HomeMy WebLinkAboutElec Load.pdfELECTRIC LOAD SUMMARY Client Name: Berglund Architects, LLC Load Tab Project Name: Reimers Residence Project No: 201614 Date: March 1, 2016 3090 Booth Creek Drive, Vail, CO TYPE SQ. FT. Residential 6229 VA/S.F. OR QTY.VA TOTAL NOTES GENERAL LIGHTING LOAD GENERAL LIGHTING 3 18,687 18,687 Per NEC 220.82(B)(1) SMALL APPLIANCE 2 1,500 3,000 Per NEC 220.82(B)(2) LAUNDRY 2 1,500 3,000 Per NEC 220.82(B)(2) TOTAL 24,687 APPLIANCE LOADS Per NEC 220.82(B)(3) & (4) REFRIGERATOR 1 1,440 1,440 COFFEE MACHINE 1 4,500 4,500 DISHWASHER 1 1,440 1,440 DISPOSAL 2 1,127 2,254 RANGE HOOD 1 960 960 RANGETOP POWER SUPPLY 1 1,440 1,440 MICROWAVE 1 1,440 1,440 DRYER 0 5,000 0 GAS DRYERS DUAL OVEN 1 8,900 8,900 BOILERS 3 250 750 PUMP-1,2,5 3 30 90 PUMP-3,4,10 3 528 1,584 PUMP-6A,6B 2 178 356 PUMP-7 1 9 9 PUMP-8,11 2 1,176 2,352 PUMP-9 1 1,656 1,656 HEAT TAPE 10 750 7,500 OUTDOOR HEATERS 5 1,000 5,000 MOTORIZED SHADES 18 500 9,000 HUMIDIFIERS 3 1,900 5,700 STEAM GENERATORS 2 12,000 24,000 APPLIANCE TOTAL 80,371 GEN. LTG AND APPLIANCE LOAD 105,058 DEMAND FACTOR NOTES 100% FIRST 10,000 VA 10000 Per NEC 220.82(B) 40% FOR REMAINDER OF LOAD 38023 Per NEC 220.82(B) TOTAL 48,023 AIR CONDITIONING & COOLING Per NEC 220.82.C DRYER BOOSTER FAN 1 71 71 EF-1-2-3-4 4 45 180 HUMIDIFICATION FAN-1-2 2 98 196 SUPPLY FAN-1 1 71 71 FAN COIL-1 1 2,400 2,400 1.5 HP Motor FAN COIL-2,3,4 3 480 1,440 CONDENSING UNIT-1 1 6,900 6,900 HEAT PUMP-2 1 7,360 7,360 WINEROOM COOLING UNIT 1 1,500 1,500 TOTAL 20,118 OVERALL TOTAL (VA)68,141 Gen. Ltg & Appl. Load + AC 284 AMPS @ 240V, 1-PH 400-AMPS SELECTED SINGLE PHASE FEEDER BASED ON NEC OPTIONAL LOAD CALCULATION