Loading...
HomeMy WebLinkAboutB16-0029_E1.0_1479389569.pdfT 18[(4 #500 MCM AL)3 1/2"C] UTILITY TRANSFORMER PAD MOUNTED HOUSE DISTRIBUTION CENTER "HDC" 3000A, 120/208V, 3P, 4W 42kAlC 2500/3 FRN-R (3)2500A HOLY CROSS METER# 95758 MAX DEMAND: 257KW FEB 2011 800/3 KRP-C (3)800A 1200/3 KRP-C (3)1000A 100/3 FRN-R (3)100A 400/3 FRN-R (3)250A DH14 HA HB HD HE DH (SPARE) PH KITCHEN H20 HEAT AH SPARE KP2 KP1 100/3 FRN-R (3)100A 200/3 FRN-R (3)200A 400/3 FRN-R (3)400A 400/3 FRN-R (3)400A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 200/3 FRN-R (3)200A 100/3 FRN-R (3)100A WEST METERBANK "WEST MB" 1200A, 120/208V, 3P, 4W 42kAlC EAST SLOPESIDE METERBANK "EAST SS MB" 1200A, 120/208V, 3P, 4W 42kAlC EAST POOL SIDE METERBANK "EAST PS MB" 1200A, 120/208V, 3P, 4W 42kAlC 1200/3 KRP-C (3)1000A 600/3 FRN-R (3)600A HOLY CROSS METER# 94722 MAX DEMAND: 19.5KW DEC 2009 ADDITION TO MAIN SERVICE 3[(3 #500 MCM AL, 1 #3/0 NEU. AL, 1 #2/0 CUG)3 1/2"C] 3[(3 #500 MCM AL, 1 #3/0 NEU. AL, 1 #2/0 CUG)3 1/2"C] 3[(3 #400 MCM AL, 1 #2/0 NEU. AL, 1 #1/0 CUG)3 1/2"C] 2[(3 #500 MCM AL, 1 #3/0 NEU. AL, 1 #2/0 CUG)3 1/2"C] 5000A, 120/208V, 3P, 4W 65kAlC ELEVATOR #1 15 FLA, 480V 3P ST 60/3 (3 #3/0 CU, 1 #6 CUG)2"C EXISTING (3 #1 CU, 1 #8 CU G)1-1/2"C EXISTING 15 KVA 208V TO 480V 3P (3 #6 CU, 1 #10 CUG)1"C (3 #8 CU, 1 #8 CUG)1"C #8 CU ELEVATOR #1 15 FLA, 480V 3P ST 60/3 15 KVA 208V TO 480V 3P #8 CU ELEVATOR #1 15 FLA, 480V 3P ST 60/3 15 KVA 208V TO 480V 3P #8 CU EM(E) PANEL ST 60/2 ELEVATOR PANEL ELEVATOR PANEL ST 60/2 (3 #6 CU, 1 #10 CUG)1"C (3 #6 CU, 1 #10 CUG)1"C 49944,AIC X 59,600 AIC X 37000 AIC X <10K AIC X <10K AIC X <10K AIC X <10K AIC X <10K AIC X <10K AIC X <10K AIC X <10K AIC X <10K AIC X NEW WORK IS CLOUDED REST IS EXISTING P PANEL P1 PANEL POOL PANEL <10K AIC X <10K AIC X <10K AIC X (4 #350 AL, 1 #1/0 ALG)3"C (4 #4/0 AL, 1 #2 ALG)2"C RELOCATE EXISTING PANEL EXTEND FEEDER AS REQUIRED REFERENCE PANEL SCHEDULE FOR NEW LOADS PROVIDE FEED THROUGH LUGS TO FEED PANEL P1. REFERENCE PANEL SCHEDULE FOR NEW LOADS equipment, etc. furnish by mechanical - refer to both electrical and electrical apparatus as shown on single line diagram and and mechanical drawing for scope and work and additinal infor- Complete connection of HVAC/Plumbing motor(s), water heater(s), Fire alarm system will be by others. Complete provision, installation and connection of lighting fixtures, exit signs and lamps as specified and as shown on drawings. Complete branch circuit wiring required for the connection of emergency lighting and exit signs to existing emergency stand Complete feeder(s) installation as required for new and/or devices, new control devices, etc. for a complete lighting and including new panelboards, new conduits, new wires, new wiring Complete wiring system for new lighting and power as shown, contract. Electrical work shall include, but not limited to, these major as indicated on drawing and as specified, as necessary to complete the SCOPE: Furnish all materials and labor required to execute this work 2. 3. 4. 6. 