HomeMy WebLinkAboutB16-0056_M-1.0_1478903415.pdfSINGLE LINE DESCRIPTION DOUBLE LINE
D
D
SPLIT BRANCH TAKE-OFF WITH SQUARE
ELBOW & SPLITTER DAMPER
SPLIT BRANCH TAKE-OFF WITH RADIUS
ELBOW & SPLITTER DAMPER
POSITIVE PRESSURE RISER,
TYPICALLY SUPPLY
NEGATIVE PRESSURE RISER, TYPICALLY
RETURN, EXHAUST OR OUTSIDE AIR
F/S COMBINATION FIRE & SMOKE DAMPER
F/S
FIRE DAMPER
MOTOR OPERATED DAMPER (MOD)
MANUAL VOLUME DAMPER, SINGLE BLADE
DAMPER (SBD) FOR ROUND OR <10" TALL,
OPPOSED BLADE DAMPER (OBD) >10" TALL
BACKDRAFT DAMPER
BDD BDD
SMOKE DAMPER
SMOKE DETECTOR
DUCT SIZE: FIRST NUMBER IS PLAN WIDTH,
SECOND NUMBER IS DEPTH.
24x36
24x36
DUCTWORK LEGEND
SD
SD
PRESSURE REDUCING VALVE
SHOCK ABSORBER
STRAINER W/ BLOW-OFF VALVE
SAFETY RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE W/ PIG TAIL & COCK
THERMOMETER
PRESSURE - TEMP. TAP
AIR VENT
PIPE ANCHOR
FLEXIBLE CONNECTOR
PIPE EXPANSION JOINT
PIPE UNION
DOUBLE CHECK BACKFLOW PREVENTER
PUMP & EQUIPMENT CONNECTOR
TEMPERATURE CONTROL VALVE (2-WAY)
DRAIN VALVE W/ HOSE END
PLUG VALVE IN RISER
FLOW BALANCING VALVE
GATE OR GLOBE VALVE IN RISER
FLOW CONTROL VALVE
BALL VALVE
PLUG OR BALANCING VALVE
CHECK VALVE
GLOBE VALVE
BUTTERFLY VALVE
VENTURI/FLOW INDICATOR
TEMPERATURE CONTROL VALVE (3-WAY)
SOLENOID VALVE
90° ELBOW UP
TEE UP
TEE DOWN
SHUT OFF (BALL, GATE, BUTTERFLY)
PIPING SYMBOLS
90° ELBOW DN
S
DUCT/PIPE RISER DESIGNATION KEY
CH
DW
HW
G
W V
PR
ST
S2
FLOW SWITCH
HOSE BIBB
WALL HYDRANT
TEMPERATURE CONTROLLER OR SENSOR
STEAM TRAP TEST CHAMBER
STEAM TRAP:
FT-FLOAT & THERMOSTATIC
TD-THERMODYNAMIC
IB-INVERTED BUCKET
TS-THERMOSTATIC
BP-BALANCED PRESSURE
BAR SINK BS 1/2" 1/2"
1-1/2" 1-1/2"
FIXTURE CONNECTION SCHEDULE
HW CW WASTE VENT
:
1. SIZES SHOWN ARE MINIMUM PIPE SIZES TO A SINGLE FIXTURE. LARGER
SIZES MAY BE INDICATED ON PLANS WHERE REQUIRED.
2. MINIMUM DOMESTIC PIPE SIZE TO (2) OR MORE FIXTURES IS 3/4".
3. RE: MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR INDIRECT WASTE
SIZES.
4. WASTE AND VENT SIZES SHOWN ABOVE APPLY TO INDIVIDUAL VENTING ONLY.
WHERE ALLOWED, INDIVIDUAL VENT CONNECTIONS MAY BE OMITTED OR
SIZES MAY VARY WHEN CIRCUIT VENTS, COMMON VENTS, WASTE STACK
VENTS, WET VENTS, OR COMBINATION DRAIN AND VENT SYSTEMS ARE USED.
