HomeMy WebLinkAboutE16-0138 load calcsViola Residence
Load Calculation 795 Potato Patch Drive #B, Vail CO A-Phase Electric, LLC
www.aphaseelectricllc.com
General Lighting and Receptacle Demand Load:
1914 sq. ft. x 3VA = 5742
1,500 VA x 2= 3000
1,500 VA x 1 = 1500
Total connected load:10,242
3,000 VA @ 100% =3,000
VA @ 35% =2,534.7
887.145
Total general lighting and
Receptacle demand load:3,887
Range demand load:
12,000VA 8,000
Dryer Load:
5,000
Fixed appliance load:
Dishwasher 1.2 kva 1 1,200
Garbage disposal .8 kva 1 800
Washer 1.2 kva 1 1,200
Microwave 1.2 kva 1 1,200
Steam shower 9.6 kva 0 0
Hot tub 12 kva 0 0
Total fixed appliance load: 4,400
Heating load:
boiler 0.2 1 200
heat tape 4 kva 1 4,000
Total heating load: 4,200
25% of largest motor:1,200
Viola Residence
Load Calculation 795 Potato Patch Drive #B, Vail CO A-Phase Electric, LLC
www.aphaseelectricllc.com
Totals:
General lighting and receptacles: 3,887
Range: 8,000
Dryer: 5,000
Fixed appliance: 4,400
Heating: 4,200
25% of largest motor: 1,200
Total:VA 26,687
AMPS 111.20
Installed Service Size: 200A single phase