Loading...
HomeMy WebLinkAboutB16-0247_A-01_1478903818.pdfGeneral Notes: The following architectural documentation is being provided as a design assist for a design build process with the contractor. Minimal required documentation has been provided for code and building compliance. It is the contractor's responsibility to comply with all applicable local, state and national building codes, ordinances, regulations and all other authorities having jurisdiction pertaining to this project. All contractors, subcontractors, shall be responsible for their role in the construction of the project and shall be held responsible for adherence to practical knowledge, implementation of the content and described intent of the documents. All manufactured assemblies, articles, materials, and equipment shall be applied, installed, erected, used, cleaned, tested and conditioned in strict accordance with the responsible manufacturers' recommendations. The contractor-owner shall field verify all site conditions, materials and dimensions. The following structural documentation is being provided as a signed, sealed and dated set of structural construction documents as required for the construction of a duplex residence in the State of Colorado. Reference Structural documents and specifications for all design loads and criteria. Due to unknown existing conditions structural documents are to be coordinated with architectural documents in the field. Prior to the start of construction, verify design loads with governing codes and site conditions. Verify and check with local building agencies for applicable wind, seismic, snow and other special loading conditions. I. GENERAL REQUIREMENTS The contractor shall be responsible for grading and adherence and coordination with an open pit soils inspection to occur prior to the start of construction and performed by a licensed geotechnical engineer. Finish grading shall be a minimum of 6" below any untreated material and sloped 6" in 10' (minimum) or as recommended by the soil's report away from structure. The contractor shall perform excavation and grading according to common construction practices and methods to the lines, grades and elevations of the site documents and in accordance with any work prescribed by any Civil Engineer or Landscape Architect consultant that may be retained for the project by the owner. Provide site preparation, work and coordination as specified by the soil's report and Geotechnical engineer. II. SITEWORK: All concrete work and materials shall be per the structural construction documents or as designed and specified by qualified others and/or the responsibility of the contractor. III. CONCRETE: All masonry work and materials shall be per the exterior finish notes and as finally approved on the mock-up during construction. All masonry work and materials are the responsibility of the contractor as designed and specified by qualified others. IV. MASONRY: All metal work and materials shall be per the details, exterior finish notes and as finally approved by Owner on the mock-up during construction. All metal work and materials are the responsibility of the contractor or as designed and specified by qualified others. All metal work, including structural steel, shall be per the structural construction documents and specifications. V. METALS: All woods and plastics work and materials shall be per the exterior finish notes and as finally approved on the mock-up during construction. All woods and plastics work and materials are the responsibility of the contractor or as designed and specified by qualified others. All woods and plastics shall be per the structural construction documents and specifications. VI. WOODS AND PLASTICS: All roofing material shall be per the exterior finish notes and as finally approved on the mock-up during construction. All thermal and moisture protection work and materials are the responsibility of the contractor or as designed and specified by qualified others. VII. THERMAL AND MOISTURE PROTECTION: All doors and windows shall be per the exterior finish notes and as finally approved on the mock-up during construction. All doors and windows, including proper insulation and installation, are the responsibility of the contractor or as designed and specified by qualified others. VIII. DOORS AND WINDOWS: Contractor to verify all windows for compliance with all energy and building code compliance, including but not limited to, tempering, U and R values, egress, etc. Gypsum drywall as required by governing codes. All other finishes the responsibility of the contractor or qualified other. IX. FINISHES: Not a part of this contract and the responsibility of the contractor or qualified other. X. SPECIALTIES: Not a part of this contract and the responsibility of the contractor or qualified other. XI. EQUIPMENT: Not a part of this contract and the responsibility of the contractor or qualified other.. XII. FURNISHINGS: Not a part of this contract and the responsibility of the contractor or qualified other. XIII. SPECIAL CONSTRUCTION: Not a part of this contract and the responsibility of the contractor or qualified other. XIV. CONVEYING SYSTEMS: Not a part of this contract and the responsibility of the contractor or qualified other. XV. MECHANICAL: Not a part of this contract and the responsibility of the contractor or qualified other. XVI. ELECTRICAL: Additional Notes: Stairs to have