Loading...
HomeMy WebLinkAboutB16-0359_Line Diagram_1478908807.pdfPage 4 of 4 9/1/2016 P.O. Box 7627, Avon, CO 81620 | P: 970.306.4233 | F: 866.403.3485 | www.activeenergies.com 4 #10 PV Wire 1# 6G Bare Cu Conductors in Free Air Inverter w/ Integrated DC Disconnect SolarEdge SE7600A-US NEMA 3R / Arc Fault / Rapid Shutdown Max AC Output: 32A @ 240V Located on south side of home DC Grounding Electrode Conductor solid bare #6 Cu per NEC 250.66(C) Service Panel south side of home Line Diagram Stadler Residence 2703 Cortina Lane Vail, CO 81657 9.6 kW Utility Interactive Photovoltaic System Modules: 96 SunTegra STS-100M-B4U Voc = 15.32V Isc = 8.72A Optimizers: 32 integrated SolarEdge P300 2 String X 16 Modules/Inverter Inverter: SolarEdge SE7600A-US Operating Voltage: 350V Operating Current: 23A Max System Voltage: 500V Max Output Current: 30A Tilt Angle: 26.57º Array Azimuth: 150° Production: 13,756kWh/yr Notes: - See Calculation Sheet for conductor sizing. - All conductors are copper unless otherwise noted. - Inverter listed (UL-1741) to de- energize upon loss of utility voltage per NEC 690.61. - Inverter has integral ground-fault protection per NEC 690.5 - 240V 1 Phase Service Panel rating of 200A (bus rating 200 amp and 200 Main disconnect) to accommodate 40A + 200A = 240A supply (up to 120% of connected power sources from residential installations per NEC 690.64(B)(2)) Array mounted on roof 96 Canadian Solar CS6P-265P-SD Solar Panels 32 integrated SolarEdge P300 DC Optimizers On south side of home Pass-Thru Box Located on roof Placard on meter and main panel stating ”Photovoltaic System Connected” per Holy Cross specifications 60A, 40a fused Disconnect adjacent to meter +/-40' ¾" C EMT/FMC 2 #10 THWN-2 1 #10 Ground +/-10' ¾" C EMT/PVC/FNMC/NM-B 3 #8 THWN-2 1 #10 Ground ... Backfeed Fuses: 40A 2p 240v 40A 1 2 3 4 5 6 7 9 8 46 47 48 ... 49 50 51 52 53 54 55 57 56 94 95 96 09/22/16