HomeMy WebLinkAboutB16-0029_E2.0_1479389570.pdfTELDAT
W.S. W.S. W.S. W.S. W.S. W.S.
W.S. W.S. W.S. W.S. W.S.
W.S.
W.S.
W.S.
W.S.W.S.W.S.
4OUTL
2OUTL
4OUTL
CLOCK OUTLET
W.S.
W.S.
NOTE : ALL EXPOSED
CONDUIT
IN FITNESS ROOM TO BE RE-
ROUTED INTO WALLS
COMPUTER STATION
UP
DN
FD
FD
FD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD FD FD
FD
G
D E C F
HH
JJ
KK
ADA POOL LIFT
LANDSCAPE AREA
CONCPAVERS
CONCPAVERS
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
DOWN
METAL FENCE
METAL FENCE
POLE LIGHT
POLE LIGHT
POLE LIGHT
POLE LIGHT
POLE LIGHT
POLE LIGHT
STEP LIGHT
STEP LIGHT
STEP LIGHTSTEP LIGHTSTEP LIGHTSTEP LIGHT
STEP LIGHT
STEP LIGHT
STEP LIGHTSTEP LIGHT
STEP LIGHTSTEP LIGHT
STEP LIGHT
STEP LIGHT
STEP LIGHT
STEP LIGHT
STEP LIGHT
S
TEP LIGHT
STEP LIGHT
STEP LIGHT
STEP LIGHT
S
TEP LIGHT
STEP LIGHT
200 AMP
PANEL BELOW
NOTE:
ALL POOL AREA LIGHTING
TO BE WIRED TO VAULT 200
S TEP LIGHT
STEP LIGHT
F
ADA SAUNA
9
ADA STEAMROOM
10
ADA TOILET
12
URINAL
13
SHOWER
14
ADA SHOWER
15
MEN'S MASSAGE
16
42' - 9"
42' - 9"
42' - 9"
42' - 9"
RECESSED CAN
LIGHTING THROUGHOUT
RECESSED CAN
LIGHTING THROUGHOUT
RECESSED CAN
LIGHTING THROUGHOUT
EXISTING STRUCTURAL
COLUMN TO REMAIN
NOTE:
LOCATE EXISTING HVAC
SUPPLY & RETURNS,
TO REMAIN
EXISTING STRUCTURAL
COLUMN TO REMAIN SLOPE 1/8"/12"
MASTER
DIM
W. SCONCE.
HEATER
GFI
W. SCONCE.
W. SCONCE.
SAUNA
CONTROLS STEAM
LIGHT
CONTACTOR
CONTROL BOX
FOR SAUNA
GFI
GFI
STEAMER CLOSET
REMOVABLE
ACCESS PANEL
ON WALL FACE
TO 400 AMP
PANEL IN
WOMENS
LOCKER ROOM
EXIT
MOTION
ADA SAUNA
1
ADA STEAM
ROOM
2
ADA TOILET
3
TOILET
4
WOMEN'S
LOCKER ROOM
5
WOMEN'S
MASSAGE
6
ADA SHOWER
7
SHOWER
8
RECESSED CAN
LIGHTING THROUGHOUT
RECESSED CAN
LIGHTING THROUGHOUT
NOTE:
LOCATE EXISTING HVAC
SUPPLY & RETURNS,
TO REMAIN
EXISTING STRUCTURAL
COLUMN TO REMAIN
42' - 9"
42' - 9"
42' - 9"
42' - 9"
SLOPE 1/8"/12"
MASTER
DIM
W. SCONCE.
CONTACTOR
CONTROL BOX
FOR SAUNA
SAUNA
CONTROL
STEAMER
CONTROL
GFI
GFI
PANEL
BOX
GFI
HEATER
W. SCONCE.
GFI
GFI
W. SCONCE.
400 AMP PANEL
GFI
EMERGENCY
LIGHT
EXIT
MOTION
PANEL
P
PANEL
P1
TO
P-4
5 A, 120V
P-15
TO
P-3
5 A, 120V
P-15
TO
B-2 & P-2
10 A, 120V
P-13
TO
B-1 & P-1
10 A, 120V
P-11
AT MECHANICAL ROOM
CONNECT WS FIXTURES AT
CORRIDOR, POOL AND EXERCISE
ROOM TO EXISTING LIGHTING
CIRCUIT. EXISTING LIGHTING
CIRCUIT HAS (10) 150W FIXTURES
REMOVED, (19) 25 WATT
FIXTURES ADDED FOR A NET
POWER REDUCTION OF 1025
WATTS ON THE EXISTING
LIGHTING CIRCUIT.
PANEL
POOL
PROVIDE NEW CIRCUITS AT POOL PANEL AS FOLLOWS:
(2) 20A1P GFI CIRCUITS, POOL-40,42 FOR LANDSCAPE LIGHTING
(1) 20A1P CIRCUIT, POOL-30 FOR BOILER AND FRACTIONAL HP PUMPS
(1) 20A1P, POOL-32 FOR CONTROLLER
P1-19,21 SAUNA 8KW,
240V 50A2P
PROVIDE (3#6 CU, #10 CU
G)1"C & 50A2P BREAKER
P1-20,22 SAUNA 8KW,
240V 50A2P
PROVIDE (3#6 CU, #10 CU
G)1"C & 50A2P BREAKER
P1-44,46 STEAM
SHOWER 116 FLA,
208V 1P
PROVIDE (3#1/0 CU,
#6 CU G)1-1/2"C &
150A2P BREAKER
5A 120V CONTROL
P1-8
P1-1
P1-3
P1-4
P1-6
CONNECT MEN'S
LIGHTING TO P1-2
CONNECT WOMEN'S
LIGHTING TO P1-2
REUSE EXISTING CIRCUIT
REUSE EXISTING CIRCUIT
PROVIDE GFI PROTECTION FOR POOL LIGHTS
500W 120V 1P
WALL HTRS
P1-7
GENERAL NOTE:
REFERENCE THIS PLAN FOR POWER PLANNING ONLY. REFERENCE ARCHITECTURAL
PLANS FOR LIGHTING DESIGN.