PRIOR APPROVAL FROM THE ENGINEER IS REQUIRED TO USE THESE
ALTERNATIVE VENTING METHODS.
5. PROVIDE TRAP PRIMER FOR ALL FLOOR DRAINS AND FLOOR SINKS NOT
LOCATED IN FOOD SERVICE AREAS.
6. MINIMUM SIZE FOR WASTE AND VENT PIPING BENEATH SLAB IS 2".
7. ALL FIXTURES LISTED ARE NOT NECESSARILY USED ON THIS PROJECT.
8. REFER TO APPLIANCE SCHEDULES (BY OTHERS) FOR ADDITIONAL PLUMBING
FIXTURE CONNECTIONS SUCH AS INST-HOTS, COFFEE MAKERS, AND
GARBAGE DISPOSALS.
9. PROVIDE ICE MAKER BOX ROUGH IN W/ 1/2"CW CONNECTION FOR ALL
REFRIGERATOR LOCATIONS.
ABBREV.
CS CLOTHES WASHER ROUGH-IN 1/2" 1/2" 2" 1-1/2"
DRINKING FOUNTAIN / E.W.C. DF - 1/2" 1-1/2" 1-1/2"
DISH MACHINE ROUGH-IN DM 3/4" 3/4" 2" 1-1/2"
DW DISHWASHER ROUGH-IN - 1/2" 2" 1-1/2"
FD FLOOR DRAIN - - 2" 1-1/2"
FS FLOOR SINK - - 3" 2"
HOSE BIB HB - - -3/4"
HAND SINK HS 1-1/2" 1-1/2"
1/2" 1/2"
KITCHEN SINK W/ OR W/O DISPOSER KS 1/2" 1/2" 2" 1-1/2"
LAVATORY LAV 1/2" 1-1/2" 1-1/2"
1/2"
MOP SERVICE BASIN MSB 3/4" 3" 2"
3/4"
SHOWER / BATHTUB SH 3/4" 3/4" 2" 1-1/2"
SERVICE SINK SS 3" 2"
1/2" 1/2"
TROUGH DRAIN TD - - 3" 2"
URINAL (BLOWOUT) UR 1" 2" 1-1/2"
-
URINAL (WASHDOWN)
UR
UR URINAL (WATERLESS)
3/4" 2" 1-1/2"
- 2" 1-1/2"
-
-
WATER CLOSET (FLUSH VALVE)
WC
WATER CLOSET (FLUSH TANK)
WCT
- 1" 4" 2"
- 1/2" 4" 2"
WS
3/4" 3/4" 2" 1-1/2"
WORK SINK
EQUIPMENT ABBREVIATIONS
AIR HANDLING UNIT
AHU
AIR SEPARATOR
AS
BOILER (HOT WATER)
B
BASE BOARD
BB
BUFFER TANK
BT
CONSTANT VOLUME BOX
CV
DISHWASHER EXHAUST FAN
DEF
ELECTRIC BASEBOARD HEATER
EBH
FURNACE
F
FAN COIL
FC
FAN POWERED BOX
FP
GLYCOL FEEDER
GF
HUMIDIFIER
HC HEATING COIL
HP HEAT PUMP
HX HEAT EXCHANGER
KITCHEN EXHAUST FAN
KEF
MAKE-UP AIR UNIT
MAU
MOTOR CONTROL CENTER
MCC
MIXING VALVE
MV
PUMP
P
RETURN (OR RELIEF) AIR FAN
RF
RADIANT ZONE
RZ
SNOWMELT AREA
SA
SUMP BASIN
SB
SUPPLY FAN
SF
STORAGE TANK
ST
THERMOSTATIC MIXING VALVE
TMV
UNIT HEATER
UH
VARIABLE VOLUME BOX
VV
WATER HEATER
WH
H
CHILLER
CH
COILING COIL
CC
CIRC PUMP
CP
CABINET UNIT HEATER
CUH
COOLING TOWER
CT
DUCT COIL
DC
ELECTRIC WATER HEATER
EWH
EVAPORATIVE COOLING UNIT
ECU
ENERGY RECOVERY UNIT
ERU
EXHAUST FAN
EF
EXPANSION TANK
ET
VARIABLE VOLUME BOX W/ REHEAT
VR
TYPE OF AIR DEVICE
RE: GRD SCHEDULE.
