HomeMy WebLinkAboutload calcs_35.pdf1956 W. Gore Creek Dr. Proposed Load Calculation 6/22/16: 3247 sq. ft.@ 3VA Kitchen appliance X 2 Dishwasher Disposal Refrigerator Microwave Oven Coo kt op Range Washer x 2 Dryer x 2 Water Heater Hot Tub General Load Sub-Total ist lOkVA @ 100% Remainder @ 40% Total Net General Load Furnace @ 100% Heat pumps @ 100% Heat Tape @ 100% Total 1 9,741 VA 3,000 VA 1,200 VA 1,200 VA 1,500 VA 1,200 VA 6,500VA 9,600 VA 10,500 VA 3,000 VA 10,000 VA 4,500 VA 9 600 VA 71,541 VA 10,000 VA 24,617 VA 34,617 VA 3,000 VA 3,000 VA 3,000 VA 43,617 VA _,- Calculated Load for Service Existing service size 200 Amps 43,617 VA I 240 volts= 182 Amps 2