a minimum width of 36"; a minimum tread depth of 10"; a minimum riser height of 4"; a maximum riser height of 7 3/4"; and a minimum headroom clearance of 6'-8" above nosing of treads. Stairs shall conform to R311.5.8 and IBC1009. I. STAIRS Handrails - Stairs having four (4) or more risers shall have a minimum of one (1) graspable handrail 34" to 38" above nosing of treads. Handgrip portion of handrails shall not be less than 1 1/4" nor more than 2" in cross sectional dimension. The handgrip portion of the the handrails shall have a smooth surface with no sharp corners. Handrails projecting from a wall shall have handrail end to be returned to walls, or terminate in newel posts. Balusters on open side of stairways to be spaced such as not to permit a 4" sphere to pass through. Handrails shall be continuous between landings ( can be interrupted by a newel post at turn). II. HANDRAILS Guardrails - Guardrail to be a minimum of 36" above floor with ballisters to be spaced so as not to permit a 4" sphere to pass through. III. GUARDRAILS Fireplaces - Provide a manual shut-off valve within 4' of the gas appliance unit (not in firebox, or unit) that is accessible to the room in which the fireplace is located. Provide ouside combustion air as required per the manufacturer's specifications. Installation instructions for the listed gas fireplaces must be on site for inspection to verify clearances to combustible framing and/or trim, etc. IV. FIREPLACES Firestop all interconnections between concealed vertical and horizontal spaces (soffits), and between stair stringers, and the openings between chimney chases, and all attic spaces. Provide fire blocking within sleeper-type flooring systems so that no area exceeds 100 square feet. Fireblock material may be 2" nominal lumber, gypsum drywall, etc. securely fastened in place loose - filled insulation is not acceptable. V. FIREBLOCKING If a super-insulated roof is not constructed provide sufficient, adequate roof and attic ventilation as prescribed by code. Provide continuous screened soffit vents and ridge venting as specified by the Developer/ Owner-General Contractor. The roof/attic ventilation shall be as described by the IBC 1/150th of the square footage of the attic area, 50% (one-half) of which shall be in the lower soffit area, and the remaining balance - 50% (one-half) of which shall be in the upper most part (high area) of the roof/attic. Each rafter space shall be vented. VI. ROOF VENTILATION Provide sufficient, adequate crawl space cross-ventilation at 1 sq. ft. of venting per 150 sq. ft. of the crawl space area. VII. CRAWL SPACE VENTILATION N/A VII. CRAWL SPACE VENTILATION Drawing List: A-00 Cover Sheet V-00 Topographic Survey A-01 Information Sheet A-02 Graphic GRFA Calcs AX-1.1 Existing Lower & Main Level Plan AX-1.2 Existing Upper Level & Roof Plan AX-2.1 Existing Elevations AX-2 .2 Existing Elevations AD-1.1 Lower Level Demo Plan AD-1.2 Main Level Demo Plan AD-1.3 Upper Level Demo Plan AD-1.4 Roof Demo Plan AD-2.1 Demo Elevations AD-2.2 Demo Elevations C-1 Grading and Drainage Plan (By Civil Engineer) AL-1.0 Landscape Plan A-1.1 Proposed Lower Level Plan A-1.2 Proposed Main Level Plan A-1.3 Proposed Upper Level Plan A-1.4 Proposed Roof Plan A-2.1 Proposed Elevations A-2.2 Proposed Elevations A-3.1 Building Section & Section Detail A-4.1 Large Scale Section A-4.2 Large Scale Section AR-1.1 Lower Level RCP/MEP AR-1.2 Main Level RCP/EMP RA-1.1 Radon Plan S1 - Foundation Plan & Details S2 - Main Level Framing S3 - Upper Level Framing S4 - Roof Framing General Contractor to locate all existing utilities and identify conflicts prior to the start of any construction and/or work. Any plumbing on an exterior wall to be relocated or insulated sufficiently to avoid freezing. VIII. MISCELLANEOUS Majority of the exterior building envelope from exterior membrane to interior drywall, including insulation is remaining unless evidence of something detrimental such as mold is discovered in the small areas being uncovered. A monitored fire detection system will be provided for Unit D per Vail Fire and Emergency service's specifications. FIRE PROTECTION Existing Residential S.F. (Not GRFA): 1,831 S.F. Existing Garage S.F. (Not GRFA): 537 S.F. Proposed Residential S.F. (Not GRFA): 2,850 S.F. Proposed Garage S.F. (Note GRFA): 480 S.F. SQUARE FOOTAGE Open Hole Soils Test Required by licensed third party. Structural steel and welding inspections required by licensed third party. Blower door test not required as not new construction. Air balancing test not required as there is not a forced air system. SPECIAL INSPECTIONS 2015 International Building Code 2015 International Residential Code 2015 International Existing Building Code 2012 Plumbing Code 2015 International Mechanical Code 2012 International Fuel Gas Code 2015 International Fire Code 2015 International Energy Conservation Code 2014 National Electric Code 2015 Amendments located in Ordinace No. 14, Series 2015 APPLICABLE DESIGN CODES A-01 Project Information Sheet K 06.13.2016: BuildingPermit 06.04.2016: Revised Pricing 03.31.2016: TOVDRB Conceptual 05.12.2016: Review 05.02.2016: TOVDRB FINAL Sheet No: Project No: 1501.00 Sheet Title: Sheet No: Revisions: Issue Dates: Seal La Dolce Vail CO 81657 (970) 390.1429 4284 Columbine Drive, Unit E annefgunion@yahoo.com Architects, llc THE KORCH RESIDENCE 4284 Columbine Drive Unit D VAIL, COLORADO 08/05/16