AIR DEVICE DESIGNATION KEY
#
CA
EXH
OSA
RA
XFR
SIZE (INCHES) OR MINIMUM
FREE AREA REQUIRED IN
SQUARE FEET.
:
FOR STANDARD MODULE SIZE REGISTERS, SIZE GIVEN IS
NECK SIZE. REFER TO GRD SCHEDULE FOR MODULE SIZE.
INDICATES AIR
INLET DEVICE.
=
=
=
=
=
=
AIR QUANTITY (CFM)
COMBUSTION AIR
EXHAUST
OUTSIDE AIR
RETURN
TRANSFER
B
XFR
12x6
A
150
12x6
REFERENCE SAMPLE
FFI = FOR FURTHER INFORMATION
FCT = FOR CONTINUATION
RE: B/M400 FFI
REFER TO:
DRAWING NUMBER OR
DIAGRAM LETTER
SHEET NUMBER
PLAN ABBREVIATIONS
ABOVE FINISHED FLOOR
AIR ADMITTANCE VALVE
ABOVE FINISHED GRADE
AUTOMATIC
BUILDING CONTROL SYSTEM
BACK DRAFT DAMPER
BUILDING
AAV
AFF
AFG
AUTO
BCS
BDD
BLDG
BETWEEN
COMMON (OR CLOSED)
COMBUSTION AIR
CONTROLS CONTRACTOR
CONTINUATION DESIGN BUILD
B/N
C
CA
CC
CDBBC
CUBIC FEET PER MINUTE (AIR FLOW RATE)
CAST IN PLACE
CEILING (OR COOLING)
CONCRETE
CONDENSATE
CONNECT (OR CONNECTION)
CONTRACTOR
CFM
CIP
CLG
CONC
COND
CONN
CONTR'R
CLEANOUT TO GRADE
COTG
DOMESTIC HOT WATER RECIRC
EXISTING
DWR
(E)
EXHAUST AIR
EA
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR
ENTERING WATER TEMPERATURE
EAT
EC
EXH EXHAUST
EWT
GENERAL CONTRACTOR
GROUND HEAT EXCHANGER
GC
GHX
GALLONS PER MINUTE (WATER FLOW RATE)
GPM
HORSEPOWER
HOT WATER
IN LIEU OF
HP
HW
ILO
KILOWATTS
KW
LEAVING AIR TEMPERATURE
LINEAR FOOT
LEAVING WATER TEMPERATURE
LAT
LF
LWT
MECHANICAL CONTRACTOR
MC
MANUFACTURER
MOTOR OPERATED DAMPER
NEW
MFG
MOD
(N)
NORMALLY CLOSED
NC
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NORMALLY OPEN
NEC
NIC
NO
OUTSIDE AIR
OA
OPPOSED BLADE VOLUME DAMPER
ON CENTER
OBD
OC
OUTSIDE AIR
OSA
RETURN AIR
REQUIRED
RA
REQ'D
REQUIREMENTS
REQ'MTS
SUPPLY AIR
SQUARE FOOT (FEET)
SA
SF
STATIC PRESSURE
SP
STAINLESS STEEL
THROW-AWAY (TRANSFER AIR)
TYPICAL
SS
TA
TYP
UNLESS NOTED OTHERWISE
UNO
WALL CLEANOUT
WCO
WITH REGARD TO
WATER COOLED
TRANSFER
WRT
W/C
XFR
DIAMETER
Ø
BY CONTRACTOR
COLD WATER
CW
HOT WATER RECIRC
HWC
ABOVE
ABV
BELOW FINISHED GRADE
BFG
DOMESTIC WATER
DOMESTIC HOT WATER
DW
DHW
DOWN
DN
DOMESTIC HOT WATER RECIRC
DHR
COMBINATION FIRE/SMOKE DAMPER
FURNISHED BY OWNER
FSD
FBO
FLOOR CLEANOUT
FCO
FOR CONTINUATION
FCT
FD FIRE DAMPER
REFER TO:
RE:
WITH
W/
CLEANOUT
CO
FUTURE
(F)
FREE AREA
FA
FFI FOR FURTHER INFORMATION
WITHOUT
W/O
VENT THRU ROOF
VTR
NOTES
1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS
ON LEGEND SHEET ARE NOT NECESSARILY USED ON
THIS PROJECT.
