HomeMy WebLinkAboutB16-0149_8E2.0_1478899756.pdfSCALE:
SITE ELECTRIAL PLAN
1" = 30'
1. LIGHTING SHALL BE CONTROLLED BY LIGHTING
CONTROL PANEL (LCP). TIMECLOCK/PHOTOCELL
ON/OFF FUNCTION.
2. FEEDER, CIRCUIT, AND CONDUIT ROUTING IS
INTENDED TO INDICATE GENERAL ROUTING AND
CONFIGURATION. CONTRACTOR SHALL FIELD
COORDINATE EXACT ROUTING TO AVOID AREAS OF
TREE PROTECTION.
NOTES:
B1
B1
B1
B1
B1
B1
B1
NEW ELECTRICAL UTILITY
TRANSFORMER BY HOLY
CROSS ENERGY.
TO PANEL 'P1' LOCATED
IN JANITOR'S CLOSET 103.
RE: SHEET E2.1 FOR
PANEL LOCATION.
RE: 1/E1.0 FOR FEEDER
AND CONDUIT SIZING.
T
2-#10, #10 GRD. 1"C
ELECTRICAL METER/MAIN
PANEL (ALL-IN ONE)
MOUNTED ON UNISTRUT
FRAME.
B1
B1
RESTROOMS
SITE LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING LUMENS LAMPS INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER
SPECIFIC
NOTES
QTY TYPE
B1 45" HIGH CORTEN PATHWAY BOLLARD WITH 30W LED
LAMP 3000K MOUNTED CONCRETE BASE
SURFACE 556 -- LED AS SUPPLIED,
3000K
30 120-277 LOUIS POULSEN BYS-30W LED
GENERAL NOTES:
A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE
PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND
SPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING.
SPECIFIC NOTES:
(1)
(2)
EXISTING SERVICE SERVING STREET
LIGHTS AND BUS SHELTER TO BE
REMOVED. CIRCUITS TO BE RECONNECTED
TO NEW SERVICE.
INTERCEPT EXISTING
STREET LIGHT AND BUS
STOP CIRCUITS AND
CONNECT THEM TO NEW
PANEL.
P1-9
REMOVE EXISTING BRANCH CIRCUIT
CONDUCTORS AND ABANDON EXISTING
RACEWAY, SERVING EXISTING BRANCH
CIRCUITS BEING RE-ROUTED TO NEW
ELECTRICAL SERVICE.
J
120 VOLT POWER FOR
IRRIGATION CONTROLLER.
CIRCUIT TO P1-10 , CIRCUIT
SERVING RECEPTACLES AT
PICNIC SHELTER.
C
DATE # DESCRIPTION
ISSUE DATE:
SHEET NUMBER
REVIEWED:
PROJECT NUMBER:
DRAWN:
1
REVISIONS
5431
2 3 4 5 6 7
A
B
C
D
E
REDEVELOPMENT
2900
MANNS
RANCH
ROAD
VAIL,
COLORADO
C O P Y R I G H T D E S I G N W O R K S H O P, I N C.
F
8 9
1 2 3 4 5 6 7 8 9
CONSTRUCTION
DOCUMENTS
April 8, 2016
BOOTH CREEK PARK
1309 ELKHORN DRIVE. VAIL, COLORADO. 81657
970.479.2158
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9667.00 Copyright 2016
SITE
ELECTRICAL
PLAN
E2.0
BAS MAS
08/19/16