POOL & SPA NOTES
1. COORDINATE GROUNDING WITH POOL/SPA CONTRACTOR TO ENSURE ALL METAL
PARTS WITHIN 5'-0" HORIZONTALLY OF POOL/SPA INSIDE WALLS ARE GROUNDED AND
APPROPRIATE BONDING LOCATIONS ARE ESTABLISHED. ALL ELECTRICAL
EQUIPMENT ASSOCIATED WITH THE POOL/SPA INCLUDING PANELBOARDS, CONDUIT,
JUNCTION BOXES, MOTORS, ETC. SHALL BE GROUNDED PER NEC 680.6.
2. UNDERGROUND WIRING SHALL NOT BE PERMITTED UNDER THE POOL/SPA OR THE
AREA EXTENDING 5'-0" HORIZONTALLY FROM THE INSIDE WALLS OF THE POOL/SPA
UNLESS NECESSARY TO SUPPLY ASSOCIATED EQUIPMENT IN THIS AREA PERMITTED
BY CODE. REF NEC 680.10.
3. ALL OUTLETS SUPPLYING POOL/SPA EQUIPMENT SHALL BE GFI PROTECTED. REF
NEC 680.21(C).
4. CIRCULATION/SANITATION MOTOR RECEPTACLES SHALL BE LOCATED A MINIMUM OF
10'-0" FROM THE INSIDE WALLS OF THE POOL/SPA. ALL OTHER RECEPTACLES SHALL
BE A MINIMUM OF 6'-0" FROM THE INSIDE WALLS OF THE POOL/SPA, MEASURED BY
CORD LENGTH. ALL 120V RECEPTACLES BEYOND 6'-0" AND WITHIN 20'-0" OF THE
POOL/SPA SHALL HAVE GFI PROTECTION. DISTANCES MEASURED BY CORD LENGTH.
REF NEC 680.22(A).
5. NO LIGHTS SHALL BE ALLOWED UNDER 5'-0" AFG WITHIN 5'-0" HORIZONTALLY FROM
THE INSIDE WALLS OF THE POOL/SPA. LIGHTS UNDER 5'-0" AFG BEYOND 5'-0" AND
WITHIN 10'-0" HORIZONTALLY SHALL HAVE GFI PROTECTION. REF NEC 680.22(B).
6. REFERENCE NEC 680.26 FOR DETAILED BONDING REQUIREMENTS. PROVIDE #8
GROUNDING CONDUCTORS TO BOND THE FOLLOWING, BUT NOT LIMITED TO THE
FOLLOWING:
6.1. CONDUCTIVE POOL SHELLS
6.2. POOL/SPA PERIMETER SURFACE WITHIN 3'-0" HORIZONTALLY FROM INSIDE
WALLS OF POOL/SPAS
6.3. ALL METALLIC COMPONENTS OF THE POOL/SPA STRUCTURE
6.4. WET NICHE LIGHT FIXTURE SHELL/MOUNTING BRACKETS
6.5. ASSOCIATED METAL FITTINGS ATTACHED TO THE POOL/SPA STRUCTURE
6.6. ALL METAL PARTS OF POOL/SPA EQUIPMENT AND ELECTRICAL EQUIPMENT
6.7. ALL FIXED METAL PARTS SUCH AS METAL SHEATHED CABLES/RACEWAYS, METAL
PIPING/AWNINGS/FENCES/WINOW AND DOOR FRAMES, ETC.
6.8. POOL WATER WITH A MINIMUM CONDUCTIVE SURFACE AREA OF 9 SQ. IN.
7. FOR ALL SPA INSTALLATIONS OTHER THAN SINGLE-FAMILY DWELLINGS, A CLEARLY
LABELED EMERGENCY SHUTOFF SWITCH SHALL BE PROVIDED WITHIN SIGHT OF AND
ADJACENT TO THE SPA, A MINIMUM OF 5'-0" AWAY FROM THE SPA, TO SHUT OFF ALL
CIRCULATION AND JET PUMPS. REF NEC 680.41.
of
Drawn By: Checked By:
DATE: ISSUE:
PROGRESS
AEC PROJECT #: VAIL SPA
CONDOMINIUMS
710 W. LIONSHEAD CIRCLE
16057
07/25/16
www.aec-vail.com
CMechanical, Electrical & Lighting Design Services
Architectural Engineering Consultants
Telephone:
970-748-8520
E
G$Q 2IILFH ZLWK /((' $FFUHGLWHG 3URIHVVLRQDOV
PERMIT
07/29/16
51* #'%
.'8'.
'.'%64+%#.
2.#0
'
NORTH
LEVEL 1 ELECTRICAL PLAN
SCALE: 3/16" = 1'0"
11/16/16