2. THIS DRAWING SET CONSISTS OF DATA GENERATED, IN
PART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES AND
NOTATION CONVENTIONS OCCURRING IN THIS
DRAWING SET ARE NECESSARILY DEFINED ON THESE
LEGENDS. CONSULT THE ENGINEER IN THE EVENT
SYMBOLOGY OR NOTATION INTERPRETATION IS
REQUIRED.
EA
OA
RA
SA
RISER NUMBER
-
-
-
-
-
-
-
-
-
-
-
-
CHILLED WATER
DOMESTIC WATER
HEATING WATER
GAS
WASTE AND/OR VENT
PIPING RISER (MISC TYPES)
STORM DRAIN
SECONDARY STORM DRAIN
EXHAUST AIR
OUTSIDE AIR
RETURN AIR
SUPPLY AIR
:
:
PLAN SYMBOLS
CONTROL PANEL/RADIANT MANIFOLD
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
DIAGRAM CONTINUATION REFERENCE
PLUMBING/HVAC RISER
POINT OF NEW CONNECTION
DUCT STATIC PRESSURE SENSOR
ROOM PRESSURE SENSOR
EMERGENCY POWER OFF SWITCH
ACCESS PANEL
SNOWMELT MANIFOLD
SECTION CUT LETTER/SHEET SHOWN ON
POINT OF DISCONNECTION
-
SP
CO2
EPO
P
CO
--
-
P
THERMOSTAT
HUMIDISTAT
REMOTE TEMPERATURE SENSOR
T
S
H
H B
W H
TC
FS
ROOF DRAIN
FLOOR DRAIN
FLOOR SINK
HORIZONTAL CLEANOUT
VERTICAL CLEANOUT
DECK/ROOF DRAIN ABOVE
PIPING DESIGNATIONS
SNOWMELT SUPPLY
SNOWMELT RETURN
HEATING WATER SUPPLY (HIGH TEMP)
HEATING WATER RETURN (HIGH TEMP)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSER RETURN
NATURAL GAS
MEDIUM PRESSURE GAS
HIGH PRESSURE STEAM
HIGH PRESSURE CONDENSATE RETURN
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE RETURN
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DOMESTIC WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER (TEMP. SHOWN)
DHW RECIRCULATION
FIRE LINE
PRESSURIZED WASTE
PLUMBING VENT PIPE
WASTE PIPE
ACID WASTE PIPE
STORM DRAIN PIPE
STORM DRAIN OVERFLOW
COMPRESSED AIR PIPE
GREASE WASTE PIPE
ACID VENT PIPE
LIQUID PROPANE GAS
SECONDARY DRAIN
SAND AND OIL WASTE
FLOOR COOLING SUPPLY
FLOOR COOLING RETURN
PROPANE GAS
HEATING WATER SUPPLY (LOW TEMP)
HEATING WATER RETURN (LOW TEMP)
SOLAR HEATING WATER SUPPLY
SOLAR HEATING WATER RETURN
GROUND LOOP SUPPLY
GROUND LOOP RETURN
GROUND WATER SUPPLY
GROUND WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
DRAIN PIPE
FUEL OIL SUPPLY
FUEL OIL RETURN
GLYCOL FEED
GREASE VENT
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE RETURN
FUEL OIL VENT
FUEL OIL FILL
PUMPED CONDENSATE
GEOTHERMAL (OR GROUND) LOOP SUPPLY
GEOTHERMAL (OR GROUND) LOOP RETURN
CLOSED CONDENSER SUPPLY
CLOSED CONDENSER RETURN
PROPANE DRAIN
CONDENSER SUPPLY
PLUMBING PIPING
NON-SOFTENED DOMESTIC WATER
CR
CS
CCR
