HomeMy WebLinkAboutB16-0149_6E1.0_1478897846.pdfGENERAL NOTES: 1. . VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK. 2. A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER. THE ARCHITECT WILL BE ISSUE ANY INTERPRETATION OR CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED ABOVE. B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE WORKING DRAWINGS AND SPECIFICATIONS. 3. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTS REQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS. 4. REVIEW ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND OTHER DRAWINGS PRIOR TO BID. 5. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE LANDSCAPE ARCHITECT AND OWNER'S REPRESENTATIVE. 6. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE OF COLORADO, AND NATIONAL CODES AND ORDINANCES. 7. PROVIDE PERMITS AND INSPECTIONS REQUIRED. 8. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER. 9. PROVIDE RECORD DRAWINGS TO OWNER. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC. 10. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE. 11. PROVIDE ENGRAVED NAMEPLATES ON PANELBOARDS, DISCONNECT SWITCHES, ETC., INDICATING EQUIPMENT DESIGNATION (OR DESIGNATION OF EQUIPMENT SERVED), AND VOLTAGE. 12. PANEL DIRECTORIES SHALL BE REMOVABLE. SUBMIT PROPOSED SCHEDULE OF DIRECTORIES TO OWNER FOR APPROVAL. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALL BE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS. 13. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS. 14. VERIFY EXACT LOCATIONS OF EXISTING AND NEW UNDERGROUND UTILITIES, PIPING, AND RACEWAY SYSTEMS PRIOR TO TRENCHING. PROVIDE NECESSARY TRENCHING, BACKFILL, EXCAVATION, SUPPORTS, SERVICE FEEDERS (CONDUIT AND/OR WIRE), PULLBOXES, TRANSFORMER PADS, SAWCUTTING AND PATCHING, CONCRETE/PAVING, ETC. REQUIRED. BACKFILL TRENCHES TO 90 PERCENT COMPACTION AND PATCH TO MATCH EXISTING. CONTRACTOR SHALL OBTAIN AND VERIFY EXACT UTILITY COMPANY DRAWINGS AND REQUIREMENTS. 15. ALL UNDERGROUND CONDUIT/RACEWAY SHALL BE BURIED AT LEAST 24” BELOW GRADE, PER NEC. 16. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN. 17. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED. 18. ALL EMPTY RACEWAY SYSTEMS SHALL HAVE A NUMBER 12 PULLWIRE OR EQUAL, AND SHALL BE IDENTIFIED AT ALL JUNCTION, PULL AND TERMINATION POINTS, USING PERMANENT METALLIC TAGS. TAG SHALL INDICATE INTENDED USE OF CONDUIT, ORIGINATION, AND TERMINATION POINTS OF EACH INDIVIDUAL CONDUIT. 19. INSTALL ALL MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BE BROUGHT TO THE ARCHITECT/ENGINEER'S ATTENTION PRIOR TO INSTALLATION. 20. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO COST TO OWNER. 21. WIRE SHALL BE COPPER, 75 DEGREE CELSIUS RATED FOR GENERAL USE. FOR HID FIXTURES AND WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL BE COPPER, MINIMUM 90 DEGREE CELSIUS RATED. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30 DEGREE CELSIUS AMBIENT. CONDUCTOR AMPACITY SHALL BE DERATED FOR HIGHER AMBIENT INSTALLATIONS. 600 VOLT ALUMINUM WIRE AND CABLE IN SIZES 1/0 AND LARGER MAY BE SUBSTITUTED FOR COPPER ON SERVICES AND FEEDERS IF AMPACITY IS EQUAL TO OR GREATER THAN COPPER, AND VOLTAGE DROP IS EQUAL TO OR LESS THAN COPPER AND SHALL BE TERMINATED AT SWITCHES, LUGS, CIRCUIT BREAKERS, ETC., WITH MAC-ADAPT SERIES "MPT" MACHINE COMPRESSION ADAPTERS OR EQUAL. 