HomeMy WebLinkAboutB16-0149_6M2.1_1478907782.pdf4" PLUMBING VENT THROUGH SIDEWALL, 10' ABOVE
GRADE. PROVIDE WITH BIRD SCREEN. TERMINATE
PER 2009 IPC RQT'S.
1
FLAG NOTES:
SCALE: 1 RESTROOM MECHANICAL PLAN
1/4" = 1'-0"
P1
P5
P5
P3
P2
P2
P2
P5
P1
P4
P7
WATER SERVICE.
RE: B/M2.1 FFI.
DOMESTIC WATER SERVICE,
I.E.=8316' A.S.L., MINIMUM 4'
BELOW FINAL GRADE. RE:
CIVIL FOR CONTINUATION.
P8
MOUNTED HIGH
ON WALL SHELF. RE:
A/M2.1 FFI.
P6
W
W
CW
FD
WC
WC
LAV
DF
DF
LAV
MS
FS
FD
UR
FD
WC
WCO
4" W EXIT
WCO
SCALE: 2 WASTE & VENT ISOMETRIC
NONE
SCALE: 3 DOMESTIC WATER ISOMETRIC
NONE
W
WW
W
4"W EXIT, I.E.=8316'
A.S.L., MINIMUM 4'
BELOW FINAL GRADE.
RE: CIVIL FCT.
WC
WC H/C HB
LAV
EH
(EXTERIOR)
DF
MS
LAV
UR
WC
CW
WATER ENTRY
LOW POINT, MEN'S RESTROOM
SIDE. SLOPE PIPES TO DRAIN
VALVE.
LOW POINT, WOMEN'S
RESTROOM SIDE. SLOPE
PIPES TO H/C HOSEBIB.
SLOPE FROM HIGH POINT ABOVE
WH TO HOSE END DRAINS.
WH
WOMEN'S
RESTROOM
BLGD.
MEN'S
RESTROOM
BLGD.
2"
2-1/2"
1
1
IN WALL
16" A.F.F.
1
1
IN WALL
16" A.F.F.
P9
PIPING THROUGH UN-HEATED ROOF TO BE INSULATED
TO EXTERIOR PIPING RQT'S.; PROVIDE WITH HEAT TAPE
THROUGH ENTIRE EXTERIOR RUN. EXTEND HEAT TAPE
AND EXTERIOR-LEVEL INSULATION 12" INTO INTERIOR
HEATED SPACE
4"
2"
2"
4"
4"
1"
1
-
1/4
"
1-1/2"
1-1
/
4"
1"
1"
1"
3
/4"
1"
1. CEILING COORDINATION OF ALL MEP SYSTEMS
(LIGHTING, DUCTWORK, ELECTRICAL, FIRE
PROTECTION, ETC.) MUST BE COMPLETED BY THE
CONTRACTOR PRIOR TO THE START OF ANY
INSTALLATIONS.
2. AVOID ROUTING DUCTWORK OR PIPING OVER OR
ELECTRICAL PANELS; MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTINGS WITH DIV. 16 CONTRACTOR.
3. VERIFY ALL EQUIPMENT ACCESS WITH
MANUFACTURER AND ARCHITECT.
4. PROTECT PIPING ROUTED ALONG COLUMNS, WALLS,
ETC. FROM DAMAGE AS NECESSARY WITH CAGES.
COORDINATE WITH ARCHITECT.
5. PEX PIPING SHALL NOT BE ALLOWED TO PENETRATE
FIRE BARRIERS WHERE FIRE CAULKING IS REQUIRED.
6. EXHAUST FAN TO OPERATE UPON DETECTION OF
OCCUPANCY BY ELECTRICAL-PROVIDED OCCUPANCY
SENSOR FOR COMBINED LIGHTING AND EXHAUST
CONTROL. COORDINATE CONTROLS WITH
ELECTRICAL AND LIGHTING. EXHAUST FAN TO
CONTINUE TO OPERATE 10 MIN (ADJ) AFTER LAST
DETECTED OCCUPANCY.
7. PIPING ON EXTERIOR WALLS OR PRE-CAST
CONCRETE WALLS TO BE ROUTED IN FRAMED WALL
ON INTERIOR SIDE OF INSULATION.