CCS
GLR
GLS
CHR
CHS
GLR
GLS
GF
HWR
HWS
HWR(LT)
HWS(LT)
HWR(HT)
HWS(HT)
FCR
FCS
SHWR
SHWS
SMS
SMR
PC
MPR
MPS
LPS
LPR
HPR
HPS
PD
D
PG
LPG
MG
G
RS
RL
FOF
FOV
FOR
FOS
GWR
GWS
CW
HW
HWC
NS
140° HW
GV
SO
SD
ST
GW
AW
AV
V
W
PW
ST(OF)
F
CA
SOLID DRAIN PIPE
DS
STEAM & CONDENSATE PIPING
HYDRONIC PIPING
90° ELBOW DOWN (ROUND DUCT ONLY)
ROUND 90° ELBOW UP (ROUND DUCT ONLY)
OFFSET TO CHANGE ELEVATION
(AT 30° WHEN POSSIBLE)
D = DROP R = RISE
ROUND RADIUS ELBOW
90° STRAIGHT TEE
90° CONICAL TEE
45° BRANCH
45° CONICAL TEE
SIZE OR SHAPE TRANSITION
ROUND FLEXIBLE DUCT
90° ELBOW DN (NEGATIVE PRESSURE)
90° ELBOW DN (POSITIVE PRESSURE)
90° ELBOW UP (NEGATIVE PRESSURE)
90° ELBOW UP (POSITIVE PRESSURE)
90° RADIUS ELBOW
90° RADIUS ELBOW W/TURNING VANES
SQUARE DUCT SPLIT
ROUND DUCT SPLIT
SUMP PUMP
SP
PR
203
MECHANICAL SYSTEMS LEGEND
ABOVE SEA LEVEL
PROJECT ALTITUDE
8400'
GRILLE, REGISTER, DIFFUSER & LOUVER
SYMBOL USE PATTERN FINISH
MANUFACTURER*
& MODEL #
ACCESSORIES REMARKS
SUPPLY CEILING, 4-WAY WHITE
TITUS
TDC
-CONNECTION SIZE TO MATCH
DUCT SIZE SHOWN ON PLAN
RETURN CEILING,
PERFORATED
WHITE
TITUS
PAR
- -
- - - - - - -
MANUFACTURERS:
GRD KRUEGER, METALAIRE, TITUS
LOUVER GREENHECK, L&D, RUSKIN
GENERAL NOTES:
A:
B:
A
BBBBB
CEILING DIFFUSER
NO SCALE
TYPICAL DIFFUSER CONNECTION DIAGRAM
EXTERIOR DUCT
INSULATION.
INSULATED ACOUSTIC
FLEX DUCT.
INTERNALLY LINED SUPPLY
DUCT, OR AS NOTED IN
SPECIFICATIONS.
CONICAL SPIN-IN FITTING WITH
MANUAL VOLUME DAMPER.
SHEET METAL
STRAP.
S.S. WORM DRIVE
CLAMP.
SQUARE TO ROUND ADAPTER
AS REQUIRED.
SHEET METAL
SHIELD.
SUPPORT AS REQUIRED
FOR MIN RADIUS
SPECIFIED.
MINIMUM ℄ RADIUS 1.5
x FLEX DUCT DIAMETER.
A
GENERAL NOTES (MECHANICAL SPECIFICATIONS):
1. Do not scale drawings. Verify dimensions in field prior to commencement of work. Refer to architectural drawings for all dimensions.
2. All subcontractors shall be licensed, experienced, and thoroughly knowledgeable in their respective areas of the construction industry and shall perform in a responsible
manner with established construction sequence, shall recognize the priority of the construction documents, and shall inform the prime contractor of potential problems
when the construction documents are unclear or inconsistent.
3. Subcontractors shall be responsible to notify the prime contractor of discrepancies or conflicts in the construction documents found during bidding and/or prior to
performing the work.
