Loading...
HomeMy WebLinkAboutB16-0359_Conductor Sizing_1478908806.pdfPage 3 of 4 9/1/2016 P.O. Box 7627, Avon, CO 81620 | P: 970.306.4233 | F: 866.403.3485 | www.activeenergies.com Conductor Sizing Pass Thru Box from Optimizers to Inverter (combined strings): 23A x 1.25 = 28.8A #10 THWN-2 Table 310.16 40A No conduit fill adjustment Table 310.15 (B)(3)(a) Temperature correction factor Table 310.15 (B)(2)(b) 40A x .77 = 30.8A Inverter to Disconnect to Service Panel: Nameplate maximum continuous output current: 32A @ 240V 32A x 125% = 40A 210.19 (A)(1) #8 THWN-2 Table 310.16 50A (75ºC column) No temperature correction factor No conduit fill adjustment Overcurrent Protection Device 40A fused disconnect Per Manufacturer Specification Conductors may be oversized for voltage drop 09/22/16