HomeMy WebLinkAboutB16-0294_E1_1478900386.pdfPROJECT: Bridge St Locker rm ENGINEER: BW-MH PROJECT #: VOLTAGE: 120/208V,3P, 4W MOUNTING: Recessed MAINS: 225A MLO TYPE: PER SPECIFICATIONS AIC: 22K PHASE PHASE DESCRIPTION A B C BKR P CIR CIR P BKR A B C DESCRIPTION Ice Maker 1400 20 2 1 2 1 20 900 Coffee 1400 3 4 1 20 350 AMP Southeast Beer Cooler 0 20 1 5 6 1 20 350 Recept 720 20 1 7 8 1 20 350 AMP Lights 0 20 9 10 1 20 1100 AMP Lights 1100 20 1 11 12 1 30 4500 FA strobe FCV 650 20 1 13 14 0 Lights FCV 650 20 1 15 16 1 20 720 Recept Lighting 20 1 17 18 1 20 1260 Recept Lighting 1100 20 1 19 20 1 20 720 Recept Lighting 1000 20 1 21 22 1 20 1080 Recept Lighting 900 20 1 23 24 1 20 1080 Recept Lighting 1200 20 1 25 26 1 20 1260 Recept Lighting 1200 20 1 27 28 1 20 180 Recept Lighting 1200 20 1 29 30 1 20 0 0 33 34 1 20 0 0 40 0 LOAD CALCULATION SUMMARY NOTE: Add New CB to exisitng Panel as shown CALCULATED POWER FACTOR: 0.97 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS APPLIANCES 7550 21 5663 16 LIGHTING & RECEPT. 15820 44 7487 21 MECHANICAL 4100 13 4800 16 KITCHEN OVEN & DRYER 0 0 0 0 TOTAL 27470 78 17950 52 PANEL A (*Existing/ *New ) 8/1/2016 08/23/16 PROJECT: Bridge St Locker rm ENGINEER: MH_BW PROJECT #: VOLTAGE: 120/240V, 3P, 4W MOUNTING: Rec MAINS: 225A MLO TYPE: PER SPECIFICATIONS AIC: 22K PHASE PHASE DESCRIPTION A B BKR P CIR CIR P BKR A B C DESCRIPTION 0 1 2 1 20 0 Lights Register 1450 20 1 3 4 1 20 0 Lights Register 1400 Lights Register 360 20 1 7 8 1 20 1400 Lights Ice Mech 1200 20 1 9 10 2 20 700 Beer Cooler Coffee 20 1 11 12 0 Refig 900 20 1 13 14 1 20 360 Water Heater Refig 900 20 1 15 16 1 20 360 Water Heater Dishwasher 30 2 17 18 1 20 Lights 600 19 20 1 20 360 Recept Recept 360 20 1 21 22 1 20 360 Recept Recept Sump pump 550 30 2 25 26 1 20 360 Lights 550 27 28 1 20 360 Water Heater Sump pump Sump pump 550 31 32 1 20 500 Roof Fan Keg Comp 1250 20 1 33 34 2 20 250 Roof Fan Keg Comp Recept 360 20 1 37 38 3 100 5983 Sub Breaker Recept 360 20 1 39 40 5983 Bath Recept LOAD CALCULATION SUMMARY NOTE: CALCULATED POWER FACTOR: 0.95 CONNECTED LOAD CONNECTED AMPS DEMAND LOAD DEMAND AMPS APPLIANCES 0 0 LIGHTING & RECEPT. 15190 42 7267 20 MECHANICAL 12100 39 12412.5 40 KITCHEN OVEN & DRYER 17950 50 17950 50 TOTAL 45240 131 37629 110 PANEL B (*Existing/ *New ) 8/1/2016 08/23/16