22. SPLICES IN EXTERIOR PULLBOXES AND MANHOLES SHALL BE MADE WATERPROOF USING "SCOTCHCAST" SPLICE KIT OR APPROVED EQUAL. SEAL ENDS OF CONDUITS AND DUCTS WITH "DUCTSEAL" OR APPROVED EQUAL. 23. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION. 24. CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT. 25. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY. 26. WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL OTHER ELECTRICAL APPARATUS SHALL BE LISTED AS SUITABLE FOR 75 DEGREE CELSIUS. 27. RECEPTACLES WHICH ARE SHOWN WALL MOUNTED ON THE ELECTRICAL DRAWINGS ON WALLS WHICH, ON THE ARCHITECTURAL DRAWINGS AND ELEVATIONS, ARE SHOWN AS GLASS OR PARTITIONS SHALL BE FLUSH FLOOR DUPLEX RECEPTACLES MOUNTED ADJACENT TO BASE OR WALLS. 28. PULLBOXES, CABINETS, ETC. MOUNTED ON THE EXTERIOR AT GRADE LEVEL, SHALL BE WEATHERPROOF TYPE WITH HINGED LOCKABLE COVERS SECURED WITH TAMPERPROOF SCREWS. 29. CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETE GROUNDING SYSTEMS OF INDIVIDUAL UNIT PANELS AND COMBINATION MAIN/METER SECTIONS. 30. MECHANICAL DRAWINGS FOR LOCATION OF MECHANICAL EQUIPMENT. PROVIDE SERVICE TO, AND CONNECT EQUIPMENT AS REQUIRED. 31. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC RACEWAYS. RACEWAYS IN SLAB-ON-GRADE OR BELOW GRADE SHALL BE SCHEDULE 40 PVC. TRANSITIONS FROM BELOW TO ABOVE GRADE SHALL BE WITH RIGID STEEL ELBOWS WITH P.V.C. JACKET OR APPROVED EQUAL PROTECTION. EMT FITTINGS SHALL BE MALLEABLE IRON OR STEEL. CONNECTORS SHALL BE INSULATED THROAT TYPE. 32. NON-METALLIC AND FLEXIBLE METAL CONDUITS SHALL HAVE A CODE- SIZED COPPER GROUNDING CONDUCTOR. INCREASE CONDUIT SIZE AS REQUIRED. 33. FINAL CONNECTIONS TO MOTORS, AND OTHER VIBRATING EQUIPMENT SHALL BE WITH SEAL TITE FLEX AND APPROVED FITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR MECHANICAL EQUIPMENT. T M PANEL 'P1' SCALE: 1 ELECTRICAL ONE-LINE DIAGRAM NOT TO SCALE EXTERIOR LIGHTING CONTROL DIAGRAM - LCP NO SCALE 120V A PC TC ILC LIGHTLEEDER 4 LIGHTING CONTROL PANEL WITH ASTRONOMICAL CLOCK FUNCTION PHOTOCELL SYSTEM TIME CLOCK - 365 DAY/ASTRONOMICAL TIME CLOCK WITH NON-VOLATILE MEMORY. LIGHTING BRANCH CIRCUIT TO LIGHTING FIXTURES METER MAIN MOUNTED ON UNISTRUT FRAME NEXT TO UTILITY TRANSFORMER. PROVIDE COMBINATION 200 AMP, 240 VOLT, 1-PHASE METER MAIN (ALL-IN-ONE) WITH 80 AMP SUB-FEED CIRCUIT BREAKER TO FEED PANEL 'P1' AND (5) 20 AMP 1-POLE BREAKERS FOR EXISTING STREET LIGHTING AND BUS STOP CIRCUITS. GFCI DUPLEX RECEPTACLE DUPLEX RECEPTACLE; HALF SWITCHED JUNCTION BOX WALL MOUNTED JUNCTION BOX DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER C DIVISION 15 EQUIPMENT POWER CONNECTION FUSED DISCONNECT NON FUSED DISCONNECT PULL BOX PUSH BUTTON TRANSFORMER PANELBOARD OR LOADCENTER CONTACTOR METER ONE-LINE DIAGRAM SYMBOLS CIRCUIT HOMERUN CONDUIT RUN CONDUIT RUN BELOW GRADE CONDUIT UP CONDUIT DOWN DISCONNECT SWITCH FUSE CIRCUIT BREAKER CURRENT TRANSFORMER POTENTIAL TRANSFORMER METER GROUND ST SHUNT TRIP COLD WATER GROUND CONNECTION BUILDING STEEL GROUND CONNECTION TIME CLOCK PHOTO-CELL LIGHTING FIXTURE SYMBOLS RECESSED LIGHTING FIXTURE WALL MOUNTED LIGHT WALL MOUNTED UP-LIGHT RECESSED STEP LIGHT FLUORESCENT STRIP LIGHT WALL MOUNTED LINEAR FLUORESCENT LIGHT FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT SWITCH LIGHTING CONTROL SYMBOLS EXTERIOR POLE MOUNTED LIGHT EXTERIOR POST (BOLLARD) MOUNTED LIGHT DAYLIGHT PHOTO SENSOR DL WALL OCCUPANCY SENSOR/SWITCH OCCUPANCY SENSOR - WALL MOUNTED S S O PC TC M C T PB N -- J J ABBREVIATIONS POWER SYMBOLS SINGLE RECEPTACLE DUPLEX RECEPTACLE DOUBLE DUPLEX RECEPTACLE NOTE: ALL SYMBOLS SHOWN ON LEGEND ARE NOT NECESSARILY USED. ELECTRICAL SYSTEMS LEGEND OS OS OCCUPANCY SENSOR - CEILING MOUNTED NOTES:  LIGHT LINEWEIGHT INDICATES EXISTING.  