5. Provide grounding and bonding Facilities. Complete all electrical demolition as required. mation. A. ELECTRICAL SPECIFICATIONS 1. drawings. by power system. and power system. b. a. items: A. Contractor shall submit shop drawings for engineer review and approval. MC cable permitted per local codes. Run hard pipe from panel to local Lighting fixtures. Shop drawing submittal shall include: Panelboard(s). CONDUIT AND WIRE: B. 13. A. B. 2. 1. and contractor shall have written approvals from building owner prior Core drilling and patching of existing building structure required for Operating, Maintenance and identification instructions manuals, if electrical work. Core drilling shall follow Building Standard procedures Applicable codes: National Electric Code (2011) PERMITS AND FEES: Obtain and pay for all necessary permits, inspec- tions, examinations and fees or charges necessary for execution and and to the requirements of Federal, State or other City agencies Town of Vail Electrical Code, pertinent NFPA publications Conform to the prevailing edition and amendments thereto of the SHOP DRAWINGS AND SUBMITTAL: to start of any work. Test of entire system and work. REGULATIONS AND CODES: having jurisdiction. completion of electrical work. 12. 11. A. 7. 9. 8. 10. any. A. General Requirements 14. decora style, 15 amp will be acceptable for Residences. Convenience receptacles will be 20 amp, commercial grade Light switches will be 20 amp, commercial grade, B. ELECTRICAL DEVICES A. decora style. Finish per owner or architect. Provide decora style, finish per owner or architect. Dimming switches will be a minimum of 600w or as noted. C. 15. Support all electrical equipment independent of accessible ceilings as required by NEC. SUPPORT A. All mounting heights will conform to ADA guidelines. Typical receptacle D. heights will be +18"AFF and switch heights will be +46"AFF unless noted otherwise. 16. At fire rated wall space electrical boxes at opposite sides of the wall no less than 24" horizontal distance. ELECTRICAL BOXES A. When phone, TV & power receptacles are shown on plan next to each other. Locate respective receptacles next to each other on site with no more B. than 1" seperating cover plates. Provide GFI type receptacles at kitchens, bathrooms, garages, exterior etc. as required by code. E. H/P HEAT/PHOTOELECTRIC SMOKE DETECTOR ELECTRICAL LEGEND (NOT ALL SYMBOLS REQUIRED FOR THIS PROJECT) RECESSED OR SURFACE DOWNLIGHT WALL MOUNTED LIGHT FIXTURE RECESSED FLUOR. LIGHT FIXTURE SURFACE FLUOR. LIGHT FIXTURE Aa Aa FIXTURE DESIGNATIONS: UPPER CASE - FIXTURE TYPE LOWER CASE - SWITCH DESIGNATION SHADING ON FIXTURE INDICATES EMERG. BATTERY BACKUP FLUORESCENT STRIP FIXTURE TRACK LIGHT AS NOTED OR SCHEDULED WALL WASHER POLE-MOUNTED FIXTURE POST (BOLLARD) FIXTURE CEILING OR WALL MOUNTED EXIT LIGHT EMERGENCY BATTERY LIGHTS DUPLEX RECEPTACLE @ 18" UNLESS NOTED DOUBLE DUPLEX RECEPTACLE @ 18" UNLESS NOTED SPECIAL OUTLET AS NOTED FLUSH FLOOR DUPLEX RECEPTACLE DUPLEX RECEPTACLE HALF-SWITCHED @ 18" UNLESS NOTED TELE-POWER POLE JUNCTION BOX IN FLOOR, CEILING OR IN WALL MULTI-OUTLET PLUG STRIP COMPUTER/TELEPHONE OUTLET IN FLOOR OR WALL CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING TELEPHONE BACKBOARD CIRCUIT HOMERUN CONDUIT RUN BELOW FLOOR OR GRADE CONDUIT STUB-UP - CAP & MARK LIGHT SWITCH AT 46" UNLESS NOTED SUBSCRIPTS: 2 = 2-POLE SWITCH 3 = 3-WAY SWITCH 4 = 4-WAY SWITCH K = KEY-OPERATED SWITCH TO = THERMAL OVERLOAD SWITCH P = SWITCH WITH PILOT LIGHT DIMMER SWITCH W/ WATTAGE MAGNETIC MOTOR STARTER DISCONNECT SWITCH TRANSFORMER GROUND PUSHBUTTON CONTROL STATION PHOTOELECTRIC CELL TIME SWITCH THERMOSTAT AT 60" UNLESS NOTED DIVISION 15 EQUIPMENT CIRCUIT BREAKER MOTOR OUTLET AUTOMATIC TRANSFER SWITCH FOOD SERVICE EQUIPMENT PC TS T ABBREVIATIONS - ABOVE COUNTER AC AFF - ABOVE FINISHED FLOOR - ABOVE FINISHED GRADE AFG - ALUMINUM AL - EMERGENCY EM - GROUND GND - GROUND FAULT INTERRUPTER GFI NIC - NOT IN CONTRACT NL - NIGHT LIGHT NTS - NOT TO SCALE UG - UNDERGROUND WP - WEATHER PROOF XFMR - TRANSFORMER +18" - MOUNTING HEIGHT TO CENTERLINE OF DEVICE AFF OR AFG FIRE ALARM SYSTEM FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM PULL STATION ALARM HORN OR SPEAKER COMBINATION HORN/STROBE OR SPEAKER/STROBE THERMAL HEAT DETECTOR H SMOKE/IONIZATION DETECTOR I PHOTOELECTRIC SMOKE DETECTOR P DUCT DETECTOR SPRINKLER SYSTEM FLOW SWITCH SPRINKLER SYSTEM TAMPER SWITCH STROBE SMOKE/FIRE DAMPER CONNECTION REMOTE INDICATOR LIGHT COMMUNICATION SYSTEM SPEAKER IN CEILING OR WALL VOLUME CONTROL AT 60" UNLESS NOTED MICROPHONE OUTLET IN FLOOR BOX OR WALL CALL-IN SWITCH PROGRAM BELL INTERCOM CLOCK AMPLIFIER TELEVISION OUTLET CONTACT DOOR SWITCH IN JAMB OR HINGE SECURITY SYSTEM KEY-OPERATED ACCESS SWITCH SURVEILLANCE CAMERA DISTRIBUTION EQUIPMENT SYMBOLS DISCONNECT SWITCH FUSES CIRCUIT BREAKER CURRENT TRANSFORMER TRANSFORMER METER CU - COPPER STEP LIGHT FACP M = MOTION-OPERATED SWITCH POP-UP RECEPTACLE - ELECTRICAL CONTRACTOR EC - AUTHORITY HAVING JURISDICTION AHJ - MECHANICAL CONTRACTOR MC - PLUMBING CONTRACTOR PC UTP - UNSHIELDED TWISTED PAIR - GENERAL CONTRACTOR GC - REFERENCE REF junction box, and run MC cable from junction box to device. CONDUCTOR SIZES AND TYPES: For sizes #1/0 AWG and larger, use coppper THW or aluminum XHHW. For sizes #1 AWG and smaller, use only copper wire with 600V insulation, types TW, THHN, or THW - stranded in sizes #8 and larger, solid in sizes #10 and smaller. Control wiring shall be #14, stranded. Use type THHN for wires entering or passing through fluorescent lighting fixtures. All motors shall be wired with copper conductors only. UNO - UNLESS NOTED OTHERWISE Provide tamper proof receptacles at all residential areas as required by code. F. 17. METERING A. EC shall coordinate whether or not meters require lever bypass with local utility and provide all meters with a lever bypass when required. CEILING MOUNT MOTION SENSOR Finish per owner or architect. of Drawn By: Checked By: DATE: ISSUE: PROGRESS AEC PROJECT #: VAIL SPA CONDOMINIUMS 710 W. LIONSHEAD CIRCLE 16057 07/25/16 www.aec-vail.com CMechanical, Electrical & Lighting Design Services Architectural Engineering Consultants Telephone: 970-748-8520 E G$Q 2IILFH ZLWK /(('Œ $FFUHGLWHG 3URIHVVLRQDOV PERMIT 07/29/16 51* #'% '.'%64+%#. 10'Ä.+0' &+#)4#/ '   11/16/16