HomeMy WebLinkAboutLoad Calcs_11.pdf Electrical load calculation for 22 west meadow drive unit #250 4/22/16
General load
1100 sq. ft @ 3 v.a. per sq. ft. = 3,300 v.a.
2 small appliance circuits = 3,000 v.a.
dishwasher = 1 ,200 v.a.
range = 8,500 v.a.
laundry circuit = 1,500 v.a.
dryer = 6,000 v.a.
total 23,500 v.a.
10 k.v.a. @ 100% = 10,000
13,500 v.a. @ 40% = 5.400
total general load 15,400 v.a.
heat provided by common building boiler =0 v.a.
15,400 v.a. @ 240 v. = 64.16 amps.
calculated load of 64.16 amps on existing 100 amp service.
scope of new work.
Lighting remodel of guest bath & master bath. Replace existing vent fans & lighting with
high efficacy fixtures. Add 5 (total) high efficacy fixtures to guest bedroom, master
bedroom & great room. Replace & re-locate electrical panel from closet to to allow for
the use of arc-fault breakers.