HATCHED AREAS INDICATE DEMOLITION.  'C' ADJACENT TO A DEVICE INDICATES MOUNTING ABOVE COUNTERTOP. AFC AFF AFG AHJ - ABOVE FINISHED CEILING - ABOVE FINISHED FLOOR - ABOVE FINISHED GRADE - AUTHORITY HAVING JURISDICTION AL - ALUMINUM AWG AP - ACCESS POINT - AMERICAN WIRE GAUGE BFG - BELOW FINISH GRADE C - CONDUIT CKT - CIRCUIT CT - CURRENT TRANSFORMER (E) - EXISTING EM - EMERGENCY FBO GFI GRD GC - FURNISHED BY OTHERS - GENERAL CONTRACTOR - GROUND FAULT CIRCUIT INTERRUPTER - GROUND IAW IN ACCORDANCE WITH - NIC (N) NEW - NOT IN CONTRACT - NL NIGHT LIGHT - NTS NOT TO SCALE - OC ON CENTER - UG UNO W V UNDERGROUND - UNLESS NOTED OTHERWISE - VOLT - WATT - WP WEATHERPROOF - +18" DEVICE ABOVE FINISH FLOOR (VERIFY W/ ARCH ELEVS) MOUNTING HEIGHT TO CENTERLINE OF - C 3-#1/0 AL, #6 GRD. 2"C 3-#250 AL, 2-1/2"C NO SCALE BOLLARD LIGHT DETAIL B TYPE B1 BOLLARD LIGHT FIXTURE 1/2"ø x 15" HOT DIP GALVANIZED STEEL ANCHOR BOLTS AT 90° POURED CONCRETE. GROUND LUG. 1" PVC CONDUIT GRADE 125 AMP, 240/120 VOLT, 1-PHASE, 24 SPACE LOADCENTER. 20 FT. #8 AWG BARE COPPER GROUND WIRE COILED UNDER FIXTURE BASE. 3'-9" 2'-0" 1'-4" INTERCEPT EXISTING STREET LIGHTING AND BUST STOP CIRCUITS AND RECONNECT TO NEW SERVICE. PANEL: P1 VOLTAGE: 120/240V, 1PH, 3W MINIMUM BUS: 125 LOCATION: RESTROOM BLDG. MAIN: 80/2 CB MOUNTING: RECESSED MINIMUM AIC: 10,000 NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO. A B POLE TRIP A B TRIP POLE A B 1 500 E BASEBOARD HEATER 1 20 + 20 1 E BASEBOARD HEATER 500 2 3 1500 E UNIT HEATER WOMENS 1 20 + 20 1 E UNIT HEATER MEN'S 1500 4 5 120 E LIGHTING CONTROLS 1 30 + 30 1 E WH-1 WATER HEATER 2000 6 7 540 R JANITOR/WATER REC. 1 20 + 20 1 E WOMENS RECEPT. 180 8 9 320 L EXTERIOR LIGHTING 1 20 + 20 1 R PICNIC SHELTER 410 10 11 200 L RESTROOM LIGHTING 1 20 + 20 1 SPARE 12 13 410 R MENS RECEPT. 1 20 + 20 1 SPARE 14 15 SPACE + 20 1 SPARE 16 17 SPACE + SPACE 18 19 SPACE + SPACE 20 21 SPACE + SPACE 22 23 SPACE + SPACE 24 LOAD TYPE PANEL TOTAL FEED THRU TOTAL SUBFEED TOTAL FEEDER SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES: A. (L) LIGHTING 520 520 125% 650 B. (R) RECEPTACLES 1360 1360 NEC 220 1360 C. (LM) LRG. MOTOR 0 0 25% 0 D. (M) MOTORS (ALL) 0 0 100% 0 E. (E) EQUIPMENT 6300 6300 100% 6300 SPECIFIC NOTES: (A) APPLIANCES 0 0 0 0 (1) PANEL TOTAL (KVA): 8.3 (2) (3) PANEL TOTAL (A): 35 (4) (5) C DATE # DESCRIPTION ISSUE DATE: SHEET NUMBER REVIEWED: PROJECT NUMBER: DRAWN: 1 REVISIONS 5431 2 3 4 5 6 7 A B C D E REDEVELOPMENT 2900 MANNS RANCH ROAD VAIL, COLORADO C O P Y R I G H T D E S I G N W O R K S H O P, I N C. F 8 9 1 2 3 4 5 6 7 8 9 CONSTRUCTION DOCUMENTS March 25, 2016 BOOTH CREEK PARK 1309 ELKHORN DRIVE. VAIL, COLORADO. 81657 970.479.2158 ALBUQUERQUE | AVON | DENVER | FORT COLLINS 303.278.3820 www˛bgbuildingworks˛com Project No. 9667.00 Copyright 2016 ELECTRICAL COVER SHEET E1.0 BAS MAS 05/23/16