8. ALL PIPING SHALL BE ROUTED AS HIGH AS POSSIBLE
IN THE CEILING SPACE. UTILIZE JOIST SPACE WHEN
POSSIBLE, ESPECIALLY WHERE CROSSING OTHER
PIPES, DUCTS, AND ELECTRICAL.
9. REFER TO THE PLUMBING FIXTURE CONNECTION
SCHEDULE FOR PIPE SIZES TO INDIVIDUAL FIXTURES.
10. NOT ALL REQUIRED CLEANOUTS ARE NECESSARILY
SHOWN ON THESE PLANS. PROVIDE CLEANOUTS ON
WASTE, VENT AND STORM PIPING AS REQUIRED BY
CODE AND FOR REASONABLE MAINTENANCE BASED
ON ACTUAL FIELD INSTALLATION. COORDINATE
LOCATIONS WITH ARCHITECT/ENGINEER.
11. INSTALL THERMOSTATIC MIXING VALVES, ASSE 1070
LISTED, AT EACH PUBLIC HANDWASHING
LAVATORY/SINK. SIZE TO MATCH HW PIPE SIZE.
12. WINTERIZATION: ALL FREEZE-PRONE SYSTEMS SHALL
BE CONSTRUCTED TO FACILITATE COMPLETE
SEASONAL DRAIN DOWN.
HVAC NOTES:
EAGLE RIVER WATER ENTRANCE DIAGRAM
M
NO SCALE
DOMESTIC WATER SERVICE
SHUT-OFF VALVE.
1-1/2" CW TO BLDG.
1-1/2" REDUCED PRESSURE TYPE
BACKFLOW PREVENTER.
CERTIFIED TESTER TO TEST.
1" WATER METER WITH
REMOTE READOUT.
PRESSURE REDUCING
VALVE, WATTS 223, 3/4"
SET @ 60 PSI
CW SERVICE ENTRY
FROM UTILITY.
:
1. WATER METER AND BACKFLOW
PREVENTER MUST BE MOUNTED
HORIZONTALLY.
2. METER, SHUT-OFF, AND BYPASS
LOCATED IN METER PIT. BACKFLOW
PREVENTER LOCATED IN WATER
ENTRY CLOSET AT MEN'S RESTROOM.
METER
BYPASS.
D
PIPING DIAGRAM
DOMESTIC WATER HEATER
FLOOR
D
S
NO SCALE
SUPPORT FROM STRUCTURE.
TEMPERING VALVE.
COLD WATER
SUPPLY.
DIAPHRAGM TYPE EXPANSION
TANK. AMTROL ST-8.
PIPE RELIEF VALVE INDIRECT
TO DRAIN PAN. TERMINATE
1-1/2" ABOVE DRAIN PAN.
SHELF WITH SAFE PAN, DRAIN
PIPE FROM SAFE PAN TO
EXTEND & SPILL 6" ABOVE
MOP BASIN OR FLOOR DRAIN.
HW TO MEN'S.
WATER
HEATER
MOP BASIN
3/4" (ELECTRIC)
SLOPE CW PIPE SERVING
BUILDING BACK TO
DRAIN-DOWN VALVE WITH
HOSE END LOCATED IN
WATER ENTRY CLOSET
FOR SEASONAL BUILDING
DRAINAGE.
HW TO WOMEN'S.
VENT HIGH POINTS.
METER
PIT
ENTRY
CLOSET
A
B
WATER HEATER DRAIN POINT.
C
DATE
#
DESCRIPTION
ISSUE DATE:
SHEET NUMBER
REVIEWED:
PROJECT NUMBER:
DRAWN:
1
REVISIONS
5431
2 3 4 5 6 7
A
B
C
D
E
REDEVELOPMENT
2900
MANNS
RANCH
ROAD
VAIL,
COLORADO
C O P Y R I G H T D E S I G N W O R K S H O P, I N C.
F
8 9
1 2 3 4 5 6 7 8 9
CONSTRUCTION
DOCUMENTS
March 25, 2016
BOOTH
CREEK
PARK
1309 ELKHORN DRIVE. VAIL, COLORADO. 81657
970.479.2158
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9667.00 Copyright 2016
RESTROOM
MECHANICAL PLAN
M2.1
08/03/16