4. Examination of bidding documents.
A. Each bidder shall examine the bidding documents carefully, and not later than seven (7) days prior to the date of receipt of bids, shall make written request to the
architect for interpretation or correction of any discrepancies, ambiguities, inconsistencies, or errors therein which he may discover. The architect will issue any
interpretation or correction as an addendum. Only a written interpretation or correction by addendum shall be binding. No bidder shall rely upon interpretations or
corrections given by any other method. If discrepancies, ambiguities, inconsistencies, or errors are not covered by addendum or written directive, contractor shall
include in his bid, labor materials and methods of construction resulting in higher cost. After award of contract, no allowance or extra compensation will be made on
behalf of the contractor due to his failure to make the written requests as described above.
B. Failure to request clarification during the bid period of any inadequacy, omission, or conflict will not relieve the contractor of his responsibilities. The signing of the
contract will be considered as implicitly denoting that the contractor has a thorough comprehension of the full intent and scope of the construction contract drawings
and specifications.
5. Provide a base bid which shall include only specified equipment or equipment listed as equivalent. No substitutions for the listed equipment shall be allowed in the base
bid.
A. The manufacturer of equipment or materials first named on the drawings is the basis of design. Other manufacturers listed are considered general equivalents only.
B. Coordination of general equivalents and substitutions: where contract documents permit selection from several general equivalents, or where substitutions are
authorized, coordinate clearance and other interface requirements with mechanical and other work.
1) Provide necessary additional items so that selected or substituted item operates equivalent to the basis of design and properly fits in the available space
allocated for the basis of design.
2) Provide all features which are standard on the basis of design plus any specified options.
3) Be responsible for assuring that piping, conduit, duct, flue, and other service locations for general equivalents or substitutions do not cause access, service, or
operational difficulties any greater that would be encountered with the base design.
6. Inasmuch as design for remodel and/or rehabilitation requires that certain assumptions be made regarding existing conditions, and because some of these assumptions
cannot be verified without destroying otherwise adequate or serviceable portions of the building, the Engineer cannot assure the Owner or the contractor that the
professional consulting services herein encompass all contingencies. Field coordination during construction is imperative. Make reasonable allowances for unseen
conditions.
7. The existing building will be occupied by the Owner during construction. Continued operation of the facility shall not be hindered by this work. Account for all additional
costs which may be incurred due to the difficulty of working over and around employees, furniture, equipment, etc.; and due to the hours of the day in which an area may
be accessible when compiling this bid.
8. Be responsible to field verify existing equipment or ductwork remaining to be connected to existing systems. Provide ductwork, piping, controls, diffusers, etc., as
required to restore continuity of system(s), or to make new work meet existing conditions, whether indicated or not.
9. Subcontractor shall verify existence and location of all utility services and coordinate as required by their respective area of the construction, notifying the prime
contractor of variations or conflicts.
10. If not specifically defined in these construction documents, materials and/or equipment shall be identified by the subcontractor with sufficient time to allow selection,
purchase, and delivery to maintain construction schedule.
11. Provide mechanical demolition as required. Refer to architectural demolition drawings for location and extent of demolition required. Visit site prior to bid to determine
extent of work involved. Existing fixtures, mechanical equipment, etc., being removed shall be returned to the Owner. Dispose of all removed piping, ductwork, etc.
unless noted otherwise. Pipes, ductwork, equipment, etc. To be removed, are shown hatched, unless otherwise noted.
12. All ductwork, diffusers, piping, fixtures, and equipment shown in light line weight is existing, new indicated by heavier line weight, except where noted. Pipes, ductwork,
equipment, etc. To be removed, are shown hatched.
13. Offset piping, ductwork, etc. As necessary to accommodate structure, beams, and columns, and existing equipment.
14. All existing support rods and straps now supporting ducts, pipes, air tubing, electrical conduit, etc. that are removed to allow room for installation of new ductwork shall
be relocated and reinstalled, or replaced if damaged.
