r N---- c 0
I -,
,,,,
(.13\ Is:#14 , '
, ,, 1 0
, \
09 , \,---4_-_---..-.-----..,.-,-----
L.__
' Zr,, /I
WI —I 1 e ' '—'
'7./,.A . X —07 N
(Er4 , I(�
,, �.
•
it i / .,
//
\ , ,, .1
/ \ . ,
1 - l..._,
ra'rcr Ff:1,, _ ,
i.LEO � k nii�F
EXIST__DEMO MECHANICAL FLOOR PLA