15. Cap all demolished and abandoned duct take-offs at trunk duct.
16. Work shall be performed in a workmanlike manner to the satisfaction of the architect, Owner, and Engineer.
17. It is the contractor's responsibility to perform his/her work in conformance with all applicable codes, ordinances and life safety features as required by local, state, or
national authorities. The contractor shall verify with the architect if modification of his/her work is required for compliance.
18. All work of all trades must be in strict compliance, or exceed the minimum material and method requirements of the 2015 version of the International Building,
Mechanical, Energy Conservation, and Fire Codes; the 2012 International Plumbing and Fuel Gas codes; and the 2014 National Electrical Code, most current NFPA, all
local ordinances and amendments and manufacturer's installation recommendations. If a conflict between those publications exists, the most stringent requirement shall
apply.
19. Pay for and secure all required permits and inspections. Prior to final payment, turn over to architect all certificates of completion.
20. Warranty the installation against defects in materials and workmanship. The warranty shall be for a period of one year after Owner's acceptance. Defects shall be
promptly remedied without cost to the Owner.
21. Submit record documents to architect. Documents shall include all addendum items, change orders, alterations, reroutings, etc.
22. Systems shall be complete, operable, and ready for continuous operation prior to acceptance by the Owner.
23. Systems shall be tested for proper operation. Perform at a minimum all code required tests or systems. If tests of work are defective, contractor shall make corrections
necessary at no additional cost to Owner.
24. All materials and/or equipment shall be handled and installed as per manufacturer's specifications and recommendations.
25. Submit all mechanical division shop drawing and product data at one time. Partial submittals will be rejected.
26. Shop drawing submittals shall state capacities, sizes, etc., of all equipment and devices and shall be certified and include computer based project specific selections
where applicable. Clearly mark each shop drawing, catalog cut and/or specification sheet to indicate those products and features which are intended to be furnished.
Specifically indicate any deviations from the design intent. Engineer reserves the right to require correction at no cost to Owner for deviations not specifically indicated in
the submittals. Review and approval of shop drawings shall not relieve the Contractor from the responsibility of furnishing equipment and materials of proper dimension,
size, quantity, quality and all performance characteristics to efficiently perform the requirements and intent of the contract documents. Submittal shall be bound and
indexed in a neat and orderly manner.
27. Submittals shall include, but not be limited to: equipment, fixtures, insulation, diffusers, and controls.
28. Failure to order, or release order for materials and/or equipment will not be accepted as a reason to substitute alternate materials, equipment, or installation methods.
29. Repair all accidental or intentional damage to match existing construction with no noticeable difference in continuity, appearance or function.
30. Temporary heat shall be furnished by the general contractor. Use of the permanent heating system will not be allowed.
31. See architectural reflected ceiling plan for all ceiling penetrations and air device locations.
32. Coordinate architectural, structural, mechanical, fire protection, electrical, landscaping, and interior design drawings prior to installation.
33. No alteration to existing controls or controls devices is anticipated. If locations of stats are altered, mount all stats at 48” AFF In “accessible” areas, 4'6” AFF In other
areas, unless noted otherwise. Coordinate location with wall finish, and to avoid casework, furniture, door swings, heat sources, and exterior walls. Notify Engineer of
any conflicts prior to beginning thermostat installation.
34. Submit a written balance report by a NEBB or AABC certified balancing contractor. Balancing procedures shall be in accordance with NEBB or AABC guidelines for
proportional balance. Submit report on standard NEBB forms or submit forms for review prior to balancing. Measurements shall include pitot tube measurement of
supply and return air main ducts, air inlet and outlets.
A. Provide belts and sheaves as required for drive changes to adjust fan speed.
B. Adjust flows to within 10% of required quantity. Where room air pressure relationship are required to be maintained as shown by a differential of supply and
exhaust/return or by note, adjust supply to within 10% and then adjust exhaust/return to provide the indicated room pressure. If actual quantity is less than 90%,
investigate cause, attempt to rectify and notify Engineer. Submittal of balance report with less than required flows without explanation is cause for rejection of
report.
C. Submit three (3) copies of all submittals in addition to any required by the contractor and his suppliers. These copies shall be retained by the Owner, Architect, and
Engineer.
35. Ductwork:
A. Flexible ductwork shall have an outer jacket of fire retardant polyethylene vapor barrier material, uniform layer of fiberglass insulation, high-strength galvanized steel
helix encapsulated in reinforced “rip stop” aluminum laminate interior core, UL listed and labeled, class 1 air duct. Working pressure rating: positive 6”, negative 4”.
Flexmaster Type 5 or equivalent. Submit samples to determine equivalence.
B. Flexible connection: Equivalent to Ventfab, fireproof glass cloth, 10” w.c. Rated.
C. Round duct: Spiral seam, galvanized steel. Die stamped or 5 gore elbows. “Snap-Lock”, longitudinal seam duct, or adjustable fittings are acceptable on individual
grille/diffuser runouts only.
D. Liner:
1) Line all supply, outside air, return air ducts, exhaust air risers, and make up air risers with 1”, 1.5 lb/CF, black matte coated insulating duct liner.
2) Liner shall be coated and sealed and shall meet ASTM C1071.
3) Material shall meet all requirements of NFPA-90.
4) Install with adhesive and welded pins in accordance with SMACNA “HVAC Duct Construction Standards”.
5) Externally wrap all round supply air ducts with flexible glass fiber, ANSI/ASTM C612; 0.002 inch foil scrim facing.
E. Ductwork: G60 galvanized sheet steel; lock forming quality; constructed to the latest edition of SMACNA “HVAC Duct Construction Standards”; +/- 1” WC pressure
classification, seal class “C”; with galvanized steel fasteners, anchors, angles, straps, etc.
F. Seal all seams (longitudinal and transverse) airtight with united McGill “Uni-Grip” UL listed, water based, non-hardening, elastic sealant or equivalent. Tape not
allowed.
36. All ductwork dimensions are outside sheet metal dimensions. Duct liner has been accounted for.
37. Ductwork notes:
A. Diffuser neck size is same as flexible duct size.
B. Unless otherwise noted, all changes in direction shall be made with radius elbows with radius to centerline equal to 1.5 duct width.
1) Where required for space constraints, provide square throat elbows with single width (non-airfoil) turning vanes.
2) For duct depths of 36” or less, provide manufactured single width (non-airfoil) turning vanes, with spacing in accordance with SMACNA duct construction
standards for “standard spacing”. Use double thickness blades for duct depths greater than 36”. Use no trailing edges.
C. All flexible ducts shall not exceed eight feet in length.
D. Return air plenum: The HVAC system will use the space above the ceiling on each floor as a return air plenum. Conform to the requirements of NFPA and local
code requirements for all material installed in the return air plenum. Provide a complete return air path between all return air devices (grilles etc.) and their
respective HVAC unit. Maximum velocity of return air in plenum shall generally not exceed 250 feet per minute, nor exceed 750 feet per minute at any cross-section
of the return air path.
CONSULTANT:
ISSUE:
OWNER:
PROJECT:
DRAWING INFORMATION:
DRAWN BY:
PROJECT NO:
SHEET TITLE:
APPROVED BY:
CHECKED BY:
SHEET OF
1 2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
P 303.607.0977
www.hcm2.com
1331 Nineteenth Street
Denver, CO. 80202
3/17/2016
4:10:34
PM
C:\Revit
Local
Files\11529_Vail
Mountain School_Central_rferrara.rvt
VAIL MOUNTAIN
SCHOOL
VAIL MOUNTAIN
SCHOOL
Checker
Author
11529.000
Approver
3000 BOOTH FALLS RD
VAIL, CO 81657
3000 BOOTH FALLS RD
VAIL, CO 81657
03/15/16 ISSUED FOR CONSTRUCTION
DOCUMENTS
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. xxxx.xx Copyright 2016
M-1.0
MECHANICAL COVER
SHEET
DRP
JMH
MECHANICAL COVER